Manual Button does not work:

   

 For the Manual switch to work there must be at least one successful temperature 

transmission from the roof module after the unit is plugged in and switched on.  
Transmissions require strong sunlight.

”00" in the display - no signal is being received. 

 

 There may be insufficient Sun.  Or the distance between the transmitter and SunSwitch 

may be too great [if so, then the transmitter must be moved closer.]

The 6-digit numbers don’t match. 

 

 The two units may be mismatched or SunSwitch might be receiving signal from another 

SunSwitch transmitter close by.   Ring 1800 BATHER for a solution to this issue.

“01" is an internal fail-safe procedure.

  

 If SunSwitch does not receive any transmissions for a set period of time it will institute a 

count down from its current temperature down to “01" and switch the pump off.

Other Odd Numbers in the Screen:

   

  If the roof transmitter has not sent a successful signal, the receiver will continue to 

recall the last piece of information recorded on start-up or resetting.  For example, the 
last recorded roof temperature or signal strength may remain the same for hours until a 
successful transmission has been received.

TROUBLESHOOTING.

Sunbather Wireless SunSwitch

Operating Instructions.

NO BATTERIES and now with exclusive 

 mode.

ENERGY SAVING

Start-up Diagnostic:  

All lights, displays and non-volatile memory are checked on 

start-up. “EE” will flash in the display if a fault is found.

Pool Sensor Fault Diagnosis:  

“Er” display indicates a faulty pool sensor.  Cold 

o

sensor is non-polar 4.7K Ohm at 25 C thermistor with these temp/resistance ohm 

o

o

o

o

readings:  10 C - 9535, 20 C - 5902,  30 C - 3770,  40 C - 2480.

o

o

Electrical Specifications:    

   T on 6 C.       T off at 2 C.  Max relay overload 230V-10A

Readout Calibration:  

To fine tune the temperature readings hold TEMP SET button 

down for 10 seconds until the display flashes. Pressing the up or down arrow buttons will 
change the units base settings one degree each press. While in standby, the display reads 
the last recorded temperature.  

Service Lock-Out Mode:  

Hold AUTO & MAN buttons down for 10 seconds (LO 

appears in display).   Controller will remain in Lock-Out for 2 hours before reverting to 
normal automatic operation.