![Sun Oracle Sun Storage 2500-M2 Arrays Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/sun-oracle/sun-storage-2500-m2-arrays/sun-storage-2500-m2-arrays_site-preparation-manual_1393115014.webp)
8
Site Preparation Guide • August 2011
Altitude
lists the altitude specifications for the array.
Airflow and Heat Dissipation
Transit gradient
68˚F (20˚C) per hour maximum
Maximum dew point
79˚F (26˚C)
Maximum gradient
10% per hour
TABLE 2-6
Altitude Ranges for the Controller Tray
Environment
Specification
Operating
100 ft (30.5 m) below sea level to 9840 ft (3000 m) above sea level
Storage
100 ft (30.5 m) below sea level to 9840 ft (3000 m) above sea level
Transit
100 ft (30.5 m) below sea level to 40,000 ft (12,000 m) above sea level
TABLE 2-7
Airflow and Minimum Clearance
Position
Clearance
Front
30 in. (76 cm)
Back
24 in. (61 cm)
TABLE 2-8
Power and Heat Dissipation for the Controller Tray
Component
KVA
Watts (AC)
Btu/Hr
Controller modules with two power-fan
modules and 12 drives
0.400
399
1366
TABLE 2-5
Humidity (noncondensing)
Parameter
Specification