2-2
Sun Fire B1600 System Chassis Hardware Installation Guide • August 2003
The vertical mounting hole pattern of the rack must conform to the standard
dimensions given in
and shown in
FIGURE 2-1
EIA/RETMA Mounting Hole Pattern Dimensions
2.2
Service Access
The bottom of lowest of the five system chassis must be mounted no lower than
2.95 in. (75 mm) above the bottom of the rack or cabinet to enable removal and fitting
of the orange sacrificial lifting handle.
Ensure that units or cables above a Sun Fire B1600 blade system chassis do not
protrude beyond the front face of the system chassis to enable proper airflow.
Access to the front and back of the Sun Fire B1600 blade system chassis is required
for installation and system maintenance.
Note –
If you are installing the system chassis into a cabinet that has a door, you
might need to swing the door back 180 degrees, or remove the door altogether.
TABLE 2-1
Mounting Hole Pattern Dimensions
Standard
Pattern
IEC297/EIA310/
RETMA (RU)
Repeating pattern of 5/8
in.
(15.7 mm)
, 5/8
in.
(15.7 mm)
,
1/2
in.
(12.7 mm)
IEC917/ETSI (SU)
Constant pitch of 0.98
in.
(
25 mm)
1U
1/2 in. (12.7 mm)
1/2 in. (12.7 mm)
5/8 in. (15.7 mm)
5/8 in. (15.7 mm)
Содержание Sun Fire B1600 Administration
Страница 6: ...vi Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Страница 10: ...x Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Страница 14: ...xiv Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Страница 30: ...2 4 Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Страница 77: ...Chapter 5 Connecting and Managing Cables 5 9 FIGURE 5 5 Attaching the Data Network Cables to the Network Ports ...
Страница 79: ...Chapter 5 Connecting and Managing Cables 5 11 FIGURE 5 7 Attaching the Network Management Cables ...
Страница 82: ...5 14 Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Страница 94: ...6 12 Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Страница 98: ...Index 4 Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...