Multi-Circuit Standard Ambient Temp Sensing Digital Controller

  

Changing Set-Point Values

     

To change the Heater-On and Low-temperature Cutout set-point values, follow the
steps below with the controller powered and the rocker switch set to AUTO:

1)

Press the SET button once to display the current Heater-On set-point value
(displays temperature in tenths of degrees). A red indicator light under “out1" will
appear.

2)

Press the UP or DOWN arrow button to adjust the value. Hold button to scroll.

3)

Press the SET button again to display the current Low-Temp Cutout set-point
value. A red indicator light under “out2" will appear.

4)

Press the UP or DOWN arrow button to adjust the value. Hold button to scroll.

5)

Press the SET button again to return to the normal operating mode (will display
the current sensed temperature with no decimal point.)

     

Low-Temp Cutout can effectively be avoided by setting its value below the lowest
expected ambient temperature (for example: -50.0.)

NOTE: Multi-Circuit controllers default start-up temperature is set to 36

E

 and

should be adjusted to actual field needs. 

Alarm Buzzer and Error Messages

     

If the alarm buzzer sounds, it can be silenced by simultaneously pressing the SET and
Down buttons. The alarm message will continue until condition is corrected. 

Common Error Messages

     

1)   “ErP” = Error of the probe not shown on display
2)   “ooo” = Open sensor (one or both sensor leads are not connected).
3)   “- - -” = Shorted Sensor (direct short between sensor leads).

Содержание 4CDC+

Страница 1: ... 120Vac to 277Vac and EverClear 812 and 822 120Vac to 277Vac self regulating heater cables by energizing multiple 4 8 or 12 individual branch circuits via adjustable control values as set on the temperature controller The Controller provides a set point for on off operation as well as a low temp cutout of the circuits The low temp cutout shuts the system off when temperatures are so cold that no s...

Страница 2: ...A 4 12 rating so they may be mounted indoors or outdoors typically near the circuit breaker panel Each branch circuit must be protected by a ground fault protection device per the NEC A 120Vac protected circuit is required to energize the controller The ambient sensor is mounted outdoors in a shaded location representative of minimum ambient conditions typically on the north side of a building and...

Страница 3: ...ndicator light under out2 will appear 4 Press the UP or DOWN arrow button to adjust the value Hold button to scroll 5 Press the SET button again to return to the normal operating mode will display the current sensed temperature with no decimal point Low Temp Cutout can effectively be avoided by setting its value below the lowest expected ambient temperature for example 50 0 NOTE Multi Circuit cont...

Страница 4: ...2 13 30A 30mA ground fault equipment protection circuit breakers to be provided for each circuit by installer typical A1 A2 X1A X2 X1A X19 X19 X19 X19 X1 X1A X19 X2 Typical A1 A2 Ground Bar Sized as Required xxx Turn off all power before servicing panel or branch circuits CAUTION HIGH VOLTAGE DANGER Note Locate sensor on the coldest exterior side of structure usually north under the overhang and n...

Отзывы: