MAINTEN
ANCE
As with an
y mechanical system, a dedicated maintenance program will prolong
the life of the equipment, and maintain its’ optimum performance. We recom-
mend at least two (2) full inspections and cleanings per year under normal
operating conditions, and more, if circumstances warrant it.
Ser
vice Should Include:
• Cleaning of screens protecting the outside hoods
• Cleaning the core – core assembly is made up of 3 cores. To access the
core, remove service panels and slide core half way out. Wash core(s)
protruding from the cabinet with water and / or a mild cleaning solution.
Push core through to the other side of the cabinet and repeat the procedure
to clean the other side of the core. In many cases, only a vacuuming of the
core surface is required.
• Always ensure that cores are installed correctly. Refer to labels referring
to “Core This Way Up” and “Air Filters This Side”.
• Inspect filters and replace as necessary.
• Wipe down drain pans and inside of the cabinet using a mild disinfectant.
• Ensure condensate drain has free flow of moisture.
• Inspect blowers and electrical disconnect panel.
• Confirm operation.
MO
TORS
Appl
y 4 – 5 drops of oil to the ports at each end of the motor every 12 months
is required. We strongly recommend that the motor ( s ) should be oiled once
every year in order to extend its’ life. USE S.A.E. 20W NON – DETERGENT
OIL. Do not “ over oil “, as this may damage the motor. Depending on the
HRV specifications, the motors may have sealed bearings that do not require
oiling. An inspection of the motors will identify if oiling is required.
21
2500DD-Install-ENG 1/17/06 5:56 PM Page 21
Содержание SHRV2500DD
Страница 5: ...5 ...
Страница 6: ...6 ...
Страница 22: ...22 WIRING DIAGRAM SHRV2500DD ...
Страница 23: ...SHRV2500 SERVICEABLE PARTS 23 CORE THIS WAY UP FILTERS THIS SIDE ...
Страница 27: ...27 Summeraire Mfg 2040 Fisher Drive Peterborough Ontario Canada K9J 6X6 SHRV 2500DD INSTALL ENG 12 05 ...