1 General

1.1 

Application areas

ATTENTION 

The maximum allowable temperature of the medium pumped:

 

Sanimax R 202 & R 202C, Sanimax MF 154 & 324 = 40 °C

 

Sanimax MF 154HW = 80 °C

The Sanimax with Sulzer submersible pump has been designed for the dewatering of buildings below the sewer 

level. It is suitable for faecal-free effluent in accordance with EN 12056/DIN 1986-100.

 

 

The Sanimax is a compact wastewater lifting unit which can be installed under or beside the wastewater source 

at floor level.

In accordance with the regulations for effluent lifting stations, pumping of effluent containing faecal 

matter, or the pumping of flammable or explosive fluids, is not allowed with these lifting stations.

Examples of substances that should not be allowed into the tank:
• 

Aggressive fluids such as acids, lyes (caustic soda) or salts.

• 

Flammable liquids such as petrol, oil or phenols.

•  Commercial and agricultural waste.
• 

Solid substances such as ash, rubbish, glass, sand, fibrous material, cardboard, paper towels, textiles, 

diapers, kitchen waste, coffee grounds, shredder waste.

• 

Liquid substances that can harden, such as bitumen, cement, lime, lime milk (whitewash), mortar, potato 

starch, grease (edible oils and fats), synthetic resin, synthetic resin emulsion, tar, paint residues.

• 

Cleaning agents, disinfectants.

•  Abrasive material.  

ATTENTION As 

with all electrical devices, this product may fail due to operating errors, absence 

of mains voltage, or even a technical defect. Such a failure may result in medium 

or water escaping. If damage may occur due to the specific usage, measures 

are required to avoid such damage arising. In this respect, taking account of the 

conditions in question, particularly use of an off-grid alarm system, use of an 

emergency generator, and provision of an additional and appropriately connected 

second unit are to be considered. 

Sanimax R 202 & R 202C, Sanimax MF 154 & 324

This product is only suitable for removing clear and dirty water up to a water temperature of 40 °C or 

up to a maximum of 60 °C during short-term operation. 

 I

f the system is fed water from units such as washing machines, then the maximum water temperature 

could be exceeded if the device is not equipped with discharge cooling or if this is not switched on, 

e.g. in order to save energy. 

 This may cause damage to the pump or the pumping system. In such case Sulzer will not accept any 

guarantee or warranty claim. 

 I

f necessary, contact the manufacturer of the device or devices provided for connection (e.g. washing 

machines) to obtain information on how to switch on discharge cooling. If not possible then we 

recommend installation of the Sanimax MF 154HW model (see below).

 Our systems are checked in accordance with EN 12050 LGA and conform to the current standards. 

Also note that the maximum inlet temperature to the public sewer system is 35 °C and that you must 

ensure that the water is cooled accordingly.

Sanimax MF 154HW

Sanimax MF 154HW is designed for the pumping of high temperature liquids up to a maximum of 80 °C.

All inflow and discharge pipework to the unit must be temperature resistant accordingly 

and is the 

responsibility of the customer. 

Содержание ABS MF 154

Страница 1: ...www sulzer com Lifting Station Type ABS Sanimax 1051 00 15970278EN 08 2019 en Installation and Operating Instructions ...

Страница 2: ...ting unit 7 5 Installation 8 5 1 Cable inlet 8 5 2 Discharge Line 8 5 2 1 Installation example Sanimax R202 and R202 C 9 5 3 Electrical connection 9 5 4 Washing machine connection 10 5 5 Hand wash basin connection 10 5 6 Shower connection only used with Sanimax R202 R202 C 10 6 Maintenance 11 6 1 General maintenance hints 11 6 2 Cleaning the lifting unit 11 Lifting Station Type ABS Sanimax R 202 M...

Страница 3: ...result in medium or water escaping If damage may occur due to the specific usage measures are required to avoid such damage arising In this respect taking account of the conditions in question particularly use of an off grid alarm system use of an emergency generator and provision of an additional and appropriately connected second unit are to be considered Sanimax R 202 R 202C Sanimax MF 154 324 ...

Страница 4: ...er backwash level is the maximum possible water level in the public sewer network Information on this can be obtained from your Local Authority If the backwash level has not been fixed by the Local Authority then the surface level of the roadway at the connection point is taken to be the level If the effluent does not give rise to foul odours then a water tight connection tank fitted with a lid is...

Страница 5: ...head MF 154HW 3 m 4 1 Design of the lifting unit 1 2 3 4 5 6 7 1053 01 1 2 3 4 5 6 7 1054 01 Figure 2 Sanimax R202 R202 C Figure 3 Sanimax MF 1 Discharge line 5 Vertical inflow in tank cover 2 Non return valve 6 Tank venting with integral odour filter and overflow protection 3 Synthetic tank triangular shape 7 Sealed cable entry 4 Wastewater pump with level control Supplied as standard Sanimax R20...

Страница 6: ... brought above the backwash loop 180 bend and then allowed to flow by gravity into the collection sewer or channel regulations EN 12056 and DIN 1986 100 The discharge line should be laid so that it is not affected by frost The discharge line should not be connected to a downpipe No other discharge lines or inflows should be connected to the discharge line Select a suitable tank port for the discha...

Страница 7: ... Electrical connection Before operating have a qualified person check that all required electrical protective measures are present Earthing neutral line earth leakage circuit breakers etc must correspond to the regulations of your local Electricity Supply Provider and must function perfectly ATTENTION Cross section and voltage drop of the power line must correspond with the local Electricity Suppl...

Страница 8: ...nnecting a shower one of the lower tank ports should be used The height difference between the floor of the shower and the floor of the tank of the lifting unit should be to EN DIN in accordance with the illustration In the case of a greater distance between the Sanimax R202 R202 C and the shower basin it is necessary to make an addition to allow for the recommended fall for gravity flow The showe...

Страница 9: ...ll bearings together with monitoring devices ensure optimum reliability of the pump provided that installation and usage is in accordance with our operating instructions Should a problem arise do not improvise but ask your Sulzer Service Centre for assistance In order to ensure a long running life regular checks and care are recommended The Sulzer Service Organisation will be glad to advise you on...

Страница 10: ...10 ...

Страница 11: ...11 ...

Страница 12: ...Sulzer Pump Solutions Ireland Ltd Clonard Road Wexford Ireland Tel 353 53 91 63 200 Fax 353 53 91 42335 www sulzer com ...

Отзывы: