3.3 Stopping the dryer
a) Use the switch to stop the dryer.
b) Stop the dryer 2 minutes after shutting down the air compressor or interrupting
the air flow to the dryer.
Avoid allowing compressed air to enter the dryer when the dryer is
switched off or when it is in an alarm situation which stops the refrigeration
compressor.
3.4 Operation
S
The dryer operates automatically. It is factory set for a dew point of 37
˚
F (3
˚
C)
(ISO 7183, Part 2) and therefore requires no further calibration.
S
Do not exceed the machine’s design limits, bypass excess air flow and check the
unit model and/or installation.
S
For maximum performance from your dryer, follow the maintenance schedule de-
scribed in Chapter 4.
S
The sound pressure level recorded for these dryers 40 inch (at 1 metre) from the
machine in free field conditions is less then 50 dB(A) (
models SR
--
5 --- SR
--
15
),
55 dB(A) (
models SR
--
25 --- SR
--
100
)
Fig. 5 shows the Dryer’s refrigeration and air circuits.
4 Maintenance
Before accessing live electrical parts
, disconnect the power supply to the
dryer using disconnect switch QS or disconnect the cable connections.
SAFETY DEVICES
SK
overload protector
HP
high pressure switch
(installed on models SR
--
50 --- SR
--
100)
COMPRESSOR TYPE
HERMETIC, PISTON
(single phase)
N.B.:
Always use original spares supplied by the manufacturer.
Failure to do so renders the manufacturer not liable for incorrect unit operation.
4.1 Preventive maintenance
For optimum performance from your dryer follow the periodic maintenance sched-
ule described below.
WEEKLY
CONDENATE DRAIN
WEEKLY
CONDENATE DRAIN
Verify that the condensate drain is draining correctly.
MONTHLY
COMPRESSOR
Make sure the compressor head temperature is below 140
˚
F (60
˚
C)
MONTHLY
Make sure the compressor head temperature is below 140 F (60 C)
when running. If this is not the case consult Chapter 7.
EVERY 4 MONTHS
CONDENSER
Remove any dust from the condenser fins.
COMPRESSOR
EVERY 4 MONTHS
COMPRESSOR
Make sure compressor power consumption complies with data plate
specifications.
YEARLY
CONDENSATE DRAIN
Completely disassemble the drain and clean all its components (see
Fig. 8 or separate manual, according to installed drain type).