User Manual US-EN
SR 10-480 AC
02250246-045 R02
41
Subject to EAR. ECCN EAR99 and related export control restrictions.
If installed
:
the TS safety
temperature switch
was triggered.
Check which of the following reasons is responsible for the triggering:
Excess thermal load
–
re-establish the standard operating conditions.
The inlet air is too hot
–
re-establish the nominal conditions.
The ambient temperature is too high or the room ventilation insufficient
–
ensure sufficient
ventilation.
The condenser unit is dirty
–
please clean it.
The fan does not work
–
see the corresponding point.
The hot-gas bypass valve needs to be re-adjusted
–
contact a specialist for refrigerating
plants to have the nominal calibration re-established.
There is a leak in the refrigeration cycle
–
please contact a SULLAIR service technician.
Reset the temperature switch by manually pushing the button on the temperature switch
–
check
the perfect functioning of the dryer.
The TS temperature switch is defective
–
replace it.
Electronic instrument
DMC15 The first and
the last led of display
are flashing
syncronous.
Verify the electric wiring of T1 DewPoint probe.
The T1 DewPoint probe is faulty - replace it.
The electronic instrument is faulty - replace it.
Electronic instrument
DMC15 The
yellow led is flashing
SR 10-100
- Verify the electric wiring of T2 fan control probe.
SR 10-100
- The T2 fan control probe is faulty - replace it.
SR 125-480
- Verify the electric wiring of resistance on terminal 1 and 2
The electronic instrument is faulty - replace it.
Electronic instrument
DMC15 The first led of
the display is flashing
DewPoint too low - see specific point.
The T1 DewPoint probe is faulty - replace it.
The electronic instrument is faulty - replace it.
Electronic instrument
DMC15 The last led of
the display is flashing
DewPoint too high - see specific point.
The T1 DewPoint probe is faulty - replace it.
The electronic instrument is faulty - replace it.
12.3 Recommended spare parts
Spare parts list is printed on a dedicated sticker applied inside the dryer. On this sticker each spare part is identified
with its ID Number and related Spare Part Number. Here below the cross-reference table between ID Numbers and
exploded drawings Ref. with their description and quantity installed in the dryers.
NOTE:
To order the recommended spare parts or other elements, the data on the name plate must be
indicated.