4: Installation
ShopTek™ ST4, ST5, ST7, ST11, ST15 Three-phase 60 Hz User Manual
88292018-236 R00
34
Subject to EAR, ECCN EAR99 and related export control restrictions.
4.2
Ventilation and cooling
• ShopTek compressors require a three foot (one
meter) clearance around their perimeter.
• The location should be free from standing
water.
• Clean air should be supplied to the compres-
sor, free from exhaust and paint fumes, dust,
metal particles, or caustic chemical vapors.
• Hot exhaust air should be vented out of the
area to prevent its recirculation back into the
compressor’s cooling system.
• Ducting or some other means must be used to
ensure that hot exhaust air is vented away from
the compressor if the compressor’s housing
has minimal overhead clearance.
Table 4-1: Ventilation requirements
Model
Ventilation air required
cfm
m
3
/hr
ST4
612
1040
ST5
612
1040
ST7
612
1040
ST11
1471
2500
ST15
1471
2500
NOTE
Remove the red shipping straps/shipping studs
before operating the drive assembly. See
and
Figure 4-2
.
NOTE
Housing the compressor in an inadequately ven-
tilated enclosure will cause higher compressor
operating temperatures.
Figure 4-1: Shipping strap—ST4, ST5, ST7
1. Shipping strap