5.1 INLET DAMPER LINKAGE ADJUSTMENT
The inlet dampers (outside air inlet and bypass
dampers) are positioned by the motor actuator to
maintain a constant mixed air temperature. The
operation of these two dampers is opposed; i.e.
when one is open, the other is closed. The motor
actuator is a spring return type, and will return the
outside air inlet damper to a fully closed position
when the compressor is not running. To adjust the
inlet damper linkage, perform the following steps in
sequence:
Too many starts may result in motor damage. If
there are questions, contact the motor manufac-
turer.
1. When looking at the mixed air motor actuator
from the end which is driving the damper, the
crank arm should be in the 2:00 position.
The compressor should be OFF for this check.
2. With the compressor not running, adjust the
active length of the short link rod by loosening
the lock bolt of the swivel mounted on the crank
arm, until the outside air damper is closed. The
crank arm swivel should be attached to the
crank arm at the largest radius that the crank
arm adjusting slot will allow.
3. When looking at the motor actuator from the con-
trol side (bypass air damper) the crank should
be in the 2:00 position (See Figure
The compressor should be OFF for this check.
The crank arm located on the bypass damper
should be in the 2:00 position with the bypass
damper fully opened.
. Place the outdoor air tem-
perature changeover control at its minimum
position. Set the room thermostat at its minimum
temperature setting and start compressor,
observing the movement of the outdoor air
damper and the bypass damper. Within 60 sec-
onds of start up, the outdoor air damper should
be opened fully and the bypass damper should
close fully. Rotation of either damper should not
exceed 90º, and the damper actuator motor
should not be stalled by the linkage. If the
bypass damper does not fully open, or the
damper actuator motor stalls, proceed to the
next step. Otherwise, the inlet damper linkage is
now correctly adjusted.
. With the compressor not run-
ning remove the motor actuator cover. This will
expose the travel adjustment screw on the
motor actuator.
Start the compressor, again observing the
movement of the outside air damper and bypass
damper. The travel adjustment screw on the
motor actuator should be adjusted so that the
outdoor air damper opens fully (horizontal),
counterclockwise to reduce travel, or clockwise
to increase travel, as required.
If the motor actuator becomes stalled before the
outdoor air damper fully opens as a result of the
bypass damper closing too soon, loosen the
stud locknuts at the cable ends. When the out-
door air damper is fully open, close the bypass
damper manually and retighten the locknuts.
Shut off the compressor. The spring return in the
motor actuator should pull the outdoor air
damper fully closed, and the bypass damper
fully open. At this point the inlet dampers should
be properly adjusted. Replace the temperature
controller cover and motor actuator cover.
5.2 DISCHARGE DAMPER LINKAGE ADJUSTMENT
The discharge dampers (rejected air damper and
recovered air damper) are factory adjusted and
should not require periodic re-adjustment. However,
if components are replaced or adjustment is other-
Figure 5-1 Typical Damper Actuator Motor
Содержание EES LS25S Series
Страница 12: ...Section 2 DESCRIPTION 8 Figure 2 2 High Room Temperature Figure 2 3 Low Room Temperature Figure 2 4 No Power ...
Страница 14: ...Section 3 SPECIFICATIONS 10 Figure 3 1 Identification TS32A 300 350 EES Typical 02250133 419R00 ...
Страница 18: ...Section 4 INSTALLATION 14 Table 2 Ductwork Static Pressure Loss Worksheet ...
Страница 20: ...NOTES 16 ...
Страница 26: ...NOTES 22 ...
Страница 28: ...Section 6 ILLUSTRATIONS AND PARTS LIST 24 6 3 ASSEMBLY EES 200 250HP 149 186KW 02250126 958R03 ...
Страница 30: ...Section 6 ILLUSTRATIONS AND PARTS LIST 26 6 3 ASSEMBLY EES 200 250HP 149 186KW 02250126 958R03 ...
Страница 34: ...Section 6 ILLUSTRATIONS AND PARTS LIST 30 6 5 HORIZONTAL REMOTE COOLER ASSEMBLY 350HP 261KW 02250123 146R03 ...
Страница 36: ...Section 6 ILLUSTRATIONS AND PARTS LIST 32 6 5 HORIZONTAL REMOTE COOLER ASSEMBLY 350HP 261KW 02250123 146R03 ...
Страница 42: ...Section 6 ILLUSTRATIONS AND PARTS LIST 38 6 8 HORIZONTAL COOLER ASSEMBLY 450HP 336KW INTEGRAL 02250125 435R05 ...
Страница 48: ...Section 6 ILLUSTRATIONS AND PARTS LIST 44 6 11 EES ENCLOSURE DOGHOUSE ASSEMBLY INTEGRAL 02250133 207R00 ...
Страница 50: ...Section 6 ILLUSTRATIONS AND PARTS LIST 46 6 12 EES ENCLOSURE 200 250HP 149 186KW INTEGRAL 02250133 208R01 ...
Страница 52: ...Section 6 ILLUSTRATIONS AND PARTS LIST 48 6 12 EES ENCLOSURE 200 250HP 149 186KW INTEGRAL 02250133 208R01 ...
Страница 54: ...Section 6 ILLUSTRATIONS AND PARTS LIST 50 6 13 EES ENCLOSURE 300 350HP 224 261KW INTEGRAL 02250133 209R01 ...
Страница 56: ...Section 6 ILLUSTRATIONS AND PARTS LIST 52 6 13 EES ENCLOSURE 300 350HP 224 261KW INTEGRAL 02250133 209R01 ...
Страница 58: ...Section 6 ILLUSTRATIONS AND PARTS LIST 54 6 14 DECAL GROUP ...
Страница 60: ...Section 6 ILLUSTRATIONS AND PARTS LIST 56 6 15 DECAL LOCATIONS ...
Страница 62: ...Section 6 ILLUSTRATIONS AND PARTS LIST 58 6 16 WIRING DIAGRAM EES SUPERVISOR CONTROL 02250133 680R02 ...
Страница 63: ...Section 6 ILLUSTRATIONS AND PARTS LIST 59 6 17 WIRING DIAGRAM EES REMOTE 02250134 081R00 ...
Страница 65: ...NOTES 61 ...