background image

Suburban Dynaline 3 A&E Manual 12/2016 Rev.1

14

SLOPE DOWN TO THE OUTSIDE

SURFACE OF FINISHED

FLOOR OR TOP OF CARPET

       MIN. (PROJECTION BEYOND EXTERIOR WALL)

Y"

X"

MOUNTING HOLES AND SCREWS

(BY INSTALLER.)

DO NOT PUT HOLES THROUGH

WALL SLEEVE BOTTOM!

REAR GRILLE

CAULK AROUND WALL SLEEVE

SURFACE OF FINISHED EXTERIOR WALL

Y" =           - ( X" +        )

SURFACE OF FINISHED INTERIOR WALL

CABINET FRONT

  X" REPRESENTS EITHER THE

  DIMENSION REQUIRED TO FLUSH

  SLEEVE TO FINISHED TRIM OR

  MOLDING, OR THE DISTANCE

  SLEEVE PROJECTS INTO ROOM

  BEYOND FINISHED INTERIOR

  WALL.

NOTE: X" CAN BE 0" IF

  SLEEVE IS FLUSH WITH

  FINISHED INTERIOR WALL.

 1

5—

8

"

1—

4

"

  1

5—

8

"

14

3—

4

"

INSTALLING 

THE CHASSIS

1. Slide chassis squarely into wall sleeve from inside and secure with four 

  (4) screws into flange on wall sleeve to ensure proper security.
2. Connect gas and electrical supply. (See pages 13, 14 and 20.)
3. Remote thermostat: Dynaline

 3 chassis are supplied for standard 

  built-in control. To convert the standard chassis to function with remote  

  thermostat, connect the thermostat wiring (according to thermostat 

  manufacturer’s instructions) to the terminal block located on the 

  module board. Move the dip switch #1 on the module board to the 

  “ON” position. (See 

Figure 12

.) Unit is capable of operating set-back 

  (5-wire) thermostat.

NOTE:

 Connecting remote thermostat overrides the built-in thermostat 

and no digital read out will be displayed on the control panel. There is no 

need to disconnect the chassis’ built-in thermostat.
4. To lock out the A/C compressor when the chassis is powered by 

  an emergency standby power generator, 24-volt lead wires from the 

  transformer (NOTE: Field supplied transformer to be powered by the 

  standby generator) must be connected to the 1/4" spade terminals on 

  the module board. (See 

Figure 27

 for ladder diagram of typical standby  

  generator electric service.)
5. Install cabinet front.

  Figure 9

WALL INSTALLATION

REAR GAS HOOK-UP

Содержание DYNALINE DL3-0712

Страница 1: ...ls Motels Apartments and Senior Housing Four BTU h Capacities 12 20 MBTU Gas Heat Low Heating Amp Draw R 410A Refrigerant ARCHITECT S AND ENGINEER S MANUAL A Combination Gas Heating Electric Cooling S...

Страница 2: ...he outside atmosphere Solid state electronic hot surface ignition HSI with no open flame is the modern alternative to pilot lights HSI increases energy conservation while ensuring safety Easy to Insta...

Страница 3: ...g Tips 33 Accessory Description Review 34 Dynaline 3 Airflow 35 Suburban Limited Warranty 36 37 Dynaline 3 PTAC Features and Benefits 38 39 Hotels Motels Individual room control Energy management inte...

Страница 4: ...or each specific locale Utilizing BIN Hour temperature data the following table provides representative examples of costs to operate one PTAC for one year Suburban will gladly prepare a BIN Hour Cost...

Страница 5: ...er year at the mid point temperature specific to a geographical location The BIN hours are derived from historical weather data For example at a location with 7 023 heating BIN hours such as Syracuse...

Страница 6: ...g infiltration of air water and contaminants into the conditioned area Electrical components Located on the indoor side of the wall they are protected from the weather and easily accessed for service...

Страница 7: ...rd design provides means of lock ing out A C compressor when standby power generator is operating Electronic control board has 24V input terminals to receive lock out signal Room air discharge Attract...

Страница 8: ...andem 15 amp 6 15 R Total amps cooling heating 7 5 1 2 5 1 1 0 3 8 1 0 3 3 1 0 Total watts cooling heating 1550 260 1125 150 855 150 675 150 Compressor Type Hermetic Rotary Refrigerant type HCFC R410...

Страница 9: ...ressor from external vibration The system shall include copper aluminum condenser and evaporator coils with capillary refrigerant control Air flow system consists of a two speed room air motor for Hi...

Страница 10: ...ructed of 20 gauge galvanized steel with a protective baked on enamel finish similar to the wall case GAS TYPE Natural gas units shall be equipped with a gas valve having a built in regulator set to o...

Страница 11: ...unit should be installed where it can effectively circulate air into the room Generally the best location is midway along the wall and away from a stairwell or other opening Unit must not be located...

Страница 12: ...a location inspect the wall and floor areas to determine that there are no hidden electrical wires piping tubing ducts girders wall studs etc that might interfere with the proper installation and safe...

Страница 13: ...4 slope to the outside Do not slope toward front To avoid water damage to the wall do not put holes through the bottom of the wall sleeve NOTE If the unit is to be mounted flush with the exterior wall...

Страница 14: ...Remote thermostat Dynaline 3 chassis are supplied for standard built in control To convert the standard chassis to function with remote thermostat connect the thermostat wiring according to thermosta...

Страница 15: ...EVE BOTTOM REAR GRILLE CAULK AROUND WALL SLEEVE SURFACE OF FINISHED EXTERIOR WALL 3 MIN 2 1 Y X Y 14 X 3 4 1 4 1 4 1 4 SURFACE OF FINISHED FLOOR OR TOP OF CARPET SLOPE DOWN TO THE OUTSIDE SURFACE OF F...

Страница 16: ...Suburban Dynaline 3 A E Manual 12 2016 Rev 1 16 Figure 12...

Страница 17: ...8 520 1 050 1 600 20 92 190 350 730 1 100 30 73 152 285 590 890 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490 100 38...

Страница 18: ...14 4 Using the two 2 8 32 x 1 2 self tapping screws provided secure hi ear elbow as illustrated See C Figure 14 5 Insert gas inlet tube assembly See D Figure 14 through bushing in firewall NOTE The sh...

Страница 19: ...for air discharge to the right but can easily be converted for discharge to the left The adaptor is 43 1 4 long with female connection The extension is 43 1 4 long with 1 male tapered flange If you w...

Страница 20: ...tor and collar assembly into position on the unit Make sure the adaptor is resting on the adaptor brackets adjust brackets as needed 7 Locate the hole in the adaptor bracket and mark the underside of...

Страница 21: ...daptor and collar assembly from the unit At the two locations marked on the adaptor in Step 8 drill a 7 64 diameter hole 2 places 10 Install adaptor and collar assembly on unit as illustrated and secu...

Страница 22: ...rolled by a toggle switch or other means in a control panel field supplied The units remain de energized until the room becomes occupied at which time the desk attendant can energize them The standard...

Страница 23: ...les of exterior grilles are available to complement building aesthetics Aluminum Grille Unpainted grille of stamped clear anodized aluminum Protects the outdoor fan coil and vent cap assembly Designed...

Страница 24: ...as in the event of a diaphragm rupture Gas escapement is limited within ANSI standard levels Multipurpose mounting internal or external For best performance and quick response mount in upright positi...

Страница 25: ...l Electrical Code ANSI NFPA No 70 in Canada with the latest edition of ETL C22 1 Canadian Electrical Code Figure 25 To convert the standard chassis to function with remote thermostat connect the therm...

Страница 26: ...Suburban Dynaline 3 A E Manual 12 2016 Rev 1 26 Figure 26 Ladder Diagram 208 230 V A C...

Страница 27: ...Suburban Dynaline 3 A E Manual 12 2016 Rev 1 27 Figure 27 Schematic 277 V A C...

Страница 28: ...Suburban Dynaline 3 A E Manual 12 2016 Rev 1 28 Figure 28 Ladder Diagram 277 V A C...

Страница 29: ...ency power generator without forfeiting zone temperature control on the heating cycle Dynaline 3 incorporates an A C compressor lock out capability This feature allows the compressor circuit to be loc...

Страница 30: ...ust gases through the unit s vent system is obstructed creating an unsafe condition If the limit switch is determined to be defective it must be replaced Never attempt to repair it and never shunt the...

Страница 31: ...air motor causes the diaphragm in the pressure switch to move closing the contacts This completes the electrical circuit to the input of the module board and a 10 second warm up period for the glo ba...

Страница 32: ...temperature rise the switch will close and the compressor will again come on provided that the thermostat is still calling for cooling NOTE Dynaline 3 has a built in 5 minute delay between compressor...

Страница 33: ...rise the switch will close and the compressor will again come on provided that the thermostat is still calling for cooling NOTE Dynaline 3 has a built in 5 minute delay between compressor cycles Anyt...

Страница 34: ...tor Air Discharge Lateral Connector 43 Air Discharge Lateral Extension 43 Rear Gas Connection Kit Field Installed 2 PSIG Regulator Leveling Legs Set of 2 each Decor Base Panel conceals gas electric co...

Страница 35: ...r either horizontally or vertically The grille is installed from the factory to deliver horizontal air flow To change the airflow to vertical simply remove the grille and reinstall in the opposite pos...

Страница 36: ...on diagnosing shipping or handling THIS WARRANTY APPLIES ONLY TO THE PRODUCT IN ITS ORIGINAL INSTALLATION LOCATION AND IS VOIDED IF THE PRODUCT IS REINSTALLED ELSEWHERE FOUR YEAR LIMITED WARRANTY ON H...

Страница 37: ...y costs or increases in such costs from any reason whatsoever 10 Suburban products whose serial number has been altered defaced or removed 11 Suburban products installed or warranty claims originating...

Страница 38: ...ting backed by a 5 year limited warranty Copper and Aluminum Evaporator and Condenser Coils For longer life and ease of repair Coils use seamless copper tubing mechanically expanded into aluminum plat...

Страница 39: ...t lights Gas is conserved and safety is ensured Room Air Discharge An attractive durable grille constructed of extruded aluminum directs air laterally Return Air Filter No tools are needed to install...

Страница 40: ...nty statement can be found in each product s Installation Operation Manual on our website As part of the Suburban continuous improvement program specifications are subject to change without notice P O...

Отзывы: