Measure the resistance of field coil with a circuit
tester.
■
NORMAL RESISTANCE
[Remedy]
If the resistance is not normal, replace rotor with a new one.
(2)
CHECKING OF DIODES AND RESISTORS ON THE ROTOR
■
Unsolder and take out the diodes and a resistor from rotor.
■
Measure the resistance of diodes.
\
Each rotor has three diodes. Check the resistance of each diode.
■
Measure the resistance of surge absorber connected to the diode holder.
■
Check the magnetic force of permanent magnets molded in the rotor.
[Remedy]
(1)
If the magnetic force of rotor magnets is weak, or if the surge absorber is not good, replace the rotor
with a new one.
(2)
If the diode is not good, replace it with a new one.
CAUTION: In case the diode troubles are frequent, check the surge absorber because it
might be broken even if its resistance is normal (
∞
Ω
). In such a case, replace the
rotor with a new one.
MODEL
RGD3300H
RGD5000H
Resistance
2.1
Ω
1.6
Ω
NORMAL RESISTANCE:
∞
Ω
[Continuity exists.]
POLARITY OF
CIRCUIT TESTER
POLARITY OF
CIRCUIT TESTER