14.8.10.4
Signals
PID-3969-INPUTSIGNALS v5
Table 452:
I103CMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of commands
PID-3969-OUTPUTSIGNALS v5
Table 453:
I103CMD Output signals
Name
Type
Description
16-AR
BOOLEAN
Information number 16, off/on of autorecloser
17-DIFF
BOOLEAN
Information number 17, block of differential
protection
18-PROT
BOOLEAN
Information number 18, block of protection
14.8.10.5
Settings
PID-3969-SETTINGS v5
Table 454:
I103CMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
14.8.11
IED commands for IEC 60870-5-103 I103IEDCMD
14.8.11.1
Functionality
GUID-19AD44B2-21D6-4DB0-AD74-1578DA30C100 v5
I103IEDCMD is a command block in control direction with defined IED functions.
All outputs are pulsed and they are NOT stored. Pulse length is fixed to 400ms.
14.8.11.2
Identification
GUID-0D0B2477-1B0C-48F3-B047-CCF9C7A71856 v1
Function description
Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
IED commands for IEC 60870-5-103
I103IEDCMD
-
-
Section 14
1MRK 505 384-UEN A
Station communication
602
Breaker protection REQ650 2.2 IEC
Technical manual
Содержание impreza 2017
Страница 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Страница 2: ......
Страница 32: ...26...
Страница 42: ...36...
Страница 50: ...44...
Страница 168: ...162...
Страница 226: ...220...
Страница 396: ...390...
Страница 498: ...492...
Страница 512: ...506...
Страница 528: ...522...
Страница 632: ...626...
Страница 650: ...644...
Страница 738: ...732...
Страница 784: ...778...
Страница 785: ...779...