14.8.9.3
Function block
GUID-B8312E77-514D-4117-BB31-B9907755580C v1
I103USRDEF
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
RT_START
IEC10000294-3-en.vsdx
IEC10000294 V3 EN-US
Figure 278:
I103USRDEF function block
14.8.9.4
Signals
PID-6485-INPUTSIGNALS v5
Table 450:
I103USRDEF Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
INPUT1
BOOLEAN
0
Binary signal Input 1
INPUT2
BOOLEAN
0
Binary signal input 2
INPUT3
BOOLEAN
0
Binary signal input 3
INPUT4
BOOLEAN
0
Binary signal input 4
INPUT5
BOOLEAN
0
Binary signal input 5
INPUT6
BOOLEAN
0
Binary signal input 6
INPUT7
BOOLEAN
0
Binary signal input 7
INPUT8
BOOLEAN
0
Binary signal input 8
RT_START
BOOLEAN
0
Trig to set base of relative time
GUID-9E29DE39-EA74-4D62-A2BA-F8E31A3D8757 v2
RT_START
registers the positive transition (0->1) of a pulse and sets the time
from which relative time is derived. Relative time is assigned only to inputs where
the corresponding
TypNo
parameter is set to
Relative
. The maximum relative time
and unit conform to the IEC 60870-5-103 standard.
1MRK 505 384-UEN A
Section 14
Station communication
Breaker protection REQ650 2.2 IEC
599
Technical manual
Содержание impreza 2017
Страница 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Страница 2: ......
Страница 32: ...26...
Страница 42: ...36...
Страница 50: ...44...
Страница 168: ...162...
Страница 226: ...220...
Страница 396: ...390...
Страница 498: ...492...
Страница 512: ...506...
Страница 528: ...522...
Страница 632: ...626...
Страница 650: ...644...
Страница 738: ...732...
Страница 784: ...778...
Страница 785: ...779...