IEC05000748_2_en.vsd
UN
ST1
TR1
ST2
TR2
START
TRIP
Comparator
UN > U1>
Start
t2
tReset2
&
Trip
Output
Logic
Step 2
Phase 1
Phase 1
Time integrator
tIReset2
ResetTypeCrv2
START
Start
t1
tReset1
&
Trip
Output
Logic
Step 1
Time integrator
tIReset1
ResetTypeCrv1
Comparator
UN > U2>
START
TRIP
TRIP
OR
OR
IEC05000748 V2 EN-US
Figure 86:
Schematic design of Two step residual overvoltage protection
ROV2PTOV
7.3.4
Technical data
M13317-2 v14
Table 115:
ROV2PTOV technical data
Function
Range or value
Accuracy
Operate voltage, step 1 - step 2
(1.0-200.0)% of
UBase
± 0.5% of U
r
at U ≤
U
r
± 0.5% of U at U > U
r
Absolute hysteresis
(0.0–50.0)% of
UBase
± 0.5% of U
r
at U ≤
U
r
± 0.5% of U at U > U
r
Inverse time characteristics for low and
-
See table
Definite time delay low step (step 1) at 0
to 1.2 x U
set
(0.00–6000.00) s
± 0.2% or ± 45 ms
whichever is greater
Definite time delay high step (step 2) at 0
to 1.2 x U
set
(0.000–60.000) s
± 0.2% or ± 45 ms
whichever is greater
Table continues on next page
1MRK 505 384-UEN A
Section 7
Voltage protection
Breaker protection REQ650 2.2 IEC
197
Technical manual
Содержание impreza 2017
Страница 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Страница 2: ......
Страница 32: ...26...
Страница 42: ...36...
Страница 50: ...44...
Страница 168: ...162...
Страница 226: ...220...
Страница 396: ...390...
Страница 498: ...492...
Страница 512: ...506...
Страница 528: ...522...
Страница 632: ...626...
Страница 650: ...644...
Страница 738: ...732...
Страница 784: ...778...
Страница 785: ...779...