SEALED SYSTEM DIAGNOSTIC INFORMATION

NOTE:  

The temperature/pressure table at right is for refer-

ence only.  A unit's temperature/pressure correlation may
differ from those listed due to: variations in evaporator ther-
mistor location, set-points, where the sealed system is in
the refrigeration cycle, ambient temperature, etc.

If a unit is experiencing temperature problems, it is recom-
mended to reference the Error Code Troubleshooting Guide
and General Troubleshooting Guide before accessing the
sealed system.  After all mechanical and electrical compo-
nents have been ruled out, sealed system pressures can
be checked and compared against those listed in the tables
below.

NOTE:

Whenever entering the sealed system, always use

solder-on process valves.  Do 

NOT

use bolt-on process

valves as they are prone to leak.

NOTE:

Whenever servicing the sealed system, the valve

assembly (includes high-side filter-drier) must be replaced.

NORMAL OPERATING PRESSURES

Model

424

Normal Low Side Pressures

10 psi to 36 psi

Normal High Side Pressures

90 psi to 100 psi

PRESSURE INDICATIONS

If low side pressure is

NORMAL

LOW

LOW

HIGH

HIGH

& high side pressure is

NORMAL

LOW

HIGH

LOW

HIGH

possible problem is 

MECHANICAL

(see General Troubleshooting Guide)

LEAK

RESTRICTION

INEFFICIENT COMPRESSOR

OVER CHARGE

Pressure

10” Vac / -.69 Bar

7” Vac / -.48 Bar
4” Vac / -.28 Bar
0” Vac / 0 Bar

2 Psi / .14 Bar
4 Psi / .28 Bar
7 Psi / .48 Bar
9 Psi / .62 Bar

12 Psi / .83 Bar
15 Psi / 1.03 Bar
18 Psi / 1.24 Bar
22 Psi / 1.51 Bar
26 Psi / 1.79 Bar
30 Psi / 2.07 Bar
35 Psi / 2.41 Bar
40 Psi / 2.76 Bar
45 Psi / 3.10 Bar
51 Psi / 3.52 Bar
57 Psi / 3.93 Bar
64 Psi / 4.41 Bar
71 Psi / 4.90 Bar
78 Psi / 5.38 Bar

Temperature

-30°F / -34°C
-25°F / -32°C
-20°F / -29°C
-15°F / -26°C
-10°F / -23°C

-5°F / -21°C

0°F / -18°C
5°F / -15°C

10°F / -12°C
15°F / -9°C
20°F / -7°C
25°F / -4°C
30°F / -1°C
35°F / 2°C
40°F / 4°C
45°F / 7°C
50°F / 10°C
55°F / 13°C
60°F / 16°C
65°F / 18°C
70°F / 21°C
75°F / 24°C

TEMPERA

TURE / LOW

-SIDE PRESSURE CORRELA

TION

#7031933  - Revision A - April, 2015

MODEL 424

MODEL 424

(SWS #3227000)

(SWS #3227000)

Troubleshooting Guides

Содержание Wolf 400 Series

Страница 1: ...Troubleshooting Guide 43 subzero com 800 222 7820 400 Service Manual...

Страница 2: ...he true set point by a one degree increment or decrement depending on choice of WARMER or COLDER key respectively 3 Initiate Diagnostic Mode by pressing and holding either COLDER key and the UNIT ON O...

Страница 3: ...ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERV...

Страница 4: ...ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERV...

Страница 5: ...ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERVICE BELL ON SERV...

Страница 6: ...or will appear constant when Diagnostic Mode ends indi cating error codes are logged To clear this and the error codes from the software memory the problem must be corrected and the unit must be ON th...

Страница 7: ...l connections Repair or replace j Check resistance of appropriate compartment thermistor for 30 000 to 33 000 ohms at 32 F 0 C Replace if defective k Initiate manual valve activation mode for appropri...

Страница 8: ...too cold in a wine storage compartment be sure to complete a Temperature Problem Diagnostic Worksheet on the preceding pages before continuing All key strokes necessary to help in diagnosing a problem...

Страница 9: ...hile pressing UNIT ON OFF key Allow time for unit to pull down to temperature Instruct customer Instruct Customer that unit performs best between 60 F 16 C 90 F 32 C a Adjust wine rack b See Door Adju...

Страница 10: ...C 90 F 32 C a Adjust wine rack b See Door Adjustment procedure in section 2 of this manual c Check hinges Replace if defective a Move to correct location b Initiate Diagnostic Mode If EE is dis played...

Страница 11: ...ay Lighting Activated ON 100 Fan Light Switch Wiring Crossed Door Switch Malfunction Initiate Temperature Units Selection Mode to check units of measure F or C selected Check thermistor ohms 30 000 33...

Страница 12: ...ard Bad Data from Control Board Bad Data from Control Board Bad LED Board in Control Panel Door or unit needs adjustment Press release UNIT ON OFF key Check switch electrical connections Check for pow...

Страница 13: ...filter drier must be replaced NORMAL OPERATING PRESSURES Model 424 Normal Low Side Pressures 10 psi to 36 psi Normal High Side Pressures 90 psi to 100 psi PRESSURE INDICATIONS If low side pressure is...

Страница 14: ...ins 4 6 only 3 With lower wine storage COLDER key pressed there should be continuity across pins 2 3 only 4 With lower wine storage WARMER key pressed there should be continuity across pins 3 4 only 5...

Отзывы: