P1 
Parameter

Function : T
or cooling.

o set controller for heating 

CLG

HTG CLG

T
the P1
parameter,
press the
SET key.

o change

Use UP/DOWN keys to get desired 
value & press set to confirm.

CLG: Cooling mode and 
HTG: Heating mode.

Min

Max

Fac.

8

P4 
Parameter

Function : To set the differential.

To change
the P4 
parameter,
press the 
SET key.

Use UP/DOWN keys to set desired 
value.
Differential between cut out and cut 
in temperature can be set between 

O

O

1.0 C to 20.0 C.

O

0.5 C

Min

Max

Fac.

O

20.0 C

O

2.0 C

Example (in cooling mode) : 

O

If the set point is set at 10.0 C and 

O

differential  is  set  at  2.0 C,  then 

O

when  the  system  reaches  10.0 C, 
the  relay  will  cut  out.  Since  the 
differential is 2.0, the relay will cut in 

O

O

O

(restart) at 12.0 C (10.0 C+2.0 C).

9

P5 
Parameter

Function : To set probe calibration.

To change  
the P5 
parameter, 
press the 
SET key.

Use UP/DOWN keys to set desired 
value.
In  time  it  may  be  possible  that  the 
display may be offset by a degree or 
so.
To  compensate  for  this  error,  you 
may  need  to  add  or  minus  the 
degrees  required  to  achieve  the 
correct  temperature.  Setting  value 

O

  

O

is from -10.0 C to +10.0 C.

O

-10.0 C

Min

Max

Fac.

O

10.0 C

O

0.0 C

Example  : 

The  temperature  on 

O

the  display  is  28.0 C,  whereas  the 

O

actual  temperature  is  30.0 C.  You 
will need to set the P5 mode to 2.0, 
which  means  that  once  out  of  the 
p r o g r a m m i n g   m o d e ,   t h e  

O

temperature  will  show  30.0 C 

O

O

(28.0 C + 2.0 C).

10

P6 
Parameter

 0 Min 20 Min 3 Min

Function : To set time delay
between relay restart time.

To change  
the P6 
parameter, 
press the 
SET key.

Min

Max

Fac.

Use UP/DOWN keys to set desired 
value.
This parameter is used to protect the 
compressor from restarting in a short 
period  of  time  and  can  be  set 
between 0 to 20 minutes.

Example :

 If this parameter is set at 3 

minutes, the relay will cut off at the 
set  temperature,  but  will  not  restart 
for a minimum of 3 minutes, even if 
the  differential  is  achieved  earlier. 
This parameter is good to protect the 
life of the compressor when there are 
p o w e r   f l u c t u a t i o n s   a n d   t h e  
compressor  is  switched  off  and  on 
within a few seconds. 

Flashing

Time delay in progress

6

P2
Parameter

 

Function : T
high temperature limit.

o set maximum allowable 

T
the P2
parameter,
press the
SET key.

o change 

Use UP/DOWN keys to set desired 
value.
Once set at a particular  value, this 
will not allow the set point to go 
above this value. 

Example  : 

Setting  this  parameter

O

at 50.0 C will not allow the set point to 

O

go  above  50.0 C.  Also,  if  the 

 

O

temperature  reaches 50.0 C,the 
display  will  show  HT(High  Temp.) 
indicating  that  the  temperature  has 
gone  above  the  value  in  this 
parameter.

SP+0.5

Max

Fac.

O

50.0 C

O

50.0 C

Min

(Message on display)

HT

7

Function : To set minimum 
allowable low temperature set point. 

Use UP/DOWN keys to set desired 
value. 
Once  set  at  a  particular  value,  this 
will  not  allow  the  set  point  to  go 
below this value.

Example :

 Setting this parameter at 

O

-50.0 C will not allow the set point to 

O

go  below  -50.0 C.  Also,  if  the 

O

temperature  reaches  -50.0 C,  the 
display  will  show  LT  (Low  Temp.) 
indicating that the temperature has 
gone  below  the  value  in  this 
parameter.

P3 
Parameter

O

-50.0 C

Max

Fac.

SP-0.5

To change
the P3 
parameter, 
press the 
SET key.

Min

(Message on display)

O

-50.0 C

LT

Содержание SZ-7510-C

Страница 1: ...e SET Point of the controller How to set other parameters To set Heating or Cooling function Max High Temp limit alarm Min Low Temp limit alarm To set Differential Hysterisis Probe calibration Time Delay relay restart after cutoff Keypad lock Relay status on probe failure To enable disable power switch Unit ID Restore factory defaults End Programming Operating messages Technical Data Wiring diagra...

Страница 2: ...ge the P6 parameter press the SET key Min Max Fac Use UP DOWN keys to set desired value This parameter is used to protect the compressor from restarting in a short period of time and can be set between 0 to 20 minutes Example If this parameter is set at 3 minutes the relay will cut off at the set temperature but will not restart for a minimum of 3 minutes even if the differential is achieved earli...

Страница 3: ...h ENB Enables power switch Controller has power switch which if enable puts controller in active or stand by state If press for 2 seconds controller will go in stand by mode display will show OF To again switch to ACTIVE WORKING MODE press power switch again for 2 seconds All leds and 7 segment display will flash and enter into NORMAL WORKING MODE 14 ID Parameter Function To set unit ID 1 240 1 Mi...

Страница 4: ...echnical data Dimensions Front 75 X 34 5 MM Depth 71 MM w o back lid Panel Cutout 29 X 71 mm Mounting Flush panel mounting with fasteners Frontal protection I P65 Connections Screw terminal blocks 2 5sqmm one wire terminal only Display 3 X17 mm 0 67 LED Data storage Non volatile EEPROM memory Power input 230Vac 15 50 60Hz Other on request O O Operating temp 5 C to 50 C non condensing O O Storage t...

Страница 5: ...rreparable damage and personal injury Kindly ensure that wiring is done by qualified personnel only Maintenance Cleaning Clean the surface of the controller with a soft moist cloth Do not use abrasive detergents petrol alcohol or solvents Notice The information in this document is subject to change in order to improve reliability design or function without prior notice and does not represent a com...

Отзывы: