14
Parameter
Function : To restore default settings of
the controller.
Function: Sets cycle time for PID action.
18
Parameter
Min
Max
Fac.
1 sec 60 sec 3 sec
Cycle time also known as duty cycle, the total length of time for
the controller to complete one ON/OFF cycle.
Example :
With a 20 second cycle time, an on time of 10
seconds and an OFF time of 10 seconds represents a 50
percent power output. The controller will cycle ON and OFF
while within the proportional band.
Min
Max
Fac.
Sets the proportional band of PID parameter.
Min
Max
Fac.
O
0.1 C
O
100.0 C
O
10.0 C
Term P is proportional to the current value of the SV-PV error .
Example :
If the (SV-PV) error is large and positive, the control
output will be proportionately large and positive and vice versa if
error is negative.
Function: Sets proportional band.
19
Parameter
Parameter
Function: Sets integration time.
20
Sets the integration time of PID parameter.
Min
Max
Fac.
0 sec 2000 sec 120 sec
Term I accounts for past values of the SV-PV error and
integrates them over time to produce the I term.
Setting "0" will turn OFF integration.
Example :
If there is a residual SV-PV error after the
application of proportional control, the integral term seeks to
eliminate the residual error by adding a control effect due to
the historic cumulative value of the error.
Min
Max
Fac.
Function: Sets differential time.
21
Parameter
Sets the differential time of PID parameter.
Setting "0" will turn OFF differential.
Term D is a best estimate of the future trend of the SV-PV error,
based on its current rate of change. It is sometimes called
"anticipatory control", as it is effectively seeking to reduce the
effect of the SV-PV error by exerting a control influence
generated by the rate of error change. The more rapid the
change, the greater the controlling or dampening effect.
Min
Max
Fac.
0 sec 1000 sec 30 sec
Function: Sets Control1 output.
23
Parameter
This parameter is used to configure control1 out as,
= SSR
= Relay
User has to set this parameter in accordance with the output
used.
24
Parameter
Function: To lock keypad.
This parameter is used to lock the parameter so that
tampering is not possible by by-standers.
= unlocked parameter
= Locked parameter
When locked all parameters can only be viewed ,but can not
be modified.
Min
Max
Fac.
Min
Max
Fac.
Function: Set the hysteresis width for ON-
OFF action in Control1.
22
Parameter
Min
Max
Fac.
O
1 C
O
100 C
O
2 C
This parameter will be prompted only if selected control action
is (reverse) or (forward) in setting.
It sets the deadband between ON & OFF switching of the
output.
O
Example (For Fd control) :
If the set point is set at 100 C and
O
O
hysteresis is set at 2 C, then when the system reaches 100 C,
O
the heater relay will go OFF. Since the hysteresis is 2 C, the
O
O
O
heater relay will get ON (restart) at 102 C (100 C +2 C).
Keypad Locked
Keypad Locked
TM
Disclaimer:
This manual & its contents remain the sole property of
PVR CONTROLS . India and shall not be reproduced or distributed
without authorization. Although great care has been taken in the
preparation of this document, the company or its vendors in no event
will be liable for direct, indirect, special, incidental or consequential
damage arising out of the use or inability to use the product or
documentation, even if advised of the possibility of such damages.
No part of this manual may be reproduced or transmitted in any form
or by any means without the prior written permission of the company.
PVR CONTROLS., reserves the right to make and changes or
improvements without prior notice.
Warranty:
This product is warranted against defects in materials and
workmanship for a period of one year from the date of purchase.
During the warranty period, product determined by us to be defective
in form or function will be repaired or, at our option, replaced at no
charge. This warranty does not apply if the product has been
damaged by accident, abuse, and misuse or as a result of service or
modification other than by the company. This warranty is in lieu of any
other warranty expressed or implied. In no event shall the company
be held liable for incidental or consequential damages, including lost
revenue or lost business opportunity arising from the purchase of this
product.
04 / 23.11.19
Digital Panel Meter
Power Analyzer
Timer , PLC , HMI
Data Logger
OUR OTHER PRODUCTS
Calibration Certificate
DATE
MODEL NO.
Claimed Accuracy :
For TC inputs
: 0.3% of FS
O
For RTD inputs : 0.1% of FS +/-1 C
(20 min of settling time for TC inputs)
Calibration Instrument & Sr. No :
Calibrated ON
:
Valid Upto
:
The calibration of this unit has been verified at the following
values :
SENSOR TYPE
RTD
VALUE
O
TESTED ( C)
O
0 C
O
100 C
O
350 C
J,K
O
50 C
O
400 C
O
650 C
Instrument is confirmed accepted as accuracy is within the
specified limit. This certificate is valid upto one year from the
date of issue.
CONTROLLER
SR. NO.
Checked By :
PVR Controls, India
(Specification are subject to change, since development is a
continuos process.)
VALUE
O
Observed ( C)
All values
within
specified
limit of
accuracy
LED Indication
LED
Description
Status
ON
OFF
Relay1 / SSR OFF.
Relay1 / SSR ON.
ON
OFF
Relay2 OFF.
Relay2 ON.
ON
OFF
Tuning is in progress.
Tuning Stop.
FLASHING
ON
Dwell time elapsed.
Dwell timer is in progress..
Alarm relay ON.
Alarm Relay OFF.
ON
OFF
ON
OFF
Parameters are Locked.
Parameters are Unlocked.
OFF
Dwell timer disabled.
Error Messages
Message
Description
Displays when input sensor is disconnected
or sensor is not connected.
Flashes when measured value is higher
than input range.
Flashes when measured value is lower
than input range.
ON
Alarm indication ON.
(for Single Relay)
OFF
Alarm indication OFF.
(for Single Relay)
If user tries to enter Pro-key mode without inserting the pro key or
with wrong connection, no further function will be activated after
displaying “ or ”. Controller will display “ ”. Then switch off
controller and insert the pro key properly and try to enter Pro key
mode.
User has to first Upload the parameters in the Subzero Validated
Blank Pro-Key and then subsequently use it for downloading.
Uploading mode
Press key to upload the parameters to Pro Key.
Lower display will show "
" once uploading is done. Press to
exit display will show "
----
" and return to normal display.
Downloading mode
Similarly connect Pro key to the controller .
Press key to download all parameters from Pro key to the
controller.
Lower display will show "
" once download is done.
Once done press key to exit and display will flash and return to
normal mode.
Pro-Key ( On Request ) (Not for Single Relay)
Function
Keys to be Used
To upload the parameters from the
controller
To download the parameters to the
controller
To set and exit
touch " " key
touch " " key
touch " " key
To use Pro-key user must insert it prior to power ON. Insert the pro-
key and power ON controller. When the display flashes for 5
seconds, touch the key for 1 second. Controller will enter into
Pro-key mode and will display “ ”. Then touch either of the
below given keys to use the Pro-key.
Functions of Pro-key and the keys to be used for are as given below:
Temperature above the maximum high
temperature limit.
Temperature below the minimum low
temperature limit.
Function: Sets the alarm type.
( only For 2 Relay)
13
Function: Set the hysteresis for ON-OFF
action in Control2.
(only For 2 Relays)
12
Min
Max
Fac.
O
1 C
Parameter
O
100 C
O
2 C
This parameter will be prompted only if selected control action
is rE (reverse) or Fd (forward) in setting.
It sets the deadband between ON & OFF switching of the
output.
It's applicable when is (reverse) or
(forward).
Min
Max
Fac.
: Deviation
: Absolute
Parameter
For alarm types setting , please
refer Alarm Type description.
O
Example (For Fd control) :
If the set point is set at 100 C and
O
O
hysteresis is set at 2 C, then when the system reaches 100 C,
O
the heater relay will go OFF. Since the hysteresis is 2 C, the
O
O
O
heater relay will get ON (restart) at 102 C (100 C +2 C).
Parameter
Function: T
temperature limit.
(only for Single relay)
o set maximum allowable high
9
O
Example:
If this parameter is set to 700 C and the
O
temperature reaches or goes above 700 C, display will show
(High Temp.) alarm indicating that the temperature has
reached or gone above the value set in this parameter.
Min
Max
Fac.
(Message on display)
Note : Ht fault will be ignored at every power ON.
Function: Sets control action for relay2.
(only For 2 Relay)
11
Parameter
This parameter used to set required control action for relay 2
as,
= No action
= Reverse
= Forward
= Dwell time
Min
Max
Fac.
Parameter
Function: To set minimum allowable low
temperature limit.
(only for Single relay)
10
O
Example:
If this parameter is set to -40 C and the temperature
O
reaches or goes below -40 C, display will show (Low temp)
alarm indicating that the temperature has reached or gone
below the value set in this parameter.
Min
Max
Fac.
(Message on display)
Function: Sets control action for
relay1/SSR.
16
This parameter is used to set required control action for
relay 1/SSR as,
Parameter
= Reverse
= Forward
= PID
Min
Max
Fac.
LEVEL2 Parameter
Press & hold key for 6 seconds to enter into Level2
parameter setting( will flash). When release the key,
will flash.
Press
UP/DOWN
keys to modify the set value and to go to the
next parameter by pressing key.
Press the key to save the set value and to come out of
parameter setting after changing the set value.
15
Parameter
Function : To restore default settings of
the controller.
When Set to Yes all parameter are programmed to factory
values.
Useful to debug setting related problems.
Min
Max
Fac.
14
Set " " to enable AL1 icon.
AL1 icon turns ON when the corresponding alarm output
turns ON.
Type of alarm can selected by using Mod2 parameter.
Parameter
Function: Sets AL1 icon as alarm relay
ON/OFF indicator for alarm indication.
(only For 2 Relay)
Min
Max
Fac.
For Single Relay :
When temperature is above high temperature limit or
temperature is below low temperature limit, AL1 indication
ON.
Both alarms will be ignore at power ON for first time till the
setpoint not achieved. (First PID action performed)
Function: Sets the upper limit of PV input.
7
Parameter
Once set at a particular value, this will not allow the set point
to go above this value.
When changing the setting value and SV > HSV, SV will
reset as HSV.
Sets the maximum limit for set point adjustment. It can be
set from LSV+1 value to maximum specified range of
selected sensor.
Min
Max
Fac.
O
750 C
For J type sensor
O
750 C
+1
Function: Sets the lower limit of PV input.
6
Parameter
Min
Max
Fac.
Once set at a particular value, this will not allow the set point
to go below this value.
O
-50 C
For J type sensor
When changing the setting value and SV < LSV, SV will
reset as LSV.
Sets the minimum limit for set point adjustment. It can be set
from minimum specified range of selected sensor to HSV-1
value.
O
-50 C
- 1
8
Parameter
Function : To set Dwell Timer.
(Only for Single Relay)
Min
Max
Fac.
When Set to Dwell timer is enabled.
Note:
When selected dwell time
can be set in Set Mode.
+
+
Function: Runs auto tuning.
17
Parameter
This parameter is used to set YES/NO to start and stop Auto-
tuning.
When Set as , the unit starts auto-tuning. After
Completing is automatically Set.
During auto-tuning, the AUTO icon is continuously ON.
This parameter will be prompted only if selected control
action is PID in .
Min
Max
Fac.
Ordering Information
=
=
=
=
=
=
=
=
=
Alarm Types ( only for Two Relay )
Setting
Alarm Type
Description
Deviation high limit alarm
Deviation low limit alarm
Absolute value high limit
alarm
Absolute value low limit
alarm
*
: Alarm output hysteresis
High temperature alarm
Low temperature alarm
SV = +
FD Alarm ON when PV < SV -
Alarm OFF when PV = SV
SV = +
FD Alarm ON when PV > SV +
Alarm OFF when PV = SV
SV =
Alarm ON when PV < SV -
Alarm OFF when PV = SV
SV =
Alarm ON when PV > SV +
Alarm OFF when PV = SV
PV >
PV <
(Only for Single Relay)
(Only for Single Relay)
=
=
=
W 2 C 3 4 XX
T
2 44
-
48 X 48
Output 1
-
-
Power
Temperature in White
Temperature in Red
Touch
Keys
Dual Line
Display
T
K
Display Color
Keypad
Analog
PT100 + TC (J, K)
TC (J, K)
Output 2
AA
Relay 16A
(Single Output)
Alarm Relay
XXX
Customized Part