background image

Connection Diagram ( for PT244-T- 

AA )

W2C30

RTD1

RTD2

RTD3

1

2

4

5

P

N

NO

C

230V

SSR 

+

SSR -

12

6

7

8

11

TC 

+

-

Caution for your safety

WIRING:

 The probe and its corresponding wires should

 

never be 

installed in a conduit next to control or power

 

supply lines. The 

electrical wiring should be done as shown in the diagram. The 

power supply circuit should be connected to a protection switch. 

The terminals admit wires of upto 2.5sq mm.

WARNING:

  Improper wiring may cause irreparable damage and 

personal  injury.  Kindly  ensure  that  wiring  is  done  by  qualified 

personnel only.

Maintenance:

 Cleaning: Clean the surface of the controller with a 

soft moist cloth. Do not use abrasive detergents, petrol, alcohol or 

solvents.

Notice: 

The information in this document is

 

subject

 

 to change in 

order to improve reliability , design or function without prior notice 

and does not represent

 

a commitment on the part of the company. 

In no

 

event will the company be liable for direct, indirect, special, 

incidental  or  consequential  damage  arising  out  of  the  use  or 

inability to use the product or documentation, even if advised of 

the possibility of such damages. No part of this manual may be 

reproduced or transmitted in any form or by any means without 

the prior written permission of the company.

Controller 

:Controller  should  be  installed  in  a  place 

protected  by  vibration,  water  and  corrosive  gasses  and 

where  ambient  temperature  does  not  exceed  the  values 

specified in the technical data.

Probe :

To give a correct reading, the probe must be installed 

in  a  place  protected  from  thermal  influences,  which  may 

affect the temperature to be controlled. 

Product Mounting

Installation :

 Fixing and dimensions of panel models:

To fix the unit, slide the fastener  1  through the guides  2  as per the 

position shown in the figure. Move the fastener in the direction of the 

arrow, pressing tab   3   it permits to move the fastener in the opposite 

direction of the arrow. 

45.5mm

45.5mm

Panel Cutout

Dimensions 

48mm

48mm

PV

SV

PT244-T

Operating Manual

PT244-T / PT244-K / PT244-T-AA 

Introduction

A proportional–integral–derivative controller (PID controller or three 

term controller) is a control loop feedback mechanism widely used in 

industrial control systems and a variety of other applications requiring 

continuously  modulated  control.  A  PID  controller  continuously 

calculates  an  error  value  as  the  difference  between  a  desired 

setpoint (SV) and a measured process variable (PV) and applies a 

correction  based  on  proportional,  integral,  and  derivative  terms 

(denoted P, I, and D respectively) which give the controller its name.

PT244-T is a two set point PID controller. It is available in touch & 

keypad version. Customized iconic display interprets status easily.

48mm

1

2

3

CONTROLLER

GASKET

PANEL

Side Lock

Connection Diagram ( for PT244-T- 

 )

W2C30

RTD1

RTD2

RTD3

1

2

3

4

5

P

N

NO1

C1

230V

SSR 

+

12

6

7

8

11

TC 

+

-

SSR

NC1

Connection Diagram ( for PT244-T/K-W2C34 )

1

2

3

4

5

6

7

8

10

12

11

RTD1

SSR +

SSR 

-

P

N

NO1

C1

NO2

C2

TC 

230V

RTD2

RTD3

+

-

Connection Diagram ( for PT244-T/K-W*C34 )

1

2

3

4

5

6

7

8

10

12

11

RTD1

SSR +

SSR 

-

NO1

C1

NO2

C2

TC 

RTD2

RTD3

+

-

+

-

Power

Supply 

*

*

 12Vac/dc or 24V ac/dc on request

1

3

4

5

6
7

Control1 set point.

Sets the type of input sensor .
Sets input correction.
Sets the lower limit of PV input.
Sets the upper limit of PV input.

Sets the dwell time.

Level1 Parameter

2

Control2 set point.

Index

Sr. 

No.

Para.

Description

User Interface
Technical Specification

Initial display when Power is ON
Parameter setting mode

Working

Input types & Input range

Set mode

Sets cycle time for PID action.
Sets proportional band.

Sets integration time.
Sets differential time.
Sets the 

hysteresis

1

Runs auto tuning.

Sets control action for relay1 / SSR.

8
9

10

Sets control action for relay2. (for 2 Relay)
Sets the hysteresis2. (for 2 Relay)
Sets the alarm type. (for 2 Relay)
Sets AL1 icon as alarm relay. (for 2 Relay)

11

12
13
14

15

16
17

Factory reset parameter.

18
19
20

Sets Control1 output.

Lock keypad.

21

LED Indications

Alarm Types

Level2 Parameter

Error Messages 
Pro-key (On-request)   

Ordering Information   

To enable Dwell timer.

Low temperature limit. (for 1 Relay)

High temperature limit. (for 1 Relay)

22
23

24

Sr. 

No. Description

Process Value (PV)

RUN mode : Displays current measured value.

SETTING mode : Displays parameter.

Set value (SV)

RUN mode : Displays set value. 

              Displays countdown time when Dwell timer is 

running. 

SETTING mode : Displays set value of parameter.

Turns ON while control  output1 is ON.

4

2

1

Displays the Temperature unit.

3

User Interface

4

7

6

1

12

5

3

2

8
9

10

11

13

PV

SV

PT244-T

8

Turns ON while control  output2 is ON. 

(for two relay)

Turns ON when auto tuning is in progress.

5

7

Flashes during Dwell timer is in progress. 

Continuous ON : Dwell time elapsed. 

Turns ON when the corresponding alarm out turns 

ON.

6

9

Turns ON when keypad is locked.

10

Next key : 

Used to enters parameters level, moves to next

parameters. 

Press & hold this key atleast 2 seconds to enter

in set mode.

Press & hold this key atleast 4 seconds to enter

in Level1 Parameters.

Press & hold this key atleast 6 seconds to enter

in Level2 Parameters.

11

Down

Used in Program mode to decrement parameter

value.

Used to reset the Dwell timer..

 / Reset Key : 

13

Up / AT  Key :

value.

Press this key for 2 seconds to start or stop auto-

tuning.

Used in Program mode to increment parameter

12

Exit Key :

Press this key to save the setting value and to exit

the programing mode.

Input types & Input range

Input Type

Thermocouple

J

K

1

Decimal

Point

1

Display

O

Input Range ( C)

O

-50 to 750 C

O

-50 to 1200 C

RTD

Pt

100

1

0.1

O

-99 to 400 C

O

-99.9 to 400.0 C

The Auto-tuning function automatically computes and sets the 

proportional band (P), Integral time (I), Derivative time (D) as 

per process characteristics.

While Auto-tune is in progress 

"AUTO"

 led will turn ON.

After Auto-tuning is complete the 

"AUTO"

 led will turn OFF.

If auto -tuning is not complete after 3-4 cycles, it is suspected to 

fail. In this case, check the wiring & parameters such as the 

control action, input type etc.

Carry out the auto-tuning again, if there is a change in setpoint 

or process parameters. 

PID-time proportional

with auto reset & rate 

Working

2. ON/OFF control action (For reverse  mode)

The relay is ‘ON’ up to the set temperature and cuts”OFF” 

above the set temperature . As the temperature of the system 

drops ,the relay is switched ‘ON’ at a temperature lower than 

the set point .

HYSTERESIS:

The  difference  between  the  temperature  at  which  relay 

switches ‘OFF’ is the hysteresis or dead band.

1. Auto tuning

Note : In Auto Tuning  running time, user can not change 

the parameter value.

1. PT244-T-W2C34 / PT244-K-W2C34 - Two Relay

2. PT244-T-W2C30AA - Single Relay

3. PT244-T-W2C30 / PT244-K-W2C30 - Single Relay

4. PT244-T-W5C34 / PT244-K-W5C34 - Two Relay

Model Description

Technical Specification

Housing        

Polycarbonate Plastic

Dimensions  

Frontal : 48 X  48mm,  Depth : 78mm

Panel Cutout 

45.5 X 45.5mm

Mounting         : 

Flush panel mounting with fasteners.

Protection     

:

 IP65 Front

Connections 

Terminal connectors. 

                              < 

2.5sq mm terminal only.

Display             : 

4 X 17mm 7 segment Red/White display,

  4 X 8mm 7 segment Green display

  7 Iconic LEDs for Indication

Data storage 

Non-volatile flash memory

Operating temp.  : 

0°C to 60°C (non-condensing)

Operating humidity : 

20% to 85% (non-condensing)

Storage temp   : 

-25°C to 60°C (non-condensing)

Power input   

:

 230 Vac ±15 % , 50/60Hz Standard. 

  85 to 265Vac, 12/24Vdc on request.

Control output  : (For all PT244-T- / PT244-K)

  Relay : 

5A, 230V AC (Res.) or 

  SSR (field selectable) : 10V DC, 30mA

  Except -

  (For PT244-T-W2C30 / PT244-K-W2C30)

  Relay : 

10A, 230V AC (Res.) or 

  SSR (field selectable) : 10V DC, 30mA

  

(For PT244-T-W2C30AA)

  

Relay : 

16A, 230V AC (Res.) or 

  SSR (field selectable) : 10V DC, 30mA

Auxiliary output  : (For all PT244-T / PT244-K)

  Relay : 

5A, 230V AC (Res.)

Input Type 

:

 RTD : Pt100

  Thermocouple : J, K 

O

O

Resolution

0.1 C / 1 C for RTD (Pt100) input

O

  1 C for Thermocouple (J, K) input

O

Display Accuracy:

 RTD : 0.1% of F.S +/- 1 C

  Thermocouple :  0.3% of F.S

                               (20 min of settling time for TC)

Sampling Period : 

1 second

When power is On, entire display part will flash for 

3 sec, software version will flash for 3 sec and then enter in to 

RUN mode.

Initial Display when Power is ON

1. Entire display Part

2. Run Mode 

Parameter Setting Mode

Function: To set control1 set point.

1

Parameter

SET MODE

This parameter is prompted only if Relay 2 is configured in 

         ,

1. As  absolute  auxiliary  control  or  as  an  alarm  (High/Low) 

mode.

2. As  deviation auxiliary control or as a deviation alarm mode.

Note: If         set to OFF,          will not be shown in the SP 

setting.

Function: To set control2 set point.

(For 2 Relays)

2

Parameter

Min

Max

Fac.

O

0 C

Press & hold        key for 2 second.

Display will show          . 

UP/ DOWN keys. Holding the key, will change the value at a 

faster rate. Press        key to store the desired value & move 

on to the next parameter.( For 2 relays           / Dwell). Set 

value also can be stored by pressing        Key

User can change           value using 

Min

Max

Fac.

O

0 C

Function: Sets input correction.

5

Parameter

Min

Max

Fac.

In time it may be possible that the display may be offset by a 

degree or so.

To compensate for this error, user may need to add or minus 

the degrees required to achieve the correct temperature.

O

Example : 

The temperature on the display is 28 C, whereas 

O

the actual temperature is 30 C. User will have to set the "      " 

O

parameter  to  2 C,  which  means  that  once  out  of  the 

O

programming mode, the temperature on display will be  30 C 

O

O

(28 C+ 2 C).

O

-20 C

O

20 C

O

0 C

LEVEL1 Parameter

Press  &  hold          key  for  4  seconds  to  enter  into  Level1 

parameter setting(            will flash).     

When release the key,         will flash.

Press 

UP/DOWN

 keys to modify the set value and to go to the 

next parameter by pressing        key.

Press the         key to save the set value and to come out of 

parameter setting after changing the set value. 

Function: Sets the type of input sensor .

4

Parameter

Min

Max

Fac.

For J type sensor

For type of input sensor & range please refer 

"Input types 

& Input range"

 table.

While changing the sensor type        ,        ,       ,      ,       ,

        ,         parameters of level1 will reset accordingly.

Function: Sets the dwell time.

3

Parameter

Min

Max

Fac.

9999 

min

This parameter is prompted only if Relay 2  is configured in 

           as "         "

.

This parameter is prompted only if           parameter in           is 

configured as       . 

(Only for Single Relay)                             

                                     

For dwell timer operation please refer Working section.

Note: 

1) Countdown timer is displayed on the lower display. Once 

total time elapsed lower display will show  "          ". 

(Not applicable for PT244-K) 

 

2) DWL icon LED blinking indicates that dwell timer is in 

progress.  It  switches  to  continuous  ‘ON’  when  dwell 

timer is over. 

3) If Dwell time programmed as OFF, it will disable the dwell 

timer.

4) When soak in progress & dwell time is modified, new 

dwell time is applicable .

5) The dwell period  can be reduced or increased  when the 

timer is running. if it is reduced to meet the time elapsed. 

the  timer will change  to the  end state.

6) Once the timer output was energized it can be reset with

the        Reset key.

A dwell timer is used to control a process at a fixed temperature 

for a defined period. Once the process reaches  the setpoint, 

dwell  timer  starts  to  count  until  time  out  .  After  the  time   

completes,  control  output  goes  OFF  and  auxiliary  output   

energises as an alarm.

3. Dwell Timer : 

Settings

           = 

           =      min

10min