Страница 2: ... Heavy duty applications Full regulated Pure Sine Wave output PWM Controlled 5 stage ATM battery Charging Field settable heavy duty charger 6A 20A for all capacity of battery 100Ah 200Ah Reduced hardware so reduced failure rate Automatic computerized testing User friendly LCD panel for messages faults Smart overload sense and short circuit protection Great power saving DSP Sine Wave Inverter s com...

Страница 3: ...3 a Front Panel 3 6 b Back Panel 7 c Concept of Charging 8 3 Salient Features 9 11 4 Getting Started 11 a Installing the Inverter 12 13 b Operation 13 5 Batteries 15 6 Battery Requirements 14 15 7 Terminology 21 8 Trouble shooting 16 9 Technical Specifications 17 10 Warranty Card 18 REV 17 03 07 R ...

Страница 4: ...xplosive gases WORKING IN THEVICINITY OF A LEAD ACID BATTERY MAY BE DANGEROUS BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL OPERATION Provide ventilation to outdoors from the battery compartments The battery enclosures should be designed to prevent accumulation and concentration of hydrogen gas in pockets at the top DSP Inverter DSP Inverter of the compartment Vent the battery compartment from ...

Страница 5: ...tools on and around batteries It could short circuit the batteries or other electrical parts producing a spark that could cause an explosion 7 Remove personal metal items such as rings bracelets necklaces and watches when working with a battery A battery can produce a short circuit current high enough to weld a ring or any metal causing severe burns 8 Never attempt to charge a frozen battery 9 If ...

Страница 6: ...st be provided as part of the system installation GROUNDING INSTRUCTIONS This inverter must be connected to a grounded permanent wiring system KNOWING YOUR DSP SINE WAVE INVERTER In its most basic form an Inverter transforms Direct Current DC to Alternating Current AC The battery bank with the Inverter acts as a reservoir to ensure continuous supply of power whenever mains supply from utility powe...

Страница 7: ...est Transformer O K Relay Test O K _____ S W Rev PASS Inverter Switch Test H W Rev _____ Self Test DSP Sine Wave O K O K If Self test result is Fail then restart the system once or twice If still the problem exist call the Service Engineer H W and S W Revision Load Capacity connected with Inverter O P AC Voltage and Frequency Either buzzer O K or Faulty If fail then restart the system by using the...

Страница 8: ... status in mains mode whether Battery is charging or Charged a _____ I P Freq Hz ______ I P Volt V b Mains I P voltage frequency b Short Circuit Occurred with buzzer PROTECTION Short ckt Overload Remedy Check Wiring Reduce Load Restart Inverter This Display shows that Short Circuit has occurred at the out put and Inverter has gone into Shutdown immediately with continuos buzzer beep Switch OFF the...

Страница 9: ...tch OFF I PVolt _____V I P Freq _____ Hz BatteryV ____V f Mains Low Cut Inverter Switch OFF In this condition the system gets permanently shutdown For using Inverter should be switched ON if the battery is charged Mains High Cut Inverter ON BatteryV ____V O P Load _____ g Mains High Cut Inverter Switch ON The Display shows High Cut protection In this condition the system comes on Inverter mode and...

Страница 10: ...nd the black colored to the negative seeing carefully the colors and the positive and negative terminals of the battery Ensure that incoming phase or line is connected to line red wire Neutral is connected to neutral black wire and earth is connected to earth green wire After this the output is connected through the output Terminal at the rear of the inverter 7 Back Panel MAINS MCB BATTERY MCB BAT...

Страница 11: ...harging rate i e 4 to 5 Amp TAPER When the voltage level of battery is 15 more than its rated voltage the taper mode of the charger will be activated which will keep the charging current about 4 Amp to achieve the specific gravity of electrolyte for full charged battery FLOAT In float stage the charger keeps the charging voltage current level at its trickle charging set point Max 13 8V with minimu...

Страница 12: ...y and will make 4 attempts for the same If the fault condition is rectified within this period then the Inverter will reset itself automatically Otherwise it will shut off and you will have to reset the Inverter manually by turning ON OFF the switch on its front panel Protection Circuitry The Su Kam DSP Sine Wave Inverter is protected from high battery voltage low battery voltage and short Circuit...

Страница 13: ...rating when battery voltage drops to 10 more than the rated battery voltage Max 13 2 for 12V battery volts Over Current Cut Out Su Kam DSP Inverter is protected from over current conditions When the load being run demands more current the inverter shuts down automatically along with display indication there for Battery Type Optimization Su Kam DSP Sine Wave Inverter is designed to prevent damage t...

Страница 14: ...in a clean dry and well ventilated place DC Cabling Ensure that the On Off switch on the front panel of the Inverter and MCB s at the rear of inverter are in the off position before you begin the installation Connect the positive wire Red of the battery to the positive Battery terminal of the Inverter It is advised not to use any other extra cable for batteries other than those supplied by the com...

Страница 15: ...uired Without it the protection circuitry will activate and reduce the maximum power available or cause the complete shutdown of the inverter As per standards inverter should be mounted on a flat surface Note Never disconnect the battery cables while the Inverter is delivering power or battery charger is operating The ON OFF switch has no effect on the charger it turns OFF only the inverter To dis...

Страница 16: ...nstalled and connected take a moment to go back over all the connections and make sure that wiring is secure and in the proper terminals 1 Check to see that the Inverter is turned off then apply battery DC power to it Ensure that all wiring has been installed properly Next turn on the battery bank DC disconnects or connect the proper fuse in line to the battery to complete the battery circuit 2 Pu...

Страница 17: ...em with your inverter They do not hurt the inverter but they simply will not last long in a deep cycle application They use lot of thin plates to maximize the surface area of the battery This allows very high starting current but lets the plates warp when the battery is cycled Deep cycle Batteries Deep cycle batteries are best suited for use with inverters They are designed to have the majority of...

Страница 18: ...a discharge level of 80 is acceptable Totally discharging a battery may result in permanent damage to it and reduced life TERMINOLOGY Here is a description of terms with which you may not be familiar with Electrolyte Typically a mixture of water and sulphuric acid it is commonly referred to as battery acid Plates Originally made of lead now fabricated from lead oxide Plates connect to the battery ...

Страница 19: ...ean all connections Check all AC output connections Check for proper AC input and output wiring Meter must be a true RMS reading meter Refer to cable and battery recommendations in this manual Weak batteries battery cable too long Measuring with the wrong typeVoltmeter Reduce the load and restart Inverter through Power Active Switch Reduce the load and reset the mains MCB given at rear side of the...

Страница 20: ...ery 10 0V 0 2V 100Ah 200Ah BATTERY DSP Controlled PWM charging with Soft start over full range of Mains Mains Output Frequency Same as Input 45Hz 55Hz Inverter Output Frequency OUTPUT P ARAMETERS 50 0 Hz 0 1 Hz OutputVoltage with Full Load 220V Wave form Overload Short Circuit protection 5V Above 110 300 Load Few mSec MODEL CAPACITY CLS 5K 5KVA CLS 7 5K 7 5KVA CLS 10K 10KVA Pure Sine Wave TECHNOLO...

Страница 21: ...t will have to be borne by the purchaser The problem of fuse blown will not be included in the warranty of the product The services given for the same will be paid service The company is in no way are will be held liable for any loss or injury or damage caused to life or property or death and disability caused to any form of life for any reason whatsoever The warranty will not apply if the origina...