DX System
ALARMS, DRY CONTACT
Alarm conditions shall activate a red LED indicator that backlights
the alarm function key. As an option, an alarm condition may
also be enunciated by an audible alarm signal. An alarm is
acknowledged by pressing the alarm key. This calls up alarm
display screens that provide a text message detailing the alarm
conditions. After an alarm condition is corrected, the alarm can
be cleared by pressing the alarm key.
SMALL BEZEL DISPLAY PANEL
The small bezel user interface display panel features an easy
to read, backlit liquid-crystal alphanumeric display equipped
with contrast adjustment and LED illuminated function keys.
The screens that appear on the user interface display panel
present data that originates from the controller I/O module. The
controller is operated via a 6-key menu-driven loop structure and
offers an alarm log plus four different interface menu levels to
the operator: Information, Control, Service, and Factory. These
menus permit the user to easily view, control, and configure
operating parameters for the CyberRow unit.
OPTIONAL ACCESSORIES
STEAM GENERATING HUMIDIFIER
The humidifier shall be a self-contained atmospheric steam
generator. The humidifier assembly shall include an integral fill
cup, fill and drain valves, disposable steam cylinder and associated
piping. The humidifier shall be equipped with an auto adaptive
control system to optimize water conductivity, control automatic
drain/flush cycles, minimize energy waste and maximize cylinder
life. Drain water tempered fill water shall insure drains do not
exceed 140°F during operation. The humidifier shall have
modulating output between 20% and 100% of rated capacity.
ELECTRIC HEAT/ REHEAT
A factory mounted and wired low-watt density, plated fin-
tubular design electric resistance heater shall be included to
provide automatic sensible re-heating as required during the
dehumidification cycle and automatic heating mode. Electric
heaters shall be provided with miniature thermal/magnetic circuit
breakers, which shall protect each ungrounded conductor. Also
included will be one automatic reset and one manual reset over-
temperature safety device (pilot duty).
19
PRODUCT GUIDE SPECIFICA
TIONS
SMOKE DETECTION
A photo-electric smoke detector shall be factory installed
and wired in the evaporator section of the suction side of
the evaporator blower. The air conditioner will shut down
upon sensing smoke in the return air stream.
FIRESTAT
The air conditioner shall be provided with a factory wired
and mounted firestat. The firestat will shut down the air
conditioner upon sensing a high return air temperature.
REMOTE WATER DETECTOR: SPOT TYPE
A remote single point water and leak detector shall
be factory supplied and shall ship separately for field
installation. Upon sensing a water leak, the normally
closed water detector control circuit shall open, thereby
shutting down the CyberRow unit’s water producing
components.
REMOTE WATER DETECTOR: STRIP TYPE
A 20 ft. long remote strip/cable type water and leak
detector shall be provided for remote field installation.
Upon sensing a water leak, the normally closed water
detector control circuit shall open, thereby shutting down
the CyberRow unit’s water producing components.
CODE CONFORMANCE
The supplied system shall be provided with the following
compliance approvals:
Heating and Cooling Equipment UL 1995 / CAN C22.2
No. 236-11 4rd edition.