-SCS C
ONDENSER
IOM
M
ANUAL
20
R410A) or your summer maximum operating head pressure.
Hold the pressure steady at this setting. You should observe
that cycling “Off” on head pressure will not occur now or
during warmer temperatures.
If a refrigerant level sight glass is included on the side of the
receiver (optional), it may be used to assist in charging the air
conditioning system. The proper charge can be confirmed by
viewing the level of refrigerant in the receiver while the unit
is running at an elevated discharge pressure (320 psig for
R407C; 440 psig for R410A).
Add refrigerant charge until the refrigerant appears in the
sight glass indicating the receiver is 80% filled. When the
level of refrigerant in the receiver reaches the sight glass,
the unit is fully charged.
CAUTION
Remove the blockage to the air intake of the condenser.
2.7.4.2.2
Final Adjustment
Now you may adjust the condenser fan settings to assist
with low ambient control. The following settings have proven
effective:
R407C Refrigerant
Fan 1 - 320 psig cut-in; 240 psig cut-out
Fan 2 - 330 cut-in; 250 cutout
Fan 3 - 340 cut-in; 260 cutout Fan
Fan 4 - 345 cut-in; 265 cutout
EC Fan (Fan 1 on SCS Condenser) - 240 psig start;
65 psig differential
R410A Refrigerant
Fan 1 - 440 psig cut-in; 330 psig cut-out
Fan 2 - 460 cut-in; 355 cutout
Fan 3 - 475 cut-in; 365 cut-out
Fan 4 - 485 cut-in; 375 cutout
EC Fan (Fan 1 on SCS Condenser) - 340 psig start; 100
psig differential
Fill out the applicable sections of the Warranty Registration
and Start-Up Checklist.
2.8
Refrigerant Characteristics
2.8.1
Pressure/Temperature Settings
Table 8 is provided to assist with the normal settings of the
system for R407C and R410A refrigerant. Where applicable,
minimum and maximum settings are given along with normal
operating pressures.
NOTE: The operating pressures for R410A refrigerator
significantly higher than R407C.
Table 8. Refrigerant
Pressure/Temperature Settings
Refrigerant Pressure/Temperature Settings
Sub-cooling °F
Normal
10
Min.
5
Max.
20
Superheat °F
15
10
20
Design Condensing Temp. @ 95 °F
Ambient
125
105
140
Suction Pressure (psig)- R407C
70
55
85
Suction Pressure (psig)- R410A
130
105
155
Fan Cycling Control- Fan On (psig)-
R407C
320
240
340
Fan Cycling Control- Fan On (psig)-
R410A
440
330
480
Fan Speed Control (psig)- R407C
320
-
-
Fan Speed Control (psig)- R410A
440
-
-
2.8.2
Saturated Refrigerant Pressure Tables
The following refrigerant vapor pressure tables are provided
for reference for R407C and R410A refrigerant.