DEZ
S
ERIES
1000
I
NSTALLATION
,
O
PERATION AND
M
AINTENANCE
M
ANUAL
5
Electric heat is generated by a heater controlled by
an SSR (solid state relay) or SCR (silicon
controlled rectifier). The SSR cycles the heater on
and off based on signals received from the system
controller to maintain the reactivation discharge air
temperature. An SCR also receives controller
signals, but modulates the percentage of heater
output energy (as opposed to turning the heater on
and off) for tighter temperature control.
There may be more than one heater bank
depending upon the output required. Refer to the
Electrical drawing and technical data sheet for more
detail.
NOTE:
The reactivation air temperatures mentioned in
the preceding discussion may vary between DEZ
systems. See the Technical Data Sheet for your unit
for target temperatures.
Figure 2 - General Theory of Operation Diagram
1.5 Construction
This desiccant dehumidifier was manufactured by
STULZ and has passed all Quality Control checks,
including a complete functional testing. Every effort
has been made to ensure the dehumidification system
will perform satisfactorily for many years.
1.5.1 Design
Features
Rugged
All-Aluminum
Cabinet
Continuous or Automatic Operation
Inert, Stable Silica Gel Desiccant
Non-toxic, Non-corrosive Desiccant
Capable of Withstanding 100% RH Without
Adverse Effect
Counterflow Process and Reactivation Air
Patterns
Overheat Safety Protection
Electric Reactivation Heat
Easy Access to Internal Components
Low Operating Cost, Energy Efficient
Dehumidification
Optional Process and Reactivation Inlet Air Filters
For a comprehensive list of the features included,
refer to the DIN Sheet provided specifically for this
unit. The DIN sheet is a listing of all the standard and
optional features that are included (see section 1.2.2).
For particular detail of the features, refer to the
drawings provided with this unit.
1.5.2 Cabinet
This unit is self-contained in an aluminum cabinet
rated for either indoor or outdoor use (see Unit
Nameplate). The exterior of the cabinet is finished
with a durable paint to protect it against corrosion.
Removable access panels are provided for easy
access to all major components for maintenance
and/or service.
The operator controls are conveniently located in the
front of the unit (see the installation drawing provided).
The cabinet houses the desiccant rotor assembly and
drive system, process and reactivation air blowers, a
Process
Air Outlet
Process
75% of rotor
Reactivation
25% of rotor
Desiccant
Rotor
Process
Air Inlet
Reactivation
Air Outlet
Process
Air Filter
Reactivation
Air Blower
Process
Air Blower
Reactivation
Air Filter
Reactivation
Heater(s)
Reactivation
Air Inlet