9
8
L
N
L1 L2 L3
L
N
Wiring
AC out connection
• Up to 3x10mm
2
cable, 1.6Nm
Protection device to protect cables
Up to 56Aac, circuit breaker type B
Protection device to protect people
Up to 56Aac, RCCB/RCD, check
earth scheme
Overvoltage protection, SPD
AC in connection
• Up to 3x10mm
2
cable, 1.6Nm
Protection device AC
50Aac, circuit breaker type B
Overvoltage protection, SPD
M10 cable
washer
fusible
ceramic
washer
bolt
M8 x 30
EN
The device must be installed in accordance with local standards and regulations in force.
FR
L’appareil doit être installé conformément aux normes et réglementations locales en vigueur.
DE
Das Gerät muss gemäß den geltenden örtlichen Normen und Vorschriften installiert werden.
ES
El dispositivo debe instalarse de acuerdo con las normas y regulaciones locales vigentes.
Remote control rcm 10
• 1x RJ 11 black flat cable
Bus termination
Communication
• 2x RJ 45 black flat cable :
rcc 02/03 / multi-units :
xtender, vt, vs, bsp, xcom
M8
T10
Battery connection
• 70mm
2
cable M8, 10Nm
xtm 1500-12
xtm 2000-12 xtm 3500-24
• 50mm
2
cable M8, 10Nm
xtm 2400-24 xtm 4000-48
• 35mm
2
cable M8, 10Nm
xtm 2600-48
Protection device (battery side)*
• 150A
xtm 2600-48
/ 200A
xtm 2400-24 xtm 4000-48
• 250A
xtm 1500-12
/ 300A
xtm 2000-12 xtm 3500-24
*Internal fuse provided on bat+, recommended external fuse
BAT+, M8
BAT-, M10
Temperature sensor bts 01
• 1x RJ 11 black flat cable
*Bat+ connection
(provided)
Lithium batteries
communication
BMS CAN
xcom CAN
CAN
Li
Auxiliary Contacts
AUX1
AUX2
NC C NO
Jumpers
L1 L2 L3
* Check
xcom CAN
manual