background image

STUDER 

INNOTEC 

 

      HP-COMPACT 

 
 
 

User manual 

HP-COMPACT V3.0 E 

22  

COMPACT which is indicated with a LED. The programming is possible for one or more 
operating situations. If the contact is programmed for many situations, it is activated as 
soon as the HP-COMPACT finds itself in any one

 

of the programmed situations. That 

means that the work of the contact meets that of the logic OR–Function.

 

5.4.2  The programming of the Auxiliary Contact is carried out in the following 

Steps 

The Push Button 21 (Program) presses down for min. 2 seconds. The LED 4 „Program“ is 
lit as an indication, that the HP-COMPACT is in program mode. 
A blinking LED shows the programmed condition for the auxiliary contact (LED 10/11/ 
12/13 factory setting). 
With the Push Button 20 (select), select the desired condition in which the contact should 
be activated. 
With the Push Button 19 (Change status) confirm or change the status for this condition. 
If desired, with the Push Button 20 (select) select another condition in which the contact 
should be activated. 
With the Push Button 19 (Change status) confirm or change the status for this condition. 
If during 20 seconds no buttons are pushed, then the settled values are automatically 
stored and the HP-COMPACT switches back to normal operating condition. 

5.4.3  Auxiliary Contact as generator starter 

As per the battery capacity 

When in the programming of the Auxiliary Contact, the Battery Capacity (LED 15-18) is 
used as a condition, you must then take note of the following requirements.  
If you have to start an emergency back-up supply with a battery having a certain residual 
capacity, then two battery levels must be programmed.  The first (i.e. Battery 25% LED 17) 
for the starting or activating the Auxiliary Contact and the second (i.e. Battery 100% 
LED15) for stopping or disabling the Auxiliary Contact. Programmed like this the Auxiliary 
Contact works with the lowest set condition and stops when it has reached the highest 
programmed condition through charging. 

 
Example: start of a genset with the HP-COMPACT 

In order to program the auxiliary contact to start at 25% and to stop at 75% of the battery 
state-of-charge, here is the procedure to follow: 

-  Press the key AUX. CONTACT (Program) 21 during at least 2 seconds. Then the 

states will be displaid blinking (factory settings LED’s 10/11/12/13). As these states 
are not wished for the start of the genset, they must be disabled. 

-  With the key (select) 20, select the LED’s to disable (the active LED’s are blinking) 

and disable them with the key 19 Change Status. Select the other LED’s to switch 
off with the key (select) 20 and switch them off with the key 19 Change Status until 
all are disabled. 

-  Then select the LED 17 with the key (select) 20 and activate the contact with the 

key 19 Change Status. The genset will start once the LED 17 

switches of

.  

-  Then select the LED 16 with the key (select) 20 and activate the contact with the 

key 19 Change Status. The genset will stop once the LED 16 

switches on

.  

-  If no key is activated during 30 seconds, the normal operation states are displaid 

automatically again. 

For a control the key Program can be pressed at least 2 seconds. The values set are dis-
plaid blinking. 

 
 

Содержание HP-COMPACT HPC 2512

Страница 1: ...attery charger Transfersystem HP COMPACT HPC 2512 HP COMPACT HPC 4024 HP COMPACT HPC 5048 HP COMPACT HPC 7048 Remote control RCC 01 Remote power sharing RPS 01 Temperature sensor CT 35 STUDER INNOTEC TEL 41 0 27 205 60 80 Rue des Casernes 57 FAX 41 0 27 205 60 88 CH 1950 SION E MAIL info studer inno com ...

Страница 2: ...NNECTION PLAN 9 3 5 CABLING 9 3 6 PRE INSTALLATION SETTINGS 10 4 CONTROL 12 4 1 DISPLAY AND CONTROL PARAMETERS 12 4 2 LIGHT EMITTING DIODES LED 12 4 3 PUSH BUTTONS 13 4 4 TURNING KNOBS 13 4 5 THE INVERTER 13 4 6 THE BATTERY CHARGER 15 4 7 THE TRANSFER SYSTEM 17 4 8 THE MULTIFUNCTIONAL CONTACT 18 4 9 THE REMOTE CONTROL 19 4 10 THE TEMPERATURE SENSOR 19 4 11 REMOTE CONTROL FOR POWER SHARING 20 5 PRO...

Страница 3: ...pliances are totally carried out in our company in Sion Switzerland The warranty for these appliances is valid for uses and operating possibilities mentioned in this manual The warranty period for the HP COMPACT is 2 years 1 3 Warranty Disclaimer We do not accept any liability for any damages occurring through use manipulation wor king situation and handling which are not explicitly mentioned in t...

Страница 4: ... you must switch on the HP COMPACT ON with the ON OFF switch After one minute the electronics are discharged and any work can now be safely carried out The HP COMPACT is only suitable for internal use and under no circumstances should it be subjected to snow rain or any other wet conditions By installations in motorized vehicles the HP COMPACT must be protected from water spray and any other wet c...

Страница 5: ...S FET power transistors a toroidal transformer and a fast regulating system makes a robust and reliable inverter with the highest efficiency A 1 20 Watt adjustable charge de tection system allows the smallest energy consumption and ensures a long life for the bat tery 2 2 2 The transfer system HP COMPACT can be connected to an AC source For example a stand by emergency generator or the AC network ...

Страница 6: ...ntrol As an option a remote control RCC 01 can be connected to HP COMPACT All operating features and displays save the adjustment levels 22 23 24 26 are available on the re mote control It is supplied with a 20m long cable This cable can be up to 40m long On the remote control output power and charging current are also displaid 2 2 5 Remote control for Power Sharing This remote control RPS 01 can ...

Страница 7: ...onnection in parallel and in serie 3 Mounting and installing 3 1 Installation place The location of the HP COMPACT must be driven by the following criteria Protection from unauthorized handling Dry dust free room no condensation Never install directly over the battery and never in a cabinet together with the batteries Keep ventilation holes free In mobile installations it is important to keep the ...

Страница 8: ...ection on the terminals AC INPUT AC OUTPUT must comply with the local rules All connecting cables and also the battery cables must be fixed with strain relief clamps The fuses supplied with the HPC4024 5048 and 7048 have to be installed see descrip tion in 3 4 The cable cross section for the HP 2512 4024 5048 and 7048 is resp 95 70 50 and 70 mm2 and their length must be as short as possible max 2m...

Страница 9: ...ion plate with Technical data and Serial number K AC Output Connection terminal for AC output L Reserved M Hole Pass through hole for RCC 01 CT 35 and RPS 01 N Protection Thermal circuit breaker 30A 50A for HPC7048 for the Transfer system 3 5 Cabling Connecting the HP COMPACT is a very important step of the installation You must take care that all connection work is carried out in a clean and corr...

Страница 10: ... mounted according to the plan below 3 6 1 2 On the battery side Caution before connecting the battery check carefully the voltage and the battery polarity with a voltmeter A polarity reverse will seriously damage the inverter for example con necting a HPC2512 to a 48V Battery Get the batteries ready for connection suitable terminals fuse on one of the connection points cable in good shape with if...

Страница 11: ...ntact are max 16A 250Vac The LED 5 Contact active shows the position of them alight mind active and off mind non active The schematic view of the connections on the front show the relay in the non active mode 3 6 5 Connection to Remote control The Remote Control RCC 01 is connected in the terminal marked Remote control with a 20m long cable and a RJ11 8 connector The Remote Control can be plugged ...

Страница 12: ...ger is working The battery charger is locked OFF see chap 4 6 or provisory out of order In that last case it will restart within 10 seconds OFF AC OUT AC IN Over Temp Overload ON OFF Batt Low High Contact manual AUX CONTACT 100A 150V 20W OFF 0 Contact active Program STANDBY CHARGER Charger Inverter Program Change status select CHARGER INVERTER RESET ALARM TRANSFER EQUALIZE 230V 1 4 5 21 6 2 14 23 ...

Страница 13: ...Absorption time is run ning 25 POWER MONITOR Display the value of the output power in of Pnom in Inverter Mode and the charge current in Amps in Charger Mode In this mode the red LED indicates that power sharing is in use 100A 4 3 Push buttons 19 ON OFF Turning the HP COMPACT on and off Help Button for Program ming 20 RESET Alarm Signal off Help Button for Programming 21 Aux Contact Control Aux co...

Страница 14: ...time or it has been working in too high sur rounding temperatures it will switch off The LED 10 Over Temp is lit and the LED 13 OFF blinks After cooling down the inverter switches back on automatically One minute before the inverter switches off for too high temperature it gives out an acoustic alarm sig nal If the Auxiliary Contact has been programmed to detect the high temperature then it synchr...

Страница 15: ...recommended for the lead acid batteries in order to mix well the electrolyte fluid and to clean the lead plates Equalization mode should never be used when using Gel Batteries If the HP COMPACT is operating with a lead acid battery which is suitable for equali zation the slide switch Equalize which is on the cable connection side must be placed in the ON position In this setting every 25 charge cy...

Страница 16: ... circuit breaker i e 6A before the HP COMPACT then you set this value on the turning knobs 26 i e 6A This adjustment can be done remotely with the optional RPS 01 see section 3 6 7 In that case the smallest values will be taken into account 4 6 4 Charging current The maximum charging current for the battery can be adjusted with the Turning Knob 22 CHARGER The charging current of the battery should...

Страница 17: ...est adjusted value set by the Turning Knob 23 TRANS FER and the frequency is between 44Hz and 65Hz this voltage is switched directly to the battery charger and to the output AC OUT The LED 7 TRANSFER is lit The inverter is switched off and the battery charger switched on This process is automatic unless the charger mode or the transfer mode is disabled see Chap 5 5 The maximum current of the Trans...

Страница 18: ...tor i e start of a vacuum cleaner etc has the effect of decreasing the voltage for a short time As in such cases the transfer to the Inverter is not desired the transfer system can be programmed with a delay When the slide switch Transfer delay is in the On position the transfer to the inverter takes place with a delay of 5 seconds If the voltage falls below 100Vac the transfer takes place without...

Страница 19: ...t max 0 5A which is independent from the Auxiliary Contact of the HP COMPACT This con tact is active in case of an alarm of the HP COMPACT The Control Input is connected in parallel to the ON OFF push button The HP COMPACT can be switched on or off through this input with an impulse button or an impulse contact Order Number for Remote Control RCC 01 Dimensions H x B x T 111 5 x 136 5 x 25mm Cautio...

Страница 20: ...s means that the connected generator will be over loaded or that the circuit breaker before the HP COMPACT will break 5 Programming 5 1 Standard setting The HP COMPACT is delivered with the following default setting 5 1 1 Battery voltage Low voltage 11 6V 23 2V 46 4V Float Charge 13 5V 27 0V 54 0V End of Charge Voltage 14 4V 28 8V 57 6V Equalization 15 3V 30 6V 61 2V Absorption Time 2 Hours 5 1 2 ...

Страница 21: ...d LED s show the function set Low voltage LED 13 ON OFF Float charge LED 12 Batt Low high Absorption End of charge LED11 Overload Equalization LED 10 Overtemp Absorption Time LED 10 11 12 13 altogether With the Push Button 19 Change status set the desired parameter voltage or time to modify LED 14 15 16 17 18 Push Button 19 Change status to set the desired value according to the table 5 3 1 If des...

Страница 22: ...wing requirements If you have to start an emergency back up supply with a battery having a certain residual capacity then two battery levels must be programmed The first i e Battery 25 LED 17 for the starting or activating the Auxiliary Contact and the second i e Battery 100 LED15 for stopping or disabling the Auxiliary Contact Programmed like this the Auxiliary Contact works with the lowest set c...

Страница 23: ...ontact The Auxiliary Contact can be operated at any time with the Push Button 21 AUX CON TACT The LED 6 Contact manual lights up as information that the Contact is manually operated and LED 5 Contact active lights up when the Contact is active By pushing the Push Button 21 a second time the Contact is disabled By pushing it the third time auto matic functions are restored 5 5 Disabling some of the...

Страница 24: ...itch function is enabled in input voltage and frequency is OK 6 Installation Maintenance Apart from the periodic controls mentioned for the connections the HP COMPACT does need any maintenance Keep the appliance clean and from time to time wipe it clean with a damp cloth 7 EC Compliance Hereby we state that the products described in this user manual comply with the following standards EN50081 I II...

Страница 25: ... 50 A Maximum input voltage 265 Vac Minimum input voltage Adjustable threshold from 150 to 230 Vac Input frequency 45 65 Hz Power Factor Correction PFC EN 61000 3 2 Battery control thresholds and times adjustable by the user Absorption time 0 4h End charge cycle voltage 14 4 V 28 8 V 57 6 V 57 6 V Floating voltage 13 6 V 27 2 V 54 4 V 54 4 V Equalisation voltage 15 6 V 31 2 V 62 4 V 62 4 V Deep di...

Отзывы: