888 Porter Rd. Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com
VENTING INSTRUCTIONS FOR AIR INTAKE / EXHAUST - DO3637R
6
BACK VIEW OF CABINET
AFTER POSITIONED ON
CUSTOMER-SUPPLIED COUNTER/BASE
19”
MINIMUM
AIR
EXHAUST
SPACE
13” MINIMUM
AIR
INTAKE SPACE
9 1/2”
Warning: The minimum intake and exhaust areas must be allowed (as illustrated
below) or case temperatures may fluctuate beyond safe parameters.
FACIA ENCLOSURE
13” MINIMUM
AIR INTAKE
SPACE
10 1/2” MIN.
AIR EXHAUST
SPACE
15” MINIMUM
MAINTENANCE
ACCESS
SPACE
32” MINIMUM MAINTENA
NCE
ACCESS SPACE
9 1/2”
NOTES:
1. BACK OF CABINET MUST BE VENTED A MINIMUM OF 13” x 13” FOR AIR INTAKE.
2. BACK OF CABINET MUST BE VENTED A MINIMUM OF 10 1/2” x 19” FOR AIR EXHAUST.
3. BACK OF CABINET MUST PROVIDE A MINIMUM OF 15” x 32” FOR MAINTENANCE ACCESS. THIS AREA (AS
DIMENSIONED BELOW) WILL ALLOW SERVICE TO SLIDE OUT CONDENSING UNIT.
4. SEE REFRIGERATION FUNDAMENTALS FOR VIEW OF CONDENSING UNIT AFTER SLIDE-OUT.
5. AIR
INTAKE
(ILLUSTRATED
BELOW).
6.
AIR EXHAUST
(ILLUSTRATED
BELOW).