11.2 Troubleshooting table
Numbers are corresponding with Table 7
Table 7: Troubleshooting table
1.
Check cable or replace the cable, check that the cable is connected to the correct connector strip.
2.
Replace room thermostat or cable: has the correct thermostat been used?
3.
Replace sensor or find cable fault.
4.
Try and loosen the pump spindle, or replace the pump drive.
5.
Add water and detect leak, also check the expansion vessel for leaks.
6.
Too much water added; drain, check the pressure in the expansion vessel for correct air cushion
pressure(only check with 0 water pressure) replace the expansion vessel if defective
7.
Place the plug: with the cables on the fan side.
8.
Clean the fan blades.
9.
Replace the fan
10.
Open gas valve.
11.
Check line and gas meter, make a resistance calculation, as required.
12.
Change gas lines.
13.
14.
Check fuse F4- check all 230 V connections: pump, PCB.
15.
16.
See paragraph 6.4
17.
Check the cabling using the wiring diagram, check the connection to the gas valve, be aware of
moister
18.
Check cable for short-circuit, overheating, nearby or jammed between steel plate; check spark
plug cap for cracks, replace cap.
19.
Replace the burner control.
20.
Moister trapped, check the cable sockets which should fit tightly around the plug pins, check the
position of the cable socket, possibly adjust before the plug slides in.
21.
Check that the plug(s) are fitting tightly.
22.
Open the drain line (left-hand side of the boiler) by unscrewing the cap. Keep a jug on hand to
catch the amount of water drained. Poke through the line using a pen, moving left upward and
right upward. Take the burner unit from the boiler as required and pour some water in the heat
exchanger to rinse out the siphon.
23.
Bleed the unit, not only the boiler itself but the entire system – in the event of such overall de-
aeration it is recommended to remove the 230 V off the boiler from the wall switch as the CH
pump should not be activated during the process.
24.
Check the cut-off valve of the three-way valve. Take the pump motor out by unscrewing the four
fastening screws. Check the valve on the inside of the housing.
The driving motor can be removed by taking out the fastening screw at the front of the housing
(right bottom) and subsequently pressing the “snap in” lug on the side of the housing, just above
the motor, while pressing the motor down at the same time.
25.
Check the air inlet and flue lines for blockage.
26.
Check the inlet and flue system.
27.
See 26.
28.
29.
REPLACE THE BOILER
30.
Replace the high-limit thermostat by unscrewing from the brass nut: no draining is needed (do not
remove the brass nut).
31.
Go over the settings as outlined in paragraph 6.6.1.
Содержание SC-B
Страница 5: ...Page 5 of 51 2 TYPICAL SYSTEM LAYOUTS 2 1 Single Boiler Layout ...
Страница 42: ...Page 42 of 51 14 EXPLODED VIEW DIAGRAMS ...
Страница 45: ...Page 45 of 51 14 2 Burner fan gas pipe heat exchanger casing S CB 150 S CB 180 Figure 5 S CB150 S CB 180 ...
Страница 47: ......
Страница 49: ...Page 49 of 51 14 4 Pipes pump S CB 150 180 Figure 6 S CB 150 S CB 180 ...