background image

SYNERGII SHOWER PANEL  

- RETROFITTABLE -  

RIGHT HAND OPERATION 

SY02930

INSTALLATION AND CARE INSTRUCTIONS

Important Information

• Hot and cold water inlet pressures should be equal.
•  Operating static pressure is 300—500kpa. If pressure exceeds this, then an 

approved pressure limiting valve must be fitted.

•  Pipework must be flushed out prior to installation of the shower panel. Damage 

caused to the shower panel by debris coming through the pipework is not 
covered under warranty.

•  Installation should comply to AS/NZS3500.1 2003 or the relevant local 

requirements.

• Maximum hot water temperature is 75°C. 
• Not suitable for gravity feed applications.

 

 

Maintenance and care

•  Using a soft cloth with a mild detergent or soap is all that is required to clean 

surfaces.

•  Do not use abrasive cream cleaners or citrus based cleaning products. These will 

damage the surface.

•  The spray channel of overhead shower is protected by a self-cleaning system. If 

scale deposits are noticed in the spray channel, turn water on lightly and rub the 
spray channels with a finger or sponge. 

WARRANTY

Guarantee

 

Arcisan shower panels are covered by a 7 year conditional residential warranty subject to 
the terms below.
>  7 year product or parts warranty against manufacturing defects. (Hoses and hand sprays 

on kitchen mixers are 2 years).

> 1 year replacement product or parts and labour warranty.
Streamline reserves the right to assess, fix, replace or service warranty claims as they see fit. 
The warranty period applies from date of purchase or date of handover for new buildings. If 
this is not available, the manufacturing date stamp on the product will be used.
Warranty claims should first be directed through the point of purchase. It is mandatory that 
the purchaser provide proof of purchase and the warranty is valid for the original purchaser 
only and is not transferable.

Exclusions

 

The warranty does not apply to the following cases:
•  Blocked or damaged aerators are not covered under the warranty. Other damage caused 

by not flushing the system before connection or use.

•  Damage caused by improper installation, abuse, accident and misuse. Also previous repair 

or alteration without the company’s or agent’s permission.

•  Warranty only applies to items purchased through an authorised re-seller within Australia.
•  Tapware used in a commercial setting. This is subject to a 1 year parts and labour warranty.
•  General wear and tear from normal use of the product, including scratching from cleaning.
•  Water temperature or pressure exceeds the stated maximums. The maximum water 

pressure is 500kpa and maximum temperature is 75 degrees Celsius.

Consequential Damages

 

Streamline Products will not liable for damage to other items (floor coverings, walls, lights 
and other fittings) or any other type of consequential losses caused by a defect in the 
product, except when the failure amounts to a major failure under your statutory rights.

Statutory Rights

 

Our goods come with guarantees that cannot be excluded in the Australian Consumer Law. 
You are entitled to a replacement or refund for a major failure and for compensation for 
any other reasonably foreseeable loss or damage. You are also entitled to have the goods 
repaired or replaced if the goods fail to be of acceptable quality and the failure does not 
amount to a major failure.

Contact

 

This warranty is provided by Streamline Products P/L 
Phone: 1300 735 352  
Email: [email protected]

Содержание Arcisan Synergii SY02930

Страница 1: ... will be used Warranty claims should first be directed through the point of purchase It is mandatory that the purchaser provide proof of purchase and the warranty is valid for the original purchaser only and is not transferable Exclusions The warranty does not apply to the following cases Blocked or damaged aerators are not covered under the warranty Other damage caused by not flushing the system ...

Страница 2: ...agram Step 2 Concealed water connection Screw flexible hose from back of shower panel onto wall connection Do not over tighten the nut Once the connections are made turn on mains water to check for leaks Step 3 Carefully hang the shower panel onto the mounting brackets ensuring that both top and bottom brackets are resting in the correct location on the back of the panel Once the panel is in place...

Страница 3: ...otice Information provided within this specification sheet is correct at the date of printing Please confirm all particulars with your sales consultant prior to purchase Version 1 0 May 2017 www streamlineproducts com au Ph 1300 735 352 Height set up for Synergii Shower Panel Right Hand Operation SY02930 1530 X Mounting bracket 110 200 400 600 520 ...

Страница 4: ... specification sheet is correct at the date of printing Please confirm all particulars with your sales consultant prior to purchase Version 1 0 May 2017 www streamlineproducts com au Ph 1300 735 352 Concealed water point installation for Synergii Shower Panel Retrofittable SY02930 X Mounting bracket Mounting bracket 565 30 50 Water inlet zone is between X and X 400 Water inlet 1 2 BSP ...

Отзывы: