Powering On the System
2-32
Stratus ftServer V 2404, V 4408, V 6408, and V 6512 Hardware Installation Guide
(R004S)
12. If there is unused space above the tape-drive enclosure, install 1U filler panels in
the unused spaces. Insert the filler panel by aligning the metal clips on the back of
the filler panel with the square holes in the cabinet and pressing straight in. The
filler will snap into place.
N O T E
The longer decorative groove in the front of the filler panel
goes on the right.
Powering On the System
This section discusses the following topics:
“Powering On the Components” on page 2-32
“Powering On the ftServer System” on page 2-38
Powering On the Components
Perform the following steps to power on the system’s components.
1. To power on the PDUs, perform steps
through
for each PDU in the system.
N O T E S
1. The system has four PDUs if it is shipped with a
network I/O enclosure or is shipped with a full
complement (six) of ftScalable Storage trays. The
system has two PDUs if it is shipped without a
network I/O enclosure and less than six ftScalable
Storage trays.
2. The system has dual power cords for all of its
components. Do not plug both power cords into the
same PDU.
a. At the rear of the cabinet, connect the power-jumper cords (number
3
in
) from the system components to the PDU.
b. Connect the PDU power-input cord (number
2
) to the PDU and
to a separate AC power source.
c. Turn on the breaker switch (number
1
).