Electrical (AC) Power Planning
4-1
Chapter 4
Electrical (AC) Power Planning
4-
For information about planning appropriate AC electrical power for your ftServer
systems, see:
•
“Redundant Power Sources” on page 4-1
•
“AC Power Service Requirements” on page 4-2
•
“Power Outlet Requirements” on page 4-5
•
“Connecting a System Directly to Two Separate Power Sources” on page 4-7
•
“Stratus-Supplied Power Cords” on page 4-9
Related Topics
•
•
Chapter 7, “ftServer Rack Configuration Planning”
Redundant Power Sources
ftServer systems and storage enclosures require at least two separate and
independent AC power sources: an
A-side
power source and the
B-side
power source.
Either side must be capable of continuing to provide power if power to the other side is
lost.
The A-side power source provides power to each system and to one half of each
storage enclosure, as well as to components that do onot rquire two sources of power:
a modem, tape drive, or monitor. If you use a universal power supply (UPS), the UPS
is the A-side power source.
The B-side power source also provides power to each system, in stand-by mode (the
B-side power source is used if power to the A-side source is interrupted), and provides
power to the other half of each storage enclosure.
The wattage required from the A-side power source will always be equal to or greater
than the wattage required from the B-side power source.
Содержание ftserver 3300
Страница 1: ...Stratus Technologies R553 01 Stratus ftServer 3300 5600 and 6600 Site Planning Guide...
Страница 10: ...Tables x Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553 Table D 4 Noise Standards D 2...
Страница 14: ...Preface xiv Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Страница 24: ...System Documentation 1 10 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Страница 32: ...Planning for Cables 3 4 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Страница 50: ...Stratus Supplied Power Cords 4 18 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Страница 62: ...Connecting ftServer Systems Directly to a UPS 5 12 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Страница 100: ...Rack Mountable ftServer 3300 System Specifications A 16 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Страница 133: ...Standards Compliance Standards Compliance D 3 VCCI Note BSMI Note...
Страница 134: ...Standards Compliance D 4 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Страница 138: ...Index Index 4 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...