background image

AAP87600 PDU Specifications

 

System Specifications

A-9

Table A-4

 lists the specifications for the AAP87600 PDUs.

Table A-4. AAP87600 PDU: Specifications

Power

Input power

N/A

Nominal input voltage; frequency

200–240 VAC; 50/60 Hz

Physical Dimensions

Height

1.75 in. (4.45 cm)

Width

19.1 in. (48.51 cm)

Depth

6.75 in. (17.15 cm)

Environmental

Operating temperature during 

operation

41

F to 95

F (5

C to 35

C)

For every 800 ft (243.8m) above 2000 ft (609.6m), lower 

the maximum operating temperature (95

F (35

C)) by 

1.8

F (1

C).

Maximum rate of temperature 

change during operation

12

C per hour or 0.2

C per minute

Relative humidity during 

operation

10% to 80% (noncondensing)

Storage temperature to 40,000 ft 

(12.2 km)

-38

F to 140

F (-40

C to 60

C)

Relative humidity during storage

5% to 95% (noncondensing)

Содержание ftServer 2600

Страница 1: ...Stratus Technologies R638 02 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide...

Страница 2: ...cument may be copied reproduced or translated either mechanically or electronically without the prior written consent of Stratus Technologies Stratus the Stratus logo ftServer and the ftServer logo ar...

Страница 3: ...AC Power Outlet Requirements 2 4 Connecting a System Directly to Separate AC Sources 2 6 Selecting a UPS Unit for ftServer Systems 2 8 Communicating with a UPS over a Network 2 10 Connecting Power to...

Страница 4: ...and Monitor Requirements 6 1 Cabinet Requirements 6 1 Monitor Requirements 6 5 Appendix A System Specifications A 1 System Specifications A 1 PCI Adapter Specifications A 7 AAP87600 PDU Specifications...

Страница 5: ...ail Clearance 6 4 Figure A 1 ftServer 2600 4500 or 6300 System CPU I O Enclosures Front View A 2 Figure A 2 ftServer 2600 4500 or 6300 System Rear View A 3 Figure A 3 AAP87600 PDU A 8 Figure B 1 Star...

Страница 6: ...Outlet Requirements No PDUs 2 5 Table 2 8 Worksheet B Side External Power Outlet Requirements No PDUs 2 5 Table 2 9 APC Symmetra Models for PDUs or for Multiple Systems 2 9 Table 2 10 APC UPS Models f...

Страница 7: ...System CPU I O Enclosure Specifications A 5 Table A 3 PCI Adapter Specifications A 7 Table A 4 AAP87600 PDU Specifications A 9 Table B 1 Connectors for AC Power Outlets B 9 Table C 1 Compliance Standa...

Страница 8: ...Tables viii Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...

Страница 9: ...ort for ftServer System Software for VMware vSphere Release 3 0 0 throughout A clarified warning New compliance information in Appendix C Minor corrections throughout Notation Conventions This documen...

Страница 10: ...es For example Many hardware components are customer replaceable units CRUs which can be replaced on site by system administrators with minimal training or tools copy filename1 filename2 Pass a pointe...

Страница 11: ...tratus com A copy of StrataDOC on supported media for your system is included with this release To order additional copies of the StrataDOC media or to obtain copies of printed manuals do one of the f...

Страница 12: ...our authorized Stratus service representative For information about how to contact the CAC see the following Web site http www stratus com support cac Commenting on the Documentation To provide correc...

Страница 13: ...page 1 10 Site Planning Overview Site planning for fault tolerant systems includes Purchasing an appropriate cabinet and monitor If you do not purchase a monitor from Stratus provide a monitor that me...

Страница 14: ...o your ftServer system see System Documentation on page 1 7 During the site planning and preparation processes work closely with your facilities group or contractor to determine space power andenviron...

Страница 15: ...ASN Connecting a system tothe ASN allows the CAC oryour authorized Stratus service representative to remotely diagnose troubleshoot and resolve problems online To enable connectivity to the ASN an AS...

Страница 16: ...adapters If so in Table 1 1 indicate the total number of ports and plan network connections for all Ethernet ports you will use N O T E The combined four ports of the two embedded physical adapters pr...

Страница 17: ...in a storage area network SAN configuration If so do you have a minimum of two switches that can accommodate the cables from the pair of Fibre Channel HBAs in each ftServer system N O T E Stratus has...

Страница 18: ...tside the cabinet What are the lengths and types of the interface and communications cables that will connect to your system Have you created a sketchof how you plan toarrange the system at the in sta...

Страница 19: ...inux systems or Table 1 5 for VMware ESX systems Table 1 2 ftServer 2600 4500 and 6300 System Documentation Document Task Stratus ActiveService Network Configuration Guide R072 Configure your system f...

Страница 20: ...icant known problems and how to work around or avoid the problems Stratus ftServer System Software Installation and Configuration for Windows Systems R002W Respond to Mini Setup questions Install or r...

Страница 21: ...ftServer System Software and BIOS and BMC firmware Stratus ftServer System Administrator s Guide for the Linux Operating System R003L Use tools that are provided by the operating system software ftSer...

Страница 22: ...the system start installing systems from the bottom of the cabinet upward Stratus ftServer System Administrator s Guide for VMware vSphere R002E Use tools that are provided by VMware vSphere ftServer...

Страница 23: ...er the equipment W A R N I N G To prevent fire or current leakage do not plug the power cord into a nonconforming outlet Use a power outlet with appropriate voltage and power type as specified in this...

Страница 24: ...s product in an environment which may contain corrosive gases Such gases include but are not limited to sulfur dioxide hydrogen sulfide nitrogen dioxide chlorine ammonia or ozone Avoid installing this...

Страница 25: ...a CRU when it is not located within the system chassis W A R N I N G Do not disassemble repair or alter the server except as described in the Stratus ftServer 2600 4500 and 6300 Systems Operation and...

Страница 26: ...Safety Notices 1 14 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638 W A R N I N G W A R N I N G W A R N I N G W A R N I N G W A R N I N G W A R N I N G...

Страница 27: ...Safety Notices Site Planning for ftServer 2600 4500 and 6300 Systems 1 15 W A R N I N G W A R N I N G W A R N I N G W A R N I N G...

Страница 28: ...Safety Notices 1 16 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638 W A R N I N G W A R N I N G W A R N I N G W A R N I N G...

Страница 29: ...e and a B side power source that provide power to the system s power receptacles labeled A and B respectively Either source must be capable of continuing to provide power if power to the other source...

Страница 30: ...lectrical Circuit and Wiring Information for more information N O T E A branch circuit breaker with ground fault protection must allow aminimum of 3 5 milliamperes mA leakage current for each power co...

Страница 31: ...operation Connect one switch to A side power and the other switch to B side power x User supplied components TOTAL A SIDE POWER REQUIREMENTS Table 2 2 Worksheet Determining B Side Power Requirements...

Страница 32: ...n the Quantity column write the number of each type of component 2 Multiply the value in the Quantity column by the value in the Outlets column and enter the total in the Subtotal column 3 Add the val...

Страница 33: ...MBER OF B SIDE POWER OUTLETS Table 2 6 Worksheet B Side External Power Outlet Requirements PDUs Used Component Quantity Outlets Subtotal PDUs x 1 Other external components TOTAL NUMBER OF B SIDE POWER...

Страница 34: ...each other beyond that level The more electrical separation between the two power sources the less likely they will both failat the same time Due to redundancy inftServer systems power to either side...

Страница 35: ...ical Power Planning 2 7 Figure 2 2 PDUs Connected Directly to AC Power 1 A side PDU 5 PDU power cords 2 B side PDU 6 AC power outlets 3 B side jumper cables 7 Circuit breakers maximum of 20A 4 A side...

Страница 36: ...hese versions of ftSSS do not include the logic to decide whether the operating system should shut down in response to certain signals from the UPS and the UPS may unnecessarily shut down the system I...

Страница 37: ...J Requires AAP87600 PDU with B50175F power cord 200V 200V L6 20R SYH2K6RMJ P1 SYH4K6RMJ P1 SYH6K6RMJ P1 200V 100 200V L6 20R 5 15R SYA8K16RMJ SYA2K16RMJ SYA16K16RMJ Requires APC SYPD7and AAP87600 PDU...

Страница 38: ...tServer system download PowerChute Network Shutdown from APC and install and configure the tool on the system as described in the Stratus ftServer System Software Installation and Configuration for Wi...

Страница 39: ...d Connections for Systems PDUs and a UPS 1 A side PDU 6 UPS 2 B side PDU 7 UPS power cord 3 B side system power cables black 8 AC power outlets 4 A side system power cables gray 9 AC power mains distr...

Страница 40: ...y to a UPS You can connect the A side power connectors of your system directly to a UPS as shown in Figure 2 4 Figure 2 4 Rack Mountable Systems A Side Power Connected Directly to a UPS 1 A side syste...

Страница 41: ...onnect ftServer systems and peripheral components directly to an AC power source not to a PDU or to a UPS Table 2 12 lists the available power cords that connect ftServer systems to qualified UPS mode...

Страница 42: ...NEMA 5 15 BSMI approved 10A 125V 4 5m Taiwan B50174 P L6 20P PSE approved 15A 250V 15 ft Japan locking power cord 200V applications Table 2 12 Power Cords Between ftServer Systems or Storage Systems...

Страница 43: ...ational B50171F IEC 60320 C19 to NEMA L6 20P 16A 250V 15 ft North America B50175F IEC 60320 C19 to NEMA L6 20P PSE approved 20A 250V 15 ft Japan locking power cord Table 2 14 AC Power Cords to Connect...

Страница 44: ...Grounding Requirements 2 16 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...

Страница 45: ...umidistat to monitor room temperature and humidity See Chapter 2 Electrical Power Planning for detailed information about HVAC planning Is as free of dust as possible meeting at a minimum ISO 14644 1...

Страница 46: ...anels as needed Provides two electrically separate grounded AC wall outlets within reach of the power cords from the system or PDUs and if used UPS units Detachable power cords are 12 ft 3 65m If the...

Страница 47: ...Us and additional outlets for any components that do not connect to a PDU For optional components AC wall outlets within reach of the power cords from the components or use PDUs Make sure that cables...

Страница 48: ...Planning for Cables 3 4 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...

Страница 49: ...ns VMware Systems on page 4 7 Telephone Line Connections on page 4 8 Site Planning for Systems in an ftGateway Group on page 4 9 N O T E S 1 Software upgrade services are available from Stratus Profes...

Страница 50: ...le Storage system For Windows systems only connect the Fibre Channel cables from one or two ftServer systems directly to an EMC storage system Connect multiple ftServer systems to ftScalable Storage s...

Страница 51: ...C storage system The following illustrations are provided to help you plan a site for ftServer systems and storage enclosures Figure 4 1 illustrates Fibre Channel connections from a single system to a...

Страница 52: ...ch Fibre Channel Connections to an ftScalable Storage System Fibre Channel Switch 2 Fibre Channel Switch 1 ftScalable Storage RAID Controller Tray 2 ftScalable Storage RAID Controller Tray 1 CPU Eleme...

Страница 53: ...embedded Ethernet ports on the system and Ethernet ports on U104 or U105 or U1081 PCIe adapters to network connection points N O T E Two Ethernet ports are typically paired and teamed in software for...

Страница 54: ...or servers 1 for each port typically teamed for fault tolerance U104 Dual Port Fiber Gigabit Ethernet PCI Express Adapter gigabit fiber optic adapter for servers 1 for each port typically teamed for f...

Страница 55: ...2 Ensure that your ftServer system provides adequate bandwidth for your iSCSI storage requirements ftScalable Storage RAID controller tray 3 two for each controller tray and one to a management PC N...

Страница 56: ...direct dial analog number Always use telephone cable that is 26 AWG or greater and is UL approved If no modem is installed a second telephone line is not necessary A modem is not necessary in the fol...

Страница 57: ...physical Ethernet subnetwork One system acts as a gateway for ASN connectivity This gateway system or ftGateway master requires an analog telephone line that connects to the modem Other systems in th...

Страница 58: ...ystem with no remote management adapter in a group with an ftGateway system that has VTMs Slave systems that have VTMs in a group with an ftGateway system that has VTMs N O T E S 1 You cannot mix VTMs...

Страница 59: ...you do have a support agreement with Stratus use pairs of PDUs to provide AC power to systems and components in a cabinet if six or more power cords would otherwise exit from the cabinet The A side t...

Страница 60: ...ts will draw and whether you need a second pair of PDUs To complete Table 5 1 1 Obtain the voltage available at your location Consult a facilities manager at your site to make sure you know the correc...

Страница 61: ...red For each component add 1 to the value in the space above and write the result 4 In column 4 write the cumulative current required For each component add the current forthe component which youenter...

Страница 62: ...and number of cabinets you need Table 5 3 Example Current and Rack Space Requirements 208 volts Component Watts Site Voltage x 1 25 Current A Rack Space ftServer system 700 208 x 1 25 4 21 4U 1U LCD m...

Страница 63: ...e LCD monitor unit one tape drive typical and one ftScalable Storage system This set of components consumes 11 62 amperes adding another ftServer system would increase the consumption to 15 83 amperes...

Страница 64: ...Example of PDU Usage Calculation 5 6 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...

Страница 65: ...alling the equipment in an environment compatible with the maximum ambient temperature Tma specified by the manufacturer Reduced Air Flow Installation of the equipment in a rack should be such that th...

Страница 66: ...espectively The vertical mounting rails have a 0 345 or 0 375 square pattern with athickness between 0 063 0 105 to accept 10 32 cage nuts and mounting hardware The vertical mounting rails are plated...

Страница 67: ...nd rear doors you can remove the doors from the cabinet while your ftServer system is operating The final installation conforms to all emission immunity safety and other applicable regulations Figure...

Страница 68: ...ts 6 4 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638 Figure 6 1 Rail Clearance 1 Front vertical EIA rail 2 Accessory leg 3 Front of cabinet 0 5 inch 1 27 cm minimum 0 5 inch min...

Страница 69: ...not supplied by Stratus make sure that The monitor accepts universal 100 240 volts AC VAC 50 60 Hertz Hz power The VGA cable has a 15 pin D sub connector The power cord for the monitor is long enough...

Страница 70: ...Monitor Requirements 6 6 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...

Страница 71: ...em Specifications The following figures show front and rear views of the systems Figure A 1 shows the front of an ftServer 2600 4500 or 6300 system mounted in a rack with its bezel pulled forward Figu...

Страница 72: ...A 1 ftServer 2600 4500 or 6300 System CPU I O Enclosures Front View 1 CPU I O 0 7 Front panel LEDs 2 CPU I O 1 8 USB port 3 CPU ID button magnifying glass icon 9 Front panel 4 System LEDs 10 Power but...

Страница 73: ...t 3 PCIe or PCI X full height Not available on ftServer 2600 systems 10 CPU I O enclosure blue identification LEDs 2 4 PCI adapter slot 4 PCIe or PCI X full height Not available on ftServer 2600 syste...

Страница 74: ...1 04m Depth 53 in 1 35m 24U Cabinet Height including casters 49 5 in 1 26m Width 27 6 in 70 cm Depth 41 in 1 04m Weight empty 280 lb 127 kg Weight empty with pallet and shipping container 436 lb 197 8...

Страница 75: ...ding rail and bezel Weight including 12 DIMMS 2 processors and 8 disks per enclosure Two enclosures 84 lb 38 1 kg fully loaded Rails and shelf unit 13 8 lb 6 26 kg Environmental Operating temperature...

Страница 76: ...er Specifications for details Additional PCI slots optional for ftServer 4500 and 6300 systems Each CPU I O enclosure supports one optional riser Optional PCIe riser supports two full height capable P...

Страница 77: ...layed projects Stratus provides ftReady third party PCI adapter testing and driver hardening services To find out more about these professional service offerings please contact your local Stratus sale...

Страница 78: ...8 AAP87600 PDU Specifications A power distribution unit PDU optionally supplies power to rack mounted ftServer systems and optional rack mountable components Figure A 3 shows the AAP87600 PDU Figure A...

Страница 79: ...51 cm Depth 6 75 in 17 15 cm Environmental Operating temperature during operation 41 F to 95 F 5 C to 35 C For every 800 ft 243 8m above 2000 ft 609 6m lower the maximum operating temperature 95 F 35...

Страница 80: ...AAP87600 PDU Specifications A 10 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...

Страница 81: ...0A Grounding Considerations The system obtains an earth reference ground through the power cords attached to the system Similarly each peripheral device connected to the system obtains ground through...

Страница 82: ...how the hot ground and or neutral AC signals should be connected to the power input plugs of the system and optional components Figure B 4 illustrates a single phase 120V AC circuit connection Figure...

Страница 83: ...e lines Therefore for split phase or three phase applications both X and Y can beelectrically hot with re spect to the system ba se earth reference ground Figure B 2 shows the physical locations of th...

Страница 84: ...Site Planning Guide R638 Figure B 4 shows a single phase 120V AC circuit connection Note that this application requires a single pole circuit breaker Figure B 4 Single Phase 120V AC Circuit Connectio...

Страница 85: ...ows a single phase 240V AC circuit connection Note that this application requires a single pole circuit breaker Figure B 5 Single Phase 240V AC Circuit Connection Circuit A or B X Y G PE To power inpu...

Страница 86: ...hows a split phase 120 240V AC circuit connection Note that this application requires a double pole circuit breaker Figure B 6 Split Phase 120 240 Volts AC Circuit Connection Circuit A or B X Y G PE T...

Страница 87: ...n Note that the X and Y inputs on the system can be connected from L1 and L2 L2 and L3 or L1 and L3 This application requires a double pole circuit breaker Figure B 7 Three Phase 208V AC Y or D Source...

Страница 88: ...ase to neutral source connection Note that the system s X input can be connected to L1 L2 or L3 This application requires a single pole circuit breaker Figure B 8 Three Phase 380V AC Y or D Source Cir...

Страница 89: ...ratus supplies with ftServer systems and optional devices Table B 1 Connectors for AC Power Outlets Connector Configuration Rating Description NEMA L6 20 20A 250 volts AC 2 pole 3 wire NEMA 5 15 15A 1...

Страница 90: ...uide R638 BS 1363 A 13A 250 volts AC 2 pole 3 wire SEV 1011 S24507 10A 250 volts AC 2 pole 3 wire SAA 3 15 AS NZS 3112 1993 15A 250 volts AC 2 pole 3 wire GB1002 1996 10A 250 volts AC 2 pole 3 wire Ta...

Страница 91: ...ation specifications Deviations from this listof components will void agency certification 2 You must install all wiring including power and communications cables in compliance with local and national...

Страница 92: ...EN 61000 3 2 2006 Electromagnetic compatibility EMC Part 3 2 Limits Limits for harmonic current emissions equipment input current 16 A per phase European Union EN 61000 3 3 1995 A2 2005 Electromagneti...

Страница 93: ...A Certificate of Compliance with the Radio Regulations South Africa KCC No 2008 39 Annex 4 of the 2008 7 Technical Requirements for EMI Safety for ITE South Korea GB4943 2001 GB3254 1998 class A GB176...

Страница 94: ...2600 4500 and 6300 systems are compliant with the European Union s Restriction of Hazardous Substances Directive RoHS based upon the exception for lead used in servers W A R N I N G The lithium batte...

Страница 95: ...on B 1 wiring diagrams B 2 communications cables planning for 4 1 compliance standards C 1 connectors electrical B 9 BS 1363 A B 10 CEE 7 VII B 9 GB1002 1996 B 10 IEC 60309 B 9 NEMA 5 15 B 9 NEMA L6 2...

Страница 96: ...ard UPS 2 10 O optical Fibre Channel connections 4 2 P PCIe adapters U104 4 5 4 6 U105 4 5 4 6 U106 4 2 U108 4 5 4 6 PDUs configuration planning 5 1 power jumper cables 2 15 power cords 2 14 site plan...

Страница 97: ...cable planning 4 3 site network 3 3 system power cords 2 13 system specifications rack mounted systems A 1 T tape drive enclosures power cords 2 13 SCSI cables 4 2 technical support See CAC telephone...

Страница 98: ...Index Index 4 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...

Отзывы: