COMPLIANCE

The Wind Capacity Tables are based on testing in accordance with AS1562.1-1992 and AS4040.0, 1 & 2-1992. Span 

tables have been developed by determining wind pressures in accordance with AS4055-2006 for domestic applications. 

Capacity tables are in limit state format.   

Material Properties

Cooldek Classic

Cooldek CGI

Base Metal 

Thickness & 

Material Grade

Top Skin

0.42mm/G550

0.42mm/G550

Bottom Skin

0.50mm/G300

0.50mm/G300

Mass (kg/linear 

metre)

50mm Panel

9.5

9.6

75mm Panel

9.8

9.9

100mm Panel

10.1

10.2

Width Coverage (mm)

1000

1000

Minimum Roof Pitch

Core

Material

SL Grade EPS (expanded polystyrene)

Thermal Conductivity

0.037 W/mK (0°C mean temp.)

Table 1

DESIGN CONSIDERATIONS

The minimum recommended roof pitch for “flat” 

verandahs shall be 2° (1 in 30) for Cooldek Classic panels 

and 3° (1 in 20) for Cooldek CGI panels. The maximum 

roof pitch for “flat” verandahs shall be 5° (1 in 12). Care 

must be taken to ensure the minimum roof pitch is 

maintained to avoid ponding of rainwater. 

The roof is designed to withstand actions incidental to 

maintenance, roofs are not to be used for floor type 

activities. 

The design contained within these span tables relate to 

wind classifications N1, N2, N3, and N4 applicable to 

Regions A & B. Stratco does not accept liability for any 

loss or damage suffered as a result of any errors in the 

interpretation or application of these span tables.

MATERIAL SPECIFICATIONS

50mm Cooldek CGI Panel

50mm Cooldek Classic Panel

Both profiles are available in 50, 75 and 100mm insulation thickness

FORM AND FUNCTION

The innovative Cooldek

®

 insulated panel provides a roof, insulation and ceiling like finish all in one product. With 

superior spanning capabilities, two roof profiles and three insulation thicknesses to choose from, it is an ideal solution 

for domestic patio roof applications.

Figure 1

SPANS

Spans given in table 2 are determined for wind speeds for 

non-cyclonic areas. Indicated spans are suitable for ‘flat’ 

roof patios. Open freestanding unit spans can be taken 

from open three sides unless a wall, eaves or boundary 

exists within 500mm of two or more sides. 

For Cooldek roofing in attached or freestanding domestic 

gable patio application, sheet spans shall not exceed 

those given for one or no open sides. Alternatively, table 

3 indicating wind capacities may be used to determine 

allowable single spans for any application.

Spans  specified  for  units  with  three  sides  open  are 

suitable  for  units  considered  ‘empty  under’  and  not 

exceeding 3 metres in height (from ground or deck 

level). For units in which goods or materials stored under 

the roof are expected to block greater than 50% of any 

open side exposed to the wind spans are to be taken 

from open two sides.

For units with two open sides, spans are based on Cp,n=-1.0 

while for units with only one or no open sides, Cp,n=-1.2.  

In all cases, relevant consideration has been given to 

local pressure.

Note: Table 3 provides allowable wind capacities for 

Cooldek in single span application for serviceability and 

strength limit states. The pressures given may be used by a 

suitably qualified engineer for any single span application 

ensuring appropriate fixing details are applied.

Figure 2

Single span

Back span

Overhang