Para-
meter
Function description
Adjustment range
Standard
setting
Custom
setting
A32
Alarm delay after
“Power-on”
0...60 min.
0 min.
A40
Hysteresis mode
contact K1
0: symmetrically
1: one-sided
0
A41
Hysteresis mode
contact K2
0: symmetrically
1: one-sided
0
A50
Minimum action time
contact K1 ”On”
0...400 sec.
0.0 sec.
A51
Minimum action time
contact K1 ”Off”
0...400 sec.
0.0 sec.
A52
Minimum action time
contact K2 ”On”
0...400 sec.
0.0 sec.
A53
Minimum action time
contact K2 ”Off”
0...400 sec.
0.0 sec.
A54
Delay after “Power-on”
0...400 sec.
0.0 sec.
A55
Mutual delay of contacts
K1 and K2
0...400 sec.
0.0 sec.
A60
Sensor type
01: Thermo element type J
02: Thermo element type K
11: PT100 (2-Leiter)
12: PT100 (3-Leiter)
21: KTY81-121 (2-Leiter)
22: PT1000 (2-Leiter)
31: 2-10 V or 4-20 mA
32: 0-10 V or 0-20 mA
dependent
on
hardware
A70
Zeitkonstante Softwarefilter 0: 0.0 sec.
1: 0.8 sec.
2: 2.4 sec.
3: 6.0 sec.
4: 16.0 sec.
5: 38.6 sec.
6: 96.0 sec.
3
A80**
Temperature scale
0: Fahrenheit
1: Celsius
1
* parameter only available if there is a voltage/current input
** not available with voltage or current input
Содержание ST70-31.03