Order number: 900350.011
V2.70
Seite 10
Para-
meter
Description of function
Setting range
Default
value
Cust.
value
Timer characteristic
tic
Timer function
0: without multiple starts
1: with multiple timer starts
0
A version
L0
Controller address
1...255
5
Pro
Program version
-----
LowFat- and NoContact controll settings
General
Temperature monitoring a fryer can show whether enough oil is available. The LowFat and NoContact control
settings provided by the controller cary out this task. Low Fat and No Contact operate independently, each
have their own parameters and can be deselected separately.
At the moment of turning on the burner the control settings start running both at once and a test heating
starts.
Heating dynamics at various amounts of oil
Rule of thumb: The more oil, the slower the heating rate at a given heat output.
Start
time t
much oil
little oil
T
H2
H1
The illustration shows the heating up with small or large quantities in the deep fryer tank.