TIP 1000: AC Power Problems
3-4
Fifth Edition
95897
6. Loosen the screws on the cable strain
relief for the AC PDU.
7. Remove the power cable from the
bottom of the PDU.
8. Use an ohmmeter to check the
continuity of all three wires in the
power cable.
Is there continuity?
Yes:
No:
Replace the cable.
9. Plug the power cord back into the
customer’s outlet.
Leave the library end of the cord
unplugged.
WARNING:
Electrocution hazard: Take the necessary safety measures when measuring line
voltage in the next procedure.
WARNUNG: Bevor Sie die Netzspannung wie nachstehend beschrieben messen,
treffen Sie die entsprechenden Sicherheitsmaßnahmen.
Avertissement:
Danger d'électrocution: Avant de mesurer la tension de secteur à l'étape suivante,
prendre les mesures de sécurité requises.
10. Switch your volt/ohmmeter to
AC volts
and measure the line voltage at the
cable.
•
Nominal voltage for North America
is 100 to120 VAC.
•
Nominal voltage for international
is 200 to 240 VAC.
Is the line voltage correct?
Yes:
Go to step
No:
Notify the customer about this potential
problem.
11. Place the cable into the bottom of the
AC PDU.
Lift the breaker.
Does the breaker still trip?
Yes:
Replace the AC PDU.
Содержание L180
Страница 1: ...L180 Tape Library Service Manual Document 95897...
Страница 2: ......
Страница 3: ...L180 Tape Library Service Manual...
Страница 6: ...Summary of Changes iv Fifth Edition 95897 This page intentionally left blank...
Страница 16: ...Tables xiv Fifth Edition 95897 This page intentionally left blank...
Страница 44: ...Component Overview 1 12 Fifth Edition 95897 This page intentionally left blank...
Страница 68: ...Configuration Overview 2 24 Fifth Edition 95897 This page intentionally left blank...
Страница 254: ...Specifications A 28 Fifth Edition 95897 This page intentionally left blank...
Страница 262: ...Index Index 8 Fifth Edition 95897 This page intentionally left blank...
Страница 265: ......