ID 442426.04
360
WE KEEP THINGS MOVING
Optimize
15
Manual SD6
15.1.6
Actions with enable
The following actions provide support for you in making motor settings:
•
B40 phase test
•
B41 autotuning
•
B45 autotune SLVC-HP
(only if
B20
=
3:ASM - sensorless vector control
)
Note that the drive controller must be enabled for these actions. Section
15.1.6.1 Executedescribes how to perform actions for which the drive controller
must be enabled.
15.1.6.1
Execute
Note that parameter values are determined specifically for these actions. You
should therefore next perform action
A00 save values
so that the values will be
safely stored if the power fails or is turned off.
15.1.6.2
B42 Optimize current controller
WARNING!
Personal injury and material damage!
The motor is turning at about 2000 rpm during this action. Coupling elements
connected to the motor shaft, for example feather key, or downstream loads
may cause damage if there are persons in the range of motion or if the
mechanical system is not designed for this speed.
Make certain that operation at this speed is permitted for the motor and
downstream loads!
Secure coupling elements such as feather keys!
Make certain no persons are injured by the motor movement and
downstream loads, for example by cordoning off a suitable area.
NOTICE
Danger due to delayed shut-down.
If you have enable the action via local operation, the action can only be
interrupted with a very long delay by deactivating the enable!
If you start action
B42
, the parameters of the current controller will be
redetermined (
B64
to
B68
).
•
Enable must be inactive if you activate the action
•
If you have started the action with
B42[0] = 1:active
, you must activate the
enable.
•
When the action is complete, the enable must be deactivated again.
Performing actions with enable
1. Change to the device state
readySwtchOn
.
2. Set the first element of the action to a value of 1 (for example
B40[0]
= 1).
3. Enable the motor.
Element 1 shows the progress of the action (for example
B40[1]
= 33
%).
4. Wait until element 1 shows a value of 100 % (for example
B40[1]
= 100 %).
5. Switch off enable.
Element 2 shows the result of the action (for example
B40[2] = 0:error
free
).
Information
Clicking noises can be heard at regular intervals during this action.
The action lasts for about 20 minutes.