![Stober 43481 Скачать руководство пользователя страница 4](http://html.mh-extra.com/html/stober/43481/43481_supplementary-documentation_1381277004.webp)
POSIDYN
®
SDS 4000
2. Technical Specifications
2
2 TECHNICAL
SPECIFICATIONS
Specification
Model 3
Type of device
SDS 4281
(Id.-no. 43481)
SDS 4481
(Id.-no. 43482)
Nominal connected load
28 kVA
48 kVA
Nominal current (effective value, ±3%)
40 A
70 A
Max. output current (max. of approx. 5 sec,
±3%)
80 A
140 A
Connected voltage
(L1 - L3) 3 x 230 V - 10% to 480 V + 10%, 50 to 60 Hz
Power fuses
3 x 50 AT gL/gG AC/DC 500 V
1
3 x 80 AT gL/gG AC/DC 500 V
1
Braking resistance fuse
16 AF gL/gG AC/DC 500 V
1
20 AF gL/gG AC/DC 500 V
1
Conductor cross section, power and motor
2
10 mm²
16 mm²
Conductor cross section, ext. 24 V / GND
Max. of 2.5 mm², consider voltage loss
Clock pulse frequency, end stage
8 kHz
Braking resistance, external
(limit data for brake chopper)
m
15
Ω
/max. of 6 kW const.
Max. of 35 kW for 1 sec
m
10
Ω
/max. of 6 kW const.
Max. of 50 kW for 1 sec
Switch-on threshold, brake chopper
840 to 870 V
Switch-off threshold, brake chopper
800 to 830 V
RFI suppression
With external power network filter in acc. w. EN 55011, class A
Power network filter (mandatory!)
Power filter 42 A/ID no. 43477
Power filter 75 A/ID no. 43478
Power derating (mandatory!)
Power derating 60 A/ID no. 43479
Power derating 75 A/ID no. 43480
Permissible motor cable length
100 m without output derating
Auxiliary voltage, 24 V
without brake connection
20 to 36 V, 2 A
Auxiliary voltage, 24 V
with brake connection
24 V - 0% to 24 V + 10%, 5 A
Fuse, 24 V
Internal: 6.3 AT, external: max. of 16 AF due to conductor cross section (2.5 mm²)
Max. output current, brake
3 A
Protection rating/mounting position
IP20/always vertical
Ambient temperature
0 to 45° C with nominal data,
Up to 55° C with performance drop of 2.5%/° C
Humidity during operation
Relative humidity of 85%, no condensation
Installation altitude
Up to 1000 m without restriction; 1000 to 2500 m with derating of 1.5%/100 m
Degree of soil
Soiling degree of 2 in acc. w. EN 60204/EN 50178
Dimensions (H, W, D) without plug (in mm)
375 x 250 x 300
Power loss
400 W
700 W
Weight (kg)
19.5
21
1
According to DIN VDE 0636
2
With partial utilization, select cross sections in acc. w. DIN VDE 0100 and 0298. Cf. SMS catalog, section E.
Содержание 43481