Room temperature compensation 

 

 

 

The temperature may consist of 

 

the room temperature, 

 

or the outside temperature, 

 

or the inlet temperature, the inlet temperature is measured with 

a separate temperature sensor. 

 

The purpose of this compensation is to prevent rapid temperature decreases in a room. The “Maximum 

temperature compensation” is used to limit the room temperature corrected by the climate computer. Instead of 

the room temperature you can also use the inlet or outside temperatures as the basis for temperature 

compensation. 

 

Room ventilation compensation 

 

 

Bandwidth compensation 

This setting is used to adjust the bandwidth to the current outside 

temperature if the outside temperature exceeds the value setting. 

 

Minimum ventilation compensation 

The percentage by which the minimum ventilation should be corrected per 

°C of change in outside temperature is set in the “Compens. minimum 

ventilation” line (the compensation of the minimum ventilation is a relative 

compensation). 

 

Manual mode 

 

You can also set the ventilation percentages for 

Cleaning

 and 

Not in use

 in 

screen “1113 Manual control” in advance. The relevant settings are copied 

as soon as the 

Cleaning

 or 

Not in use

 modes become effective for the 

room. 

 

Setting the room status to “

Cleaning

” and “

Not in use

” enables you to 

manually enter the desired ventilation percentage when cleaning the room 

at “Manual control” (percentage setting and calculated percentage are 

equal). If the room has determined that the KL-61 is on manual operation, 

the current status of the room is set to "cleaning" and the potentiometer 

position of the KL-61 is taken over as the calculated manual operation (set 

value and calculated value are not equal). 

 

 

Note! The MANUAL CONTROL mode (cleaning) influences the alarm system, only use 

this mode if there are NO ANIMALS in the room. 

 

Room ventilation using growth curves 

 

 

To ensure that the climate in the house develops along with the growth of 

your animals, the climate computer has growth curves. Depending on the 

current day number, the current setting is determined from the curve (if 

the curve is 

on

). A growth curve can consist of a maximum of 7 

breakpoints. 

 

Climate settings which are calculated in accordance with a curve are 

preceded by the text “Growth curve”. To avoid having to continuously 

adjust the curve settings to the animals' behaviour, you can increase or 

decrease the calculated curve settings. 

 

Growth curve temperature: 

this enables you to increase or decrease the calculated room temperature. 

Growth curve minimum:    

this enables you to increase or decrease the minimum ventilation. 

Growth curve maximum:    

this enables you to increase or decrease the maximum ventilation. 

 

Содержание KL-6400 Series

Страница 1: ...USER MANUAL CLIMATE COMPUTERS KL 6400 series EN StienenBE KL 6400 G EN02000...

Страница 2: ...our Customer Service Department if you have any questions Be sure to have all necessary data at hand To ensure a speedy solution to the malfunction and to avoid any misunderstandings it is advisable...

Страница 3: ...ting 16 Miscellaneous 17 Growth curves 18 Overviews 20 Alarm 21 Communication alarm 21 Climate alarm codes 22 ROOM STATUS 24 SENSORS 25 Outside temperature alarm 25 ALARM 26 Latest alarm for device 26...

Страница 4: ...If the sensor is connected via a fixed socket outlet FSO push on the flap of the fixed socket outlet until you hear it click lock Application notes Central ventilation KL64CV N ENxxxxx Compensations...

Страница 5: ...6401 KL 6402 KL 6405 KL 6410 Whenever a key is pressed the display will be lit for a couple of seconds so that you can also see the settings and measurements in a dark animal house Note Only press the...

Страница 6: ...r is in room 4 and you press the key the cursor will remain in room 4 Alarm key Short key for alarm screens Test alarm test This enables you to test the operation of the alarm relay siren If you enter...

Страница 7: ...e with the table below The serial number must be between 01 and 99 00 means that the input output is not in use I O type Letter Serial number Explanation 0 10V output A 1 99 Analogue output with a ran...

Страница 8: ...confirm Menu option Start change Confirm change The cursor is displayed as a green rectangle e g While a change is being made the cursor is displayed as a black border e g TEMPERATURE SETTINGS With a...

Страница 9: ...in use Cleaning room Cleaning room Pre heating room Pre heating room Measuring fan switched off Measuring fan switched off Cooling on Cooling on Room heating on Room heating on Room heating switched...

Страница 10: ...sed users from changing settings on your climate computer you can have your installer set an access code An access code consists of a combination of 4 digits You can have a maximum of 6 access codes s...

Страница 11: ...to 7 C depending on the outside temperature is to be advised Minimum and maximum ventilation If compensation depending on the fill ratio has been installed the minimum and or maximum ventilation will...

Страница 12: ...above 100 This will result in the minimum and maximum ventilation being increased without you having to adjust other settings Minimum and maximum ventilation The fill ratio is used to calculate the m...

Страница 13: ...the flap Outside temperature Current outside temperature Frost protection Current status of frost protection active off Cycle time Current cycle time Flaps Current flap status auto open close Compensa...

Страница 14: ...g the room status to Cleaning and Not in use enables you to manually enter the desired ventilation percentage when cleaning the room at Manual control percentage setting and calculated percentage are...

Страница 15: ...inlet flap temperature setting 3 0 C Bandwidth 4 0 C Minimum flap opening 15 Maximum flap opening 100 Minimum and maximum flap opening If desired you can restrict the minimum and maximum flap position...

Страница 16: ...average of these temperature sensors If a sensor is defective it will be left out of the average calculation and the heating will continue to control on the basis of the remaining temperature sensors...

Страница 17: ...lowered by the percentage set for Compens maximum vent to increase the cooling effect TEMPERATURE MONITORING The temperature monitoring function is activated by your installer The current measurement...

Страница 18: ...urve of the setting you want to change is active you can only change the relevant setting by changing the setting of the curve The settings obtained from a growth curve are recalculated every hour to...

Страница 19: ...INLET FLAP 1 Minimum flap opening Maximum flap opening You can only set the growth curve for the temperature with an air inlet flap which controls on the basis of temperature AIR INLET FLAP 2 Setting...

Страница 20: ...h the minimum and maximum temperatures of the past week of the temperature selected will be shown The table also states the times when the minimum and maximum temperatures occurred on the various days...

Страница 21: ...and NOT IN USE states influence the alarm operation Installation errors such as Output already assigned Incorrect output type Input already assigned etc have to be solved first before putting the syst...

Страница 22: ...E You can set the alarm limits for the room temperature here If temperature compensation is active the maximum alarm limit can be adjusted by means of the corrected Temperature setting If an outdoor s...

Страница 23: ...or you can switch the inlet temperature alarm on or off in this screen The current inlet temperature is shown next to the alarm status Cooling Temperature monitoring Switching off the temperature moni...

Страница 24: ...or the following temperature measurements room temperature inlet temperature with inlet heating with frost protection floor temperature Pre heat All heatings are controlled except the inlet heating wh...

Страница 25: ...temperatures of the past week The table also states the times when the minimum and maximum temperatures occurred on the various days If the climate computer has its own outside temperature sensor this...

Страница 26: ...used the alarm relay to de energize due to an alarm condition in the relevant room are saved per room The cause of the alarm is displayed in addition to the date and time Alarm 0 The cause of the most...

Страница 27: ...ess of the active situation here operating mode off You can set the sleep mode brightness here On time Number of seconds during which the screen is lit after the last time a key is pressed Setting 0 s...

Страница 28: ...ad to draughts and in summer they can result in unwanted heating due to hot air being drawn in from between the roof and the insulating materials for example This will require the fans to work extra h...

Отзывы: