iNSTALLATiON
Safety
www.stiebel-eltron.com
WPL-A Premium |
7
iNSTALLATiON
7. Safety
Only a qualified contractor should carry out installation, commis-
sioning, maintenance and repair of the appliance.
7.1 General safety instructions
We guarantee trouble-free function and operational reliability only
if original accessories and spare parts intended for the appliance
are used.
7.2 Instructions, standards and regulations
Note
Observe all applicable national and regional regulations
and instructions.
The appliance conforms to IEC 61000-3-12.
The appliance meets the specified standard, as long as it is oper-
ated in accordance with EN 61000-3-11:2000 para. 4a.
8. Appliance description
The appliance offers frost protection for the connection lines. The
integral frost protection circuit starts the circulation pump in the
heat pump circuit automatically at a condenser temperature of
8 °C, and thereby ensures circulation in all water-carrying sec-
tions. If the temperature inside the buffer cylinder drops, the heat
pump starts automatically no later than when the temperature
falls below +5 °C.
8.1 Accessories
8.1.1 Required accessories
- Heat pump manager
WPM
8.1.2 Additional accessories
- Hydraulic module
HM(S)
- Hydraulic module
HM(S) Trend
- Integral cylinders
HSBC 200 (S)(GB)(BE)
- Integral cylinders
HSBC 300 cool
- Cylinder and hydraulic module HSBB 200 (S)(GB)(BE)
- Remote control
FET
- Remote control
FE7
- Ribbon heater
HZB 1
- Ribbon heater
HZB 2
- High limit safety cut-out for
area heating system
STB-FB
- Heating circuit pump
UP 25/7.5 PCV
- T-support
SK 1
- Wall mounting bracket
WK 2
- Mounting bracket
MK 1
- Connection set
AS-WP 1
- Connection set
AS-WP 2
9. Preparation
!
D
00000
60
16
3
The appliance is designed for siting in front of a wall. Observe the
minimum clearances. If the appliance is installed in an open space
or on a roof, protect the air intake side. Do this by erecting a wall
to shield it against the wind.
9.1 Sound emissions
The appliance is louder on the air intake and air discharge sides
than on the two enclosed sides. Take the following information
into account when selecting the installation location.
Note
For details regarding the sound power level, see chapter
"Specification / Data table".
- Lawn areas and shrubs help reduce the spread of noise.
- Noise propagation can also be reduced through dense pali-
sades or similar.
f
Ensure that the entire appliance frame is in full contact with
the substrate. Uneven substrates can increase sound emis-
sions.
f
Ensure that the air intake direction is the same as the main
wind direction. Air should not be drawn in against the wind.
f
Ensure that the air intake and air discharge are never direct-
ed towards noise-sensitive rooms of the house, e.g. bed-
rooms, or neighbouring houses.
f
Avoid installation on large, echoing floor areas, e.g. tiled
floors.
f
Avoid installation between reflective building walls. Reflect-
ing building walls can increase the noise level.
Содержание WPL-A 05 HK 230 Premium
Страница 1: ...OPERATION AND INSTALLATION Air source heat pump WPL A 05 HK 230 Premium WPL A 07 HK 230 Premium...
Страница 29: ...Installation Specification www stiebel eltron com WPL A Premium 29...
Страница 38: ...38 WPL A Premium www stiebel eltron com NOTES...
Страница 39: ...www stiebel eltron com WPL A Premium 39 NOTES...