26
| LWZ 170 E PLUS / LWZ 370 PLUS WWW.STIEBEL-ELTRON.COM
INSTALLATION
Specification
15. Specification
15.1 Dimensions and connections
677
45
879
765
138
388
138
328
280
526
564
g03
g05
g04
g06
d45
b01
D
00000
21
55
4
LWZ 370
plus
LWZ 170 E
plus
b01 Entry electrical
cables
d45 Condensate drain
Diameter
mm
32
32
g03 Outdoor air
Nominal di-
ameter
DN 180
DN 160
g04 Exhaust air
Nominal di-
ameter
DN 180
DN 160
g05 Extract air
Nominal di-
ameter
DN 180
DN 160
g06 inrushing air
Nominal di-
ameter
DN 180
DN 160
15.2 Minimum clearances
≥400
≥700
≥400
D
00000
23
25
1
15.3 Data table
LWZ 370
plus
LWZ 170 E
plus
232033
233850
Sound data
Sound power level (EN 12102)
dB(A)
54
45
Electrical data
Rated voltage
V
230
230
Max. current drawn
A
6
6
Power consumption without preheater coil
A
0.7
0.5
Power consumption with preheater coil
A
6
6
Phases
1/N/PE
1/N/PE
Frequency
Hz
50
50
Fan power consumption
W
9- 172
9 - 138
Power consumption without preheater coil
W
172
132
Power consumption with preheater coil
W
1380
1350
Versions
IP rating
IP30
IP30
Filter class
G4
G4
Dimensions
Height
mm
765
765
Width
mm
677
677
Depth
mm
567
567
Weights
Weight
kg
38
38
Connections
Air connector diameter
mm
180
160
Condensate connection
mm
32
32
Values
Air flow rate
m³/h
50-400
50-300
Heat recovery level up to
%
90
90
Extract air application range
°C
15-30
15-30
Max. ambient temperature
°C
60
60
Available external pressure, ventilation
Pa
160
160