INSTALLATIoN
Installation
www.stiebel-eltron.com
VRL-C 300/625/870 |
23
EN
GL
ISH
- The appliance is not suitable for the mounting or attachment
of other objects.
- In the case of appliance versions with a supply air grille,
check that there is no obstruction in front of the supply air
grille that could lead to disruptions in the flow.
- If increased sound insulation is required, use suitable fixing
materials to insulate the appliance from the wall and ceiling.
- Make the insulation on the outdoor and exhaust air lines va-
pour diffusion-proof.
If insulation is not carried out correctly,
this can cause condensation to form, damage the fabric of
the building and result in energy losses.
- To prevent condensation forming and avoid increased sound
transmission, use the fixing collars with an insulating insert.
- In the case of roof outlets, ensure that no condensate can
enter from outside or collect in the roof boards. Observe
local installation guidelines regarding snow and rain loads.
- For operational reliability, use our external covers.
4.4 Minimum clearances
≥400
≥500
≥20
≥40
≥2000
D
00000
96
41
7
325
188
20
D
00000
96
48
3
Appliance with grille: the suspended ceiling must be above the
grille.
Appliance with duct connection: the suspended ceiling must be
below the connections for extract air and supply air.
4.5 Preparing for installation
f
Design the cable routing.
f
Prepare the condensate drain pipe.
f
Prepare the programming unit installation location. Observe
the maximum cable length.
5. Installation
WARNING Electrocution
Do not install the appliance if it is damaged and there is
a risk that live components could be touched.
f
Check the appliance for external damage.
!
Material losses
f
Check whether the ceiling can bear the weight of
the appliance. Observe the maximum load per fixing
point.
!
Material losses
f
Always install the appliance horizontally so that any
condensate arising can flow into the condensate
drain.
Note
Install the appliance before mounting the ceiling panels
of the suspended ceiling.
Note
f
When positioning the appliance, ensure there is
sufficient space to install the supply and extract air
ducts (see chapter "Preparations / Installation site /
Minimum clearances").
5.1 Determining the installation position
f
Select the mounting system based on the installation posi-
tion. The distance between the ceiling and the appliance with
Z profile rails is 20 mm.
External wall outlets
Install the outdoor air intake into the building at a location where
contamination (dust, soot, odours, flue gas, exhaust air) is as low
as possible.
5.2 Drilling core holes for outdoor air and exhaust
air
b
a
D
00000
96
48
5
Z profile rail system:
Appliance
a
b
Core hole Ø
VRL-C 300 ...
224
830
280
VRL-C 625 ..., VRL-C 870 ...
283
1195
400
C profile rail system:
Appliance
b
Core hole Ø
VRL-C 300 ...
830
280
VRL-C 625 ..., VRL-C 870 ...
1195
400
Содержание 204132
Страница 17: ...Installation Technische Daten DEUTSCH www stiebel eltron com VRL C 300 625 870 17 D0000096524 ...
Страница 35: ...Installation Specification www stiebel eltron com VRL C 300 625 870 35 ENGLISH D0000096524 ...
Страница 53: ...Installation Données techniques www stiebel eltron com VRL C 300 625 870 53 FRANÇAIS D0000096524 ...
Страница 71: ...Installazione Dati tecnici www stiebel eltron com VRL C 300 625 870 71 ITALIANO D0000096524 ...
Страница 124: ...Instalacja Dane techniczne 124 VRL C 300 625 870 www stiebel eltron com D0000096524 ...
Страница 141: ...Telepítés Műszaki adatok www stiebel eltron com VRL C 300 625 870 141 MAGYAR D0000096524 ...
Страница 157: ...安装 技术参数 www stiebel eltron com VRL C 300 625 870 157 中文 D0000096524 ...