NOTES
It is important to read, understand and follow all instructions provided with this product. It
is the installer’s responsibility to comply with NFPA 70 & 101, NEC, mounting specifications
according to ADA and other applicable electrical codes. For Type SM (Self Monitored) rating,
the term Emergency message may be installed on Model UB-1 when used in a system
with a Listed, compatible Releasing Device. All other applications are rated Type NM (Non-
Monitored) for non-emergency signaling. To avoid electrical shock, DO NOT attempt to install
this product when power is on. ADA mounting compliance requires the operable part of
the initiating device shall not be less than 3 1/2 ft. (1.1m ) or greater than 4 1/2 ft. (1.37m)
above finished floor surface. After installation and testing are complete, provide a copy of
this manual to all personnel responsible for testing and maintenance of this product.
REMARQUES
Il est important de lire, de comprendre et de suivre
toutes les instructions fournies avec ce produit. Il
incombe à l’installateur de se conformer aux normes
NFPA 70 et 101, NEC, aux spécifications de montage
selon l’ADA et aux autres codes de l’électricité en
vigueur. Pour les cotes de type SM (auto surveillée),
le message d’Urgence peut être apposé sur le modèle
UB-1 lorsqu’il est utilisé dans un système intégrant
un dispositif de déclenchement compatible et
homologué. Toutes les autres applications sont cotées
de Type NM (non surveillée) pour la signalisation non
urgente. Pour éviter un choc électrique, NE tentez
PAS d’installer ce produit lorsqu’il est sous tension.
La conformité aux règles d’installation de l’ADA exige
que la partie utilisable du dispositif de déclenchement
soit installée à une hauteur située entre 3 1/2 pi (1,1
m) et 4 1/2 pi (1,37 m) au-dessus du plancher fini.
Une fois l’installation et les essais terminés, vous devez fournir une copie de ce manuel à l’ensemble du
personnel chargé de l’essai et de l’entretien de ce produit.
SWITCH RATING
2 Momentary Independent Form “C” contacts
UB-1/rated at: 10A, 1/2 HP, 125/250 VAC
6A, 30 VDC
100,000 Operations
Temperature: -40° to 185°F (-40° to 85°C)
- 2 -
Model UB-1/LTUL
Form C contacts on
Timer rated:
30 VDC 3A, 1.0 pf
Power In
12–30 VDC/VAC
Safety Tech. Int’l Inc.
P/N UB-11. Ver 1.0
wwyy
DIFFUSER
TO SUPERVISED STATION
OR AUXILLARY DEVICE
SW1
SW2
NC
COM
NO
NC
COM
NO
MAG LOCK
MESSAGE LENS PCB
12–24VDC
BUTTON LED
NORMAL POSITION BUTTON ACTIVATED
MAGNETIC LOCK
BUTTON LAMP
MESSAGE LAMP
ON
ON
OFF
OFF
OFF
ON
NO
NC
COM
LED –
LED +
SWIT
CH 1
SWIT
CH 2
1
2
3
4
SCREWDRIVER
4.830 in.
(123mm)
3.220 in.
(82mm)
1.328 in.
(34mm)
.867 in.
(22mm)
UB-1L LED PCB
NYLON WASHER
SELF TAPPING SCREW
19085 #6 - 32 x 1” OVAL
HEAD MACHINE SCREW
(2) PROVIDED
19018 ANCHOR
(4) PROVIDED
DRILL POINT PROVIDED TOP & BOTTOM
FOR 1/2 in. CONDUIT. DRILL AS NEEDED.
19039 SCREW
#6 x 1 1/4 in.
(4) PROVIDED
DRILL (4)
3/16 in.
DIAMETER HOLES
71100A
BACKBOX
19085 #6-32 x 1 in.
OVAL HEAD MACHINE SCREW
(2) PROVIDED
DRILL OUT THE (4) MOUNTING
HOLES, ONE IN EACH CORNER,
USING 5/32 in. DRILL BIT
BACKBOX MUST BE MOUNTED
WITH ARROWS POINTING UP
.867 in.
(22mm)
1.575 in.
(40mm)
UB-1L LED PCB
TOP TAB
ACTUATOR
Power In
12–30 VDC/VAC
Safety Tech. Int’l Inc.
P/N UB-11. Ver 1.0
wwyy
CAP
BUTTON
SPRING
NEW DRAWING