background image

4

Safety regulations, instructions 

and guidelines

The  substructure  as  well  as  its  connections  to  the 

building have to be checked on site according to the local 

regulations.

The collectors have to be mounted in an angle of at least 

20° to max. 70°.

Recommended heat transfer medium is a mixture of glycol 
and  water,  e.g.  Tyfocor  L  or  similar  The  collectors  may 
never be operated or tested under pressure with water.

To protect the system of overheating during standstill  and 

accelerated glycole-aging a self-draining system (e.g. STI 

Drain Master or Drain Box) is recommended.

It is absolutely necessary to pay attention, that the back flow 

temperature is never lower than the ambient temperature. If 

necessary, take appropriate action (e.g. increase back flow 

temperature to at least 30°C).

Lightning protection

Note country-specific legislation!

Throughout the installation of metal fastening, a check is 

needed by an authorized qualified electrician.

The  metallic    pipes  of  the  solar  circle  are  connected  via 

a  copper  pipe  of  at  least  16  mm²  with  the  earth  circuit 
connector.

Please  ensure  sufficient  ventilation  for  each  assembly 

method. Do not close the ventilation openings. Especially 

in case of  roof-integrated assembly, the ventilation of the 

collector  is  definitely  necessary.  Appropriate  ventilation 

hoods are available from the supplier. Pay attention to the 

regulations of the ZVDH (Germany), SVDW (Switzerland) 

as well as different local regulations concerning the ventila-

tion. If necessary, consult an expert.

Responsibilites

The constructor of the installation is responsible for the in-

tegration of the installation according to regulations and for 

compliance with the safety regualtions.

The operator of the installation is responsible for an ope-

ration  of  the  installation  according  to  regulations  and  for 

consultation of experts in case of problems.

This instruction is not subjected to the control of a service of modi-

fications. It does not absolve the manufacturer and operator of the 

installation of his responsibilities to install and operate all parts of 

the installation according to utmost professional knowledge. The 

manufacturer of the installation is responsible to observe and keep 

all appropriate regulations and instructions.

Statics

Before  beginning  the  assembly  it  is  vital  to  test  the  roof  or 

substructure on site to sufficient load-carrying capacity. 

Pay  increased  attention  to  the  possible  durability  of  the  screw 

fittings to fasten the collectors as well as to the quality of the sub-

structure.

According to DIN 1055 part 4 and 5 or rather according to the local  

engineer standards it is necessary to check on site the whole sys-

tem construction, especially in snowy regions (note: 1 m² powder 

snow ~ 60 kg / 1 m² wet snow ~ 200 kg) as well as in regions with 

high  wind  speed.  Before  starting  the  assembly  all  aspects  that 

may lead to incorrect load of the whole construction have to be 

considered!

Install the  collectors the way that backlog of snow (e.g. due to 

snow guards or other obstacles) is not possible.  

In case of correct assembly snow loads (pressure loads) up to 2 

kN/m² and wind loads (suction loads) up to 1 kN/m² acting on the 

collector are permitted.

For transport and stocking

 
Never abandon the delivered collectors unprotected at the building 
site. Never lay down the collectors onto a rough surface with over-
hanging pieces like stones, timbers, etc.
Stock  the  collectors  always  upright  leaning  against  a  solid  sur-
face.
The rigidity of the collectors is limited. During transport to the buil-
ding site always ensure a torsion-free transport type. In case of an 
elevated  intermediate  storage  make  sure  that  the  collectors  are 
protected against sliding down.

Содержание FKA 200H

Страница 1: ...1 Assembly Instructions Solar collectors FKA 200 240 270 console installation...

Страница 2: ...r solar collectors Blauer Engel labeled products and to consign it to recycling Safety regulations instructions and guidelines 3 Product description 5 Hydraulic connections 7 Collector field dimension...

Страница 3: ...ichnung Ausr stung und Pr fung DIN 4757 Teil 1 Sonnenheizungsanlagen mit Wasser und Wassergemischen als W rmetr ger Anforderungen an die Sicherheitstechnische Ausr stung Teil 2 Sonnenheizungsanlagen m...

Страница 4: ...n ope ration of the installation according to regulations and for consultation of experts in case of problems This instruction is not subjected to the control of a service of modi fications It does no...

Страница 5: ...er medium This glycol water mixture gives off the stored heat via a heat exchanger to a storage The obtained energy can be used for water heating and heating support Sectional model 1 Aluminium frame...

Страница 6: ...15 m 2 52 m 1 80 m 2 15 m 2 52 m Length 1 777 mm 2 100 mm 2 400 mm 1 200 mm 1 200 mm 1 200 mm Width 1 200 mm 1 200 mm 1 200 mm 1 777 mm 2 100 mm 2 400 mm Height 115 mm 115 mm 115 mm 115 mm 115 mm 115...

Страница 7: ...to six collectors in one row Connection F red Connection BF blue A or B C or D Close unused connections with caps Installations with seven up to 15 collectors in one row Connection bottom left at the...

Страница 8: ...ther on a solid surface or on the concrete blocks shown in this instruction The available concrete elements are recommended as a weight for locations up to 700 meters above sea level with leeward situ...

Страница 9: ...176 cm 211 cm The specified levels are reported without concrete blocks To determine the total height the height of the concrete block 15 cm must be added Block distance center center Dimensional cha...

Страница 10: ...lock 65 kg 1420101 additional block 45 kg concrete block 65 kg additional block 45 kg console 8 kg collector filled 240 46 kg travers position angle 20 30 45 60 position P1 P2 P3 P2 P1 P2 P3 P2 200 24...

Страница 11: ...observance of the specified clearances between the concrete blocks The short distance between the threaded sleeve and block edge 10 cm shows the front of the block Make sure that every concrete block...

Страница 12: ...ill two holes per base console in the existing surface to fix the fixed dowel pin M10 Pay attention to precise alignment of the two holes In addition all other holes hare to be oriented in exactly one...

Страница 13: ...he compensator must be mounted on the concisely protruding flange It is important to ensure that the 0 ring seal is used for the compensator 1300001 Collector connection set hydraulical Fixation of th...

Страница 14: ...hooks into the collector profile Then fix the fastening plate Fix the upper and lower compensator with the clamp Before tightening of the screw the clamp must be positioned by a rotary motion up and d...

Страница 15: ...r inserting the sensor is protected with a silicon grommet which has to be centrally opened using a knife or small screwdriver before inserting the sensor The insertion depth is limited to 4 cm Furthe...

Страница 16: ...the roof tiles have to be mounted above the rafters in other words the support must lie on the rafter alternatively a higher number of roof tiles may be considered depending on load Initial position t...

Страница 17: ...oof mounted installations one profile set alu 1400035 1400026 1400027 or 1400028 depending on the collector type is delivered for each collector If several collectors are mounted in one row for each c...

Страница 18: ...f the lower lath 24x80x600 mm with two screws 5x60 mm If the lath is placed near the counter lath the lath 24x80x600 mm must not be applied 1410002 Roof tile clamp V2 without lead The lower roof tile...

Страница 19: ...hed mounting of screw as distance saver Caulk if necessary the coarsely ground brick with a foam tape against water In addition to the grinding of the roof tile we recommend to use a screw that is mou...

Страница 20: ...ith high snow load zone of 2 kN m it is necessary to place the roof hooks in the rafter area Completely lifted area for placement of a hook Mount the lower lath 24x80x600 mm with two screws 4x50 mm If...

Страница 21: ...oof tile clamp must not cover the lower tile Otherwise a pressure point on the lower tile may arise Mount the upper mounting tab Bend it up sidewise The screws of the roof tile clamp must be covered P...

Страница 22: ...ough space for a covering tile to avoid grinding The tile clamp is fixed with two screws 5x60 mm The roof tile clamp may not rest or rather cause pressure points on the tile If the tile clamp is mount...

Страница 23: ...zone of 2 kN m it is necessary to place the roof hooks in the rafter area Assembly of the lower tile clamp supporte 80x50x45 mm with two screws 5x60 mm Timber excess length of 5 mm timber is higher t...

Страница 24: ...with lower lead sheet The tile clamp must have a minimum distance to the underlying tile of 5 mm Mount the upper lead sheet while placing the lead laterally under the tiles Pay attention that the cor...

Страница 25: ...ath the corrugated roof covering the roof clamp can additionally be fixed with a second fastening screw Completely mounted roof clamp ready for assembly of fastening profiles If the roof clamps can no...

Страница 26: ...not exceed the T head screw s tightening torque of 27 Nm The slots in the hooks are for evening out bumps The fastening of the profile must be realised in the upper third of the slot In the border ar...

Страница 27: ...070 mm 910 mm measure T 540 mm 710 mm 930 mm measure W Top of the collector to hole center upper hole 96 mm 117 mm 140 mm middle hole 176 mm 197 mm 220 mm bottom hole 256 mm 277 mm 300 mm measure Z H...

Страница 28: ...003 Wall console 200 240 270 H 45 without fastening Then place the wall console in the desired position Make sure that all consoles have the same mounting position the corresponding distance measures...

Страница 29: ...on set hydraulical Fixation of the compensator on one side with the clamp Before tightening of the screw the clamp must be positioned by a rotary motion up and down Tighten the screw on the clamp only...

Страница 30: ...llector on the consoles Move the collector until the fastening plate double hooks into the collector profile Then fix the fastening plate Fix the upper and lower compensator with the clamp Before tigh...

Страница 31: ...r inserting the sensor is protected with a silicon grommet which has to be centrally opened using a knife or small screwdriver before inserting the sensor The insertion depth is limited to 4 cm Furthe...

Страница 32: ...ctor connection set 22 mm 2 pcs compl 1310104 Collector connection set 22 mm Al 2 pcs compl Air eliminator without extension 1310007 Air eliminator set without extension pipe compl with caps Completel...

Страница 33: ...tings Collector connection 22 mm for soldered fittings or clamping ring joints Collector connection hydraulical compensator connects two collectors and compensates thermal dilations Clamp collector co...

Страница 34: ...e distance metal sheet is inserted from below into the collector grooves Fig 2 and 3 In case of vertical collectors or rather in case of multi row assembly of the collectors further distance metal she...

Страница 35: ...1 28 x 1 5 28 x 1 5 15 coll 990 L h 22 x 1 28 x 1 5 28 x 1 5 Length of pipe F BF Number of collectors from 20 m to 25 m from 25 m to 30 m from 30 m to 35 m from 35 m to 40 m 2 coll 132 L h 15 x 1 15...

Страница 36: ...30 L h 22 x 1 22 x 1 22 x 1 22 x 1 6 coll 396 L h 22 x 1 22 x 1 22 x 1 22 x 1 7 coll 462 L h 28 x 1 5 28 x 1 5 28 x 1 5 28 x 1 5 8 coll 528 L h 28 x 1 5 28 x 1 5 28 x 1 5 28 x 1 5 9 coll 594 L h 28 x...

Страница 37: ...y necessary to make sure that the back flow temperature never falls below the ambient temperature If necessary take appropriate measures e g increase of back flow temperature to at least 30 C Regular...

Страница 38: ...ce F BF Hysteresis Consumer 1 e g water for domestic use C K K Consumer 2 e g 1 buffer store C K K Consumer 3 e g 2 buffer store C K K Consumer 4 e g swimming pool C K K Maximum temperatur of collecto...

Страница 39: ...ed changes on the collectors and the accessoiries There is no guarantee or warranty due to optical or technical reduction or defects on the collector resulting from external influences forasmuch as th...

Страница 40: ...ogie International GmbH Seiferitzer Allee 14 08393 Meerane GERMANY Tel 49 03764 795610 Fax 49 03764 7956115 E Mail info sti solar de Homepage www sti solar de Copyright STI Solar Technologie Internati...

Отзывы: