background image

Page 2 of 4 

INSTALLATION GUIDE • SERIES 44+ MODULAR FLOOR GRID SYSTEM 

          ZIS1049  0916

PREPARATION

Orientation: Grids are designed to be installed with slots running parallel to cable pathway or support systems 

such as vertical cable trays or racks (Fig 3).

Floor Opening: The EZ-Path Modular Floor Grid System installs into preformed, rectangular openings through 

concrete floors. Opening must be properly sized and positioned. Dimensions vary according to the model selected 

and are shown in Table B. Mounting of the grid frame requires an additional 2-1/2” of clear unobstructed space 

beyond the periphery of the opening on all sides. Where standing water or flooding is a concern, it is recommended 

that the grid frame be mounted to raised curbs formed into the concrete (Fig 4).

INSTALLATION

Assemble Grid Frame: Assemble grid frame by installing 1/4-20 x 1/2” bolts and nuts through flanges at mitered 

corners (Fig 5).

Mark and Drill Anchor Holes: Mark lines parallel to and an 1-1/4” from the periphery of the opening on all sides. 

Place assembled grid over opening so that these lines appear under anchor holes in frame on all four sides. 

Mark anchor holes and trace reference marks around the four outside corners of the grid frame (Figs 6 & 7). 

Remove frame and drill holes for anchors.

B

C

D

A

PeripheryofOpening

1-1/4"

RefMark

RefMark

Pathway

Capacity

Model (Catalog No.)

Module

Capacity

Cable

Capacity*

Opening 

Width (A)

Total

Width (C)

Opening

Length (B)

Total

Length (D)

With 

Modules

Without 

Modules

4

EZDG444S / 

EZDG444S2

EZG444

1

875+

6” 

(15.3 cm)

11”  

(28 cm)

18”

(45.7 cm)

23”

(58.4 cm)

8

EZDG844S / 

EZDG844S2

EZG844

2

1750+

12”

(30.5 cm)

17”

(43.2 cm)

18”

(45.7 cm)

23”

(58.4 cm)

16

EZDG1644S / 

EZDG1644S2

EZG1644

4

3500+

24”

(61 cm)

29”

(73.7 cm)

18”

(45.7 cm)

23”

(58.4 cm)

NOTE: *Nominal capacity using Cat 5E cables for reference.

Table B: Dimensions & Capacities

Fig 6: Marking corner reference and anchor points

Fig 7: Mark Anchor Points

Fig 8: Position Gaskets

Fig 9: Grid Frame Installed

Install Grid Frame: Place gasket on concrete (Fig 8). Replace assembled grid frame back over opening using

corner reference marks to reposition (Fig 9). Using concrete screw, probe through gasket to locate drilled holes.

Install fastener loosely. Continue installing fasteners. When finished, tighten all fasteners securely.

Содержание EZ-Path 44+ Series

Страница 1: ...lowing Product Data Sheets EZ Path Series 44 Fire Rated Pathway Spec Seal Intumescent Composite Sheet INSTALLATION GUIDE SERIES 44 MODULAR FLOOR GRID SYSTEM TABLE A Components Model Pathway Module Four Pathways Firestop Panels Panel Clips Space Bar Assembly Concrete Fasteners Not Included EZDG444S EZDG444S2 One 1 Included NA NA NA 12 EZDG844S EZDG844S2 Two 2 Included NA NA One 1 12 EZDG1644S EZDG1...

Страница 2: ...ce assembled grid over opening so that these lines appear under anchor holes in frame on all four sides Mark anchor holes and trace reference marks around the four outside corners of the grid frame Figs 6 7 Remove frame and drill holes for anchors B C D A Periphery of Opening 1 1 4 Ref Mark Ref Mark Pathway Capacity Model Catalog No Module Capacity Cable Capacity Opening Width A Total Width C Open...

Страница 3: ...with notches in side rails located between pathway modules Press down until top of spacer bar is flush with side rails Place spacer strap gasket in place over spacer bar Install spacer strap over gasketed spacer bar pressing strap down tightly against gasket Install clamping bolts at each end and tighten to clamp spacer bar in place Tighten pathway module bracket bolts 1 4 20 x 1 1 2 provided Inst...

Страница 4: ...sable space within the pathway device SUPPORTING CABLES Allow slack where cables flow through pathways by providing support for cables above and below the floor Cable support system should orient cables so that the flow is vertical through the center of the pathways PRECAUTIONARY INFORMATION The use of these products is subject to local regional and national codes Consult the local Building Code O...

Отзывы: