Electrical connection
Caution
: Laying of cables and electrical connection should only be carried out by an approved electrical
company. The power cables must not be strained by tension, twisting, squashing or by shearing off.
Follow the safety instructions (see page 14).
Note
: See the plans for the control panels for further Information on connections.
Type designation:
M2 / [stroke] - [force]/ [type] / [colour] / RWA
Type: :
SG
= with integrated pulse generator for synchronous operation by synchro modul
LA
= with integrated power cut-off
1G
= speed of operation approx. 4,2 mm/s
2G
= speed of operation approx. 8,3 mm/s
without declaration
= without integrated power cut-off and without integrated pulse
generator, for operation with the external power cut-off
Further possible connection please find in the technical information and operating of the synchro module, power cut-off
or of the used control panel.
+ -
M
=
24 V DC
- +
24 V DC
+
-
M
=
24 V DC
-
+
24 V DC
Type SG
Type LA
red
signal line for
external synchro
module
blue
brown
white
black
blue
brown
Caution
: without integrated power cut-off.
Destruction of the linear drive - never operate
linear drive without pulse generator
Caution
: Operate only with integrated or
external power cut-off (dependent on type).
Destruction of the linear drive - never ope-
rate without power cut-off.
SHE linear drive M2/...-1000N/.../EV1/RWA