Sterling SDFI Скачать руководство пользователя страница 27

– 27 –

SECTION VIII - MAINTENANCE SCHEDULE AND LUBRICATION REQUIREMENTS

f. Inspect all electrical components, connections and

terminals. Clean and tighten where necessary.

g. Test ignition spark. Adjust gap if necessary.
h. Clean ignition electrodes and check for cracks.
i. Test flame safeguard relay and replace components if

necessary.

j. Inspect all regulators, relief valves, motorized valves,

solenoid valves, vent valves, manual shut off valves
and safety shut off valves. Check their operation and
clean as necessary.

k. Ensure all vents to the atmosphere are clean and free

from obstruction.

l. Inspect and clean all drip legs in the fuel line.
m. Lubricate fan motor as directed by motor manufac-

turer.

n. Inspect fan motor wiring for loose connections.
o. Lightly oil all door latches.
p. Check that cabinet is weathertight, replace door

gaskets and recaulk as necessary.

NOTE: Keep screened air intakes clear of obstruc-
tions at all times.

B. Lubrication Instructions

Item

Manufacturer

Bearing Type

All 3 phase

US., Baldor

Single row ball

fan motors

or equal

bearings

(1 HP to
100 HP)
ODP, TEFC

Recommendation: See following note.

All 1 phase

Century, G.E.,

Bronze sleeve

motors

or equal

bearings

(Fractional
HP)  ODP,
TEFC or
TEAO

Recommendation: See following note.

Fractional HP

Century, G.E.

Bronze sleeve

single phase,

or equal

bearings

ODP or
TEFC

Recommendation: See following note.

Fan shaft

Browning

Self-aligning

bearings

or equal

single row or
double row roller
or ball bearings,
resilient mounted

Recommendation: See following note.

Dampers

Mestek

Sleeve

or equal

Recommendation: See following note.

Periodic maintenance is essential to the efficient
operation and extended service life of this equipment.
Failure to provide maintenance as recommended may
void the equipment warranty.

A. Maintenance Schedule
1. Weekly

a. Check that fan belts are tight and sheaves are

aligned. The fan belts can be checked every 30 days
after the first 60 days of new belt run-in.

CAUTION: Do not overtighten belts.

2. Monthly

a. Check all valves, piping and connections for leaks.
b. Check the flame signal.
c. Check the fuel pressure in the fuel supply line to each

heater.

d. Check the burner manifold pressure at full fire and

that low fire has a continous flame all across burner.

e. Clean the flame sensor(s).
f. Inspect filters. Clean or replace as necessary.
g. Inspect the main fan bearings.
h. Check all dampers, damper actuators and linkages.

Adjust and tighten if necessary.

i. Ensure that there are no obstruction blocking the air

supply to the heater or the air discharge from the
heater.

j. Inspect the area and make sure that no combustible

or hazardous material has been stored within the
clearances as shown on the unit nameplate.

3. Quarterly

a. Complete the monthly maintenance schedule.
b. Check the belt tension for the main fan(s) and adjust if

necessary.

c. Check the alignment of the sheaves and adjust if

necessary.

d. Inspect all bearings set screws for tightness and

lubricate bearings if necessary.

e. Check the pilot electrical system (if applicable). Adjust

if necessary.

f. Check the pilot assembly (if applicable). Clean and

adjust if necessary.

g. Inspect the burner carefully. Clean and adjust if

necessary.

h. Check voltages and amp draw on main fan motor.
i. Check the operation of all safety controls individually.
j. Check the operation of the automatic gas shut off

valves and check them for leakage at the pressure
test ports provided.

4. Off Season or Yearly

a. Complete the monthly and quarterly maintenance

schedule.

b. Inspect all fan wheels and housings. Clean if necessary.
c. Check that all fan wheels and sheaves are securely

set on the shaft.

d. Inspect all bearings and alignment. Adjust if necessary.
e. Inspect all V-belts. Replace if necessary.

Содержание SDFI

Страница 1: ...errupteur 3 teindre toute flamme ouverte 4 Appelez imm diatement votre fournisseur de gaz AVERTISSEMENT Une installation d ficiente de m me qu un mauvais r glage modification entretien ou maintenance...

Страница 2: ...ould be checked carefully for physical damage in the presence of the carrier s representative If parts are missing or damage has occurred a claim should be filed immedi ately with the carrier All Dire...

Страница 3: ...e pillow block ball bearing assemblies in the fan section It is recommended that all nuts and set screws be tightened Turn fan shaft by hand to make certain that blower does not rub against blower hou...

Страница 4: ...C Location of Accessories Where applicable standard or optional accessories will be placed inside the fan section of the unit for shipment and must be removed and installed by the mechanical or electr...

Страница 5: ...at thermostats especially those with mercury bulb contacts be mounted on a vibration free surface The side of building columns away from the heater or interior walls are usually the location best suit...

Страница 6: ...ockwise to decrease pressure Connect test instrument to pilot flame test jack located on flame safeguard relay Set all thermostats to call for heat Set inlet ductstat if applicable above outside air t...

Страница 7: ...e pilot and burner a number of times to insure smooth light off Check flame signal with burner cycling through full firing range and burner profile damper operation if applicable Unit Start Up Systems...

Страница 8: ...eat switch will have to be turned off for approximately five seconds to reset the ignition control D Air Pressure Switches The high air pressure switch is checked by removing the sensing tube from the...

Страница 9: ...terminal is energized RM7895C D EC7895C RM7896C D f Internal system fault occurred g Purge card is removed h Purge card is bad 5 MAIN FLAME ESTABLISHING PERIOD MFEP RM7895C D EC7895C RM7896C D a Airf...

Страница 10: ...ain Flame Establishing Period MFEP a After Ignition Trials and with the presence of flame the main fuel valve terminal 9 is pow ered If a flameout occurs the relay module locks out or recycles dependi...

Страница 11: ...VII TROUBLE SHOOTING continued SETTINGS AND ADJUSTMENTS Selectable Site Configurable Jumpers The relay module has three site configurable jumper options see Fig 6 and Table 7 If necessary clip the si...

Страница 12: ...IRFLOW SWITCH FLAME DETECTOR IGN AIRFLOW SW CHECK OPERATING CONTROLS AND INTERLOCKS INITIATE ALARM ALARM STANDBY POWER POWER PILOT FLAME MAIN TIMED PURGE ALARM POWER PILOT FLAME MAIN RUN STANDBY BURNE...

Страница 13: ...ITIATE ALARM ALARM STANDBY POWER POWER PILOT FLAME MAIN TIMED PURGE ALARM POWER PILOT FLAME MAIN ALARM POWER PILOT FLAME MAIN RUN STANDBY BURNER START MAIN VALVE LIMITS AND BURNER CONTROLLER CLOSED 10...

Страница 14: ...he appliance nameplate for high pressure The gas control full rate outlet pressure should match this rating 4 With main burner operating check the gas control flow rate using the meter clocking method...

Страница 15: ...at or controller above room tempera ture to call for heat 3 Watch for ignition spark or for glow at hot surface igniter either immediately or following prepurge See IP module specifications 4 Time the...

Страница 16: ...quired gas pressure 3 No gas through pilot regulator with inlet gas pressure ok 4 No gas through pilot solenoid 1 Check power source 2 Check and replace 3 Close or connect customer interlock 4 Switch...

Страница 17: ...in main flame check wiring and flame rod 1 Place in Run position see technical cut sheet on flame safeguard relay 5 Type of gas natural LP supplied different from factory required type Note component...

Страница 18: ...ing down the reset button 7 Correct problem Reset both switches 8 Check for power and replace if necessary 1 Low or no voltage 2 Fuse s blown 3 Customer interlock not closed or connected 4 Fan Off On...

Страница 19: ...ng or replace if necessary 12 Clean or replace regulator 13 Check vent lines or replace limiters 14 Adjust setting on modulating valve or gas valve 1 See following troubleshooting guide for Maxitrol s...

Страница 20: ...20 TROUBLESHOOTING GUIDE P 001004 P 001003...

Страница 21: ...Inspect for loose or broken wires between amplifier terminals 1 2 and TD114 terminals 1 3 3 Connect test resistor as described in Preliminary Circuit Analysis in Section IX Follow procedures outlined...

Страница 22: ...tor as described in Preliminary Circuit Analysis Turn TD114 selector dial so heater goes through its entire modulating range 3 Temporarily wire each TD114 TS114 and MR212 externally and observe heater...

Страница 23: ...If on high fire control can do no more Heater unable to furnish additional heat to raise temperature 1 Replace automatic control valve 2 Correct wiring I Incorrect Discharge Air Temperature J Burned...

Страница 24: ...ult Install replacement amplifier 1 Adjust to proper low fire 2 If greater than 1 5 negative pressure check equipment for clogged filters and other inlet air restrictions For other solutions consult f...

Страница 25: ...read 6000 ohms 1000 T244 If TS244 TD244 are used meter should read 4500 ohms 1000 TS244 and 2100 ohms 150 TD244 3 Follow procedures outline in Preliminary Circuit Analysis in Section IX 1 Compare sen...

Страница 26: ...l circuit 1 Incorrect maximum discharge air temper ature setting A1044 2 Incorrect minimum discharge air temper ature setting A1044 3 Insufficient burner capacity 4 Incorrect space temperature calibra...

Страница 27: ...warranty A Maintenance Schedule 1 Weekly a Check that fan belts are tight and sheaves are aligned The fan belts can be checked every 30 days after the first 60 days of new belt run in CAUTION Do not...

Страница 28: ...seals and a high operating temperature suggest too much grease Frequency of Lubrication Frequency of lubrication depends upon operating conditions The bearing operating temperature is the best index...

Страница 29: ...ompare the force you have applied with the values given in the table below If the force is between the values for normal tension and 1 1 2 times normal tension the belt tension should be satisfactory...

Страница 30: ...specific mixing plate or plates involved must be replaced c Put system back into operation and view burner while cycling through full firing range This will give a visual check for blocked burner port...

Страница 31: ...inuous low fire 2 Remove cap B and loosen lock screw C Turn D to desired low fire adjustment Clockwise rotation reduces minimum flow rate 3 Tighten screw C replace cap B and reconnect wire to amplifie...

Страница 32: ...ructed the problem can be isolated to the electron ics and this may once again be reviewed in the check list After test remove the test resistor and reconnect the Discharge Air Sensor to terminals 3 a...

Страница 33: ...igure 1 except have TS144 connected in place of jumper Set A1044 MIN temperature selector at least 10 F above outdoor temperature Set A1044 MAX temperature selector at mid range Heater is now under co...

Страница 34: ...s generated by the heater may create hazard ous concentration of carbon monoxide nitrogen dioxide and other combustion products in the heated space If gas fork trucks or other fossil fuel powered equi...

Страница 35: ...35...

Страница 36: ...4830 Transport Drive Dallas TX 75247 Phone 214 638 6010 Fax 214 905 0806 www sterlinghvac com HVAC PRODUCTS...

Отзывы: