GENERAL SAFETY INFORMATION

 Failure to comply with the general

safety information may result in extensive
property damage, severe personal injury, or
death.

 This product must be installed by

a licensed plumber or gas fitter when installed
within the Commonwealth of Massachusetts.

Installation must be made in accordance with
local codes, or in absence of local codes, with
the latest edition of ANSI Standard Z223.1 (N.F.P.A.
No. 54) National Fuel Gas Code.

 All of the ANSI

and NFPA Standards referred to in these installation
instructions are those that were applicable at the
time the design of this appliance was certified.The
ANSI Standards are available from CSA Information
Services 1-800-463-6727. The NFPA Standards are
available from the National Fire Protection Association,
Batterymarch Park, Quincy, MA  02269.

If installed in Canada, the installation must conform with
local building codes, or in the absence of local building
codes, with CGA-B149.1 "Installation Codes for Natural
Gas Burning Appliances and Equipment" or CGA-B149.2
"Installation Codes for Propane Gas Burning Appliances
and Equipment." These unit heaters have been designed
and certified to comply with CGA 2.6.

 Do not alter the unit heater in any

way or damage to the unit and/or severe personal
injury or death may occur!

Disconnect all power and gas

supplies before installing or servicing the heater.
If the power disconnect is out of sight, lock it in
the open position and tag it to prevent unexpected
application of power. Failure to do so could result
in fatal electric shock, or severe personal injury.

 Ensure that all power sources conform

to the requirements of the unit heater, or damage to
the unit will result!

Follow installation instructions CAREFULLY to avoid
creating unsafe conditions. All wiring should be done
and checked by a qualified electrician, using copper wire
only. All gas connections should be made and leak-
tested by a suitably qualified individual, per instructions
in this manual.  Also follow procedures listed on "Gas
Equipment Start-Up Sheet" located in this manual.

Use only the fuel for which the heater is designed (see
rating plate). Using LP gas in a heater that requires
natural gas, or vice versa, will create risk of gas leaks,
carbon monoxide poisoning, and explosion.

 Do not attempt to convert the

heater for use with a fuel other than the one
intended. Such conversion is dangerous, as it
will create the risks previously listed.

Make certain that the power source conforms to the
electrical requirements of the heater.

 Do not depend upon a thermostat

or other switch as sole means of disconnecting
power when installing or servicing heater.  Always
disconnect power at main circuit breaker as
described above.  Failure to do so could result in
fatal electric shock.

Special attention must be given to any grounding
information pertaining to this heater. To prevent the risk
of electrocution, the heater must be securely and
adequately grounded. This should be accomplished by
connecting a ground conductor between the service panel
and the heater. To ensure a proper ground, the grounding
means must be tested by a qualified electrician.

Do not insert fingers or foreign objects into heater or its
air moving device. Do not block or tamper with the heater
in any manner while in operation, or just after it has been
turned off, as some parts maybe hot enough to cause
injury.

This heater is intended for general heating applications
ONLY. It must NOT be used in potentially dangerous
locations such as flammable, explosive, chemical-laden,
or wet atmospheres.

Do not attach ductwork to this product or use it as a
makeup air heater. Such usage voids the warranty and
will create unsafe operation.

In cases in which property damage may result from
malfunction of the heater, a back-up system or
temperature sensitive alarm should be used.

Should overheating occur, or the gas supply fail to shut
off, shut off the manual gas valve to the appliance before
shutting off the electrical supply.

 The open end of piping systems being

purged shall not discharge into areas where there
are sources of ignition or into confined spaces
UNLESS precautions are taken as follows: (1) by
ventilation of the space, (2) control of the purging
rate, (3) elimination of all hazardous conditions.  All
precautions must be taken to perform this operation
in a safe manner!

Unless otherwise specified, the following conversions
may be used for calculating SI unit measurements:
1 foot = 0.305 m
1 inch = 25.4 mm
1 gallon = 3.785 L
1 pound = 0.453 kg
1 psig = 6.894 kPa
1 cubic foot = 0.028m

3

1000 BTU/cu. ft. = 37.5 MJ/m

3

1000 BTU per hour = 0.293 kW
1 inch water column = 0.249 kPa
liter/second = CFM x 0.472
meters/second = FPM ÷ 196.8

Содержание RF-30

Страница 1: ...NT OF INSTALLATION RECORD THE UNIT MODEL AND SERIAL No s IN THE SPACE PROVIDED RETAIN FOR FUTURE REFERENCE INSTALLATION INSTRUCTIONS AND PARTS LIST TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATER...

Страница 2: ...ONS 9 10 VENTING 11 12 13 14 15 16 17 18 19 OPERATION Explanation of Controls and Operation 20 Main Burner Orifice Schedule 21 Adjustments 21 High Altitude Operation 21 22 MAINTENANCE Servicing Cleani...

Страница 3: ...n monoxide poisoning and explosion Do not attempt to convert the heater for use with a fuel other than the one intended Such conversion is dangerous as it will create the risks previously listed Make...

Страница 4: ...10 1 2 10 1 2 10 1 2 184 184 267 267 267 Center Line Electric Connection 10 1 4 10 1 4 16 16 16 260 260 406 406 406 F Discharge Opening Height 10 1 2 10 1 2 16 1 4 16 1 4 16 1 4 267 267 413 413 413 G...

Страница 5: ...ocation in which the facilities for ventilation permit satisfactory combustion of gas proper venting and the maintenance of ambient air at safe limits under normal conditions of use The unit heater sh...

Страница 6: ...or the electrical conduit be used to support the heater or should any other objects i e ladder person lean against the heater gas lines venting system or the electrical conduit for support Failure to...

Страница 7: ...ble 2 Match Length of Pipe in Feet with appropriate Gas Input Cu Ft Hr figure This figure can then be matched to the pipe size at the top of the column Example It is determined that a 67 foot 20 4m ru...

Страница 8: ...National Fuel Gas Code in Canada according to CGA B149 See Tables 1 2 for correct gas piping size and also refer to Tables 3 5 and 6 If gas pressure is excessive on natural gas applications install a...

Страница 9: ...ither affixed to the side jacket or enclosed in the installation instructions envelope Should any original wire supplied with the heater have to be replaced it must be replaced with wiring material ha...

Страница 10: ...0 Unit Sizes with Natural and Propane LP Gas NOTICE See Figures 7 8 and 9 for connecting the thermostat to the unit heater If using a standard low voltage thermostat with a sub base switch for fan con...

Страница 11: ...clothes dryers and any exhaust fans such as range hoods and bathroom exhausts so they shall operate at maximum speed Do not operate a summer exhaust fan Close fireplace damper 4 Follow the lighting in...

Страница 12: ...pipe through unheated spaces 7 When this cannot be avoided insulate the pipe to prevent condensation of moisture on the walls of the pipe Insulate vent pipe runs longer than 10 feet 3m Insulation sho...

Страница 13: ...OT terminate over public walkways or over an area where the condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators relief valves or other equipmen...

Страница 14: ...Length Vertical Rise Distance Size in Ft In from Wall 30 4 1 4 12 36 4 1 8 18 36 4 2 4 12 36 4 2 8 18 36 45 4 1 10 18 36 4 2 5 18 36 5 2 10 12 36 60 5 2 10 12 36 75 5 2 10 24 36 90 5 1 10 24 24 5 2 1...

Страница 15: ...15 Figure 14 Vent Support D 06839A...

Страница 16: ...gh to prevent degradation of the building material by flue gases The vent terminal must be at least 1 foot 305mm above grade or in snow areas at least 3 feet 1m above the snow line to prevent blockage...

Страница 17: ...e 15 Category III Horizontal Venting Requirements Using Single Wall Vent Pipe Figure 15A Category III Horizontal Venting Requirements Using Type B Double Wall Vent Pipe Figure 15B Type B Draft Hood Co...

Страница 18: ...18 Figure 16 Figure 17 VENTING continued...

Страница 19: ...19 VENTING continued Figure 18 Figure 19...

Страница 20: ...imit switch interrupts the flow of electric current to the control board the unit will begin a post purge period When the post purge period ends the power venter motor is de energized 7 The fan operat...

Страница 21: ...ew cap 2 PROPANE GAS An exact manifold pressure of 10 0 inches W C 2 5 kPa must be maintained for proper operation of the unit heater If the unit is equipped with a pressure regulator on the combinati...

Страница 22: ...726 711 696 Manifold Pressure In W C PROPANE LP GAS Heating Value BTU Cu ft Altitude Feet Table 6 Manifold Pressure In W C Heating Value BTU Cu ft 10 0 10 0 10 0 10 0 10 0 9 9 9 7 9 6 9 5 2 278 2 237...

Страница 23: ...ground wires and connections 8 Check both for wiring according to diagram check for 24V at gas valve terminals during trial for ignition period if present and valve does not open Replace valve 1 Refe...

Страница 24: ...terminal strip 4 Check air movement across heat exchanger Check voltage and amps at the fan motor Check gas input to ensure unit is not over fired Check heat exchanger to ensure unit is not dirty 5 C...

Страница 25: ...open when unit is running or is the switch open during start up 4 Check for 24v on line side of the high limit Constant voltage should be recorded if not control board is suspect Check flash code 1 Ch...

Страница 26: ...p fuse on circuit board 1 Common side of transformer grounded to chassis 2 Loose spark ignitor 1 Gas supply off or gas supply pressure too low 2 Flame sense rod contaminated or loose wire 3 Gas valve...

Страница 27: ...Guard 16 Standard Fan 17 Fan Guard Motor Mount Hardware Kit 18 Flue Collector 19 Power Venter Drafter Ass y 20 Flue Collar Ass y 21 Vinyl Tubing Pressure Switch 22 Power Venter Mounting Plate 23 Louve...

Страница 28: ...23 Internal Furnace Components Figure 21 Propeller Parts Figure 22 Component Parts Figure 24 Power Ventor Assembly D4791 D4810 NOTE No rubber grommets are equipped with the 30 and 45 unit sizes Pressu...

Страница 29: ...ny expenses including labor or material incurred during removal or reinstallation of the Product c to any damage due to corrosion by chemicals including halogenated hydrocarbons precipitated in the ai...

Страница 30: ...ll field installed controls been installed Do you understand all the controls on this equipment If not contact your wholesaler or rep DO NOT START this equipment unless you fully understand the contro...

Страница 31: ......

Страница 32: ......

Отзывы: