Sterling M) Скачать руководство пользователя страница 10

10

ELECTRICAL CONNECTIONS

* Thermostat wires tagged ÒWÓ and ÒGÓ must be 

connected together except when using a general 

purpose ÒSPDTÓ 24VAC relay and a standard thermostat 

with subbase, or when using Honeywell T834H-1009 or 

T834H-1017 thermostats. Also refer to Figure 7 for other 

wiring connections.

Figure 7 - C1267G

THERMOSTAT HEAT ANTICIPATOR ADJUSTMENTS:

The initial heat anticipator setpoint should equal the 

thermostat's current amperage draw when the unit is 

firing. This setpoint should be measured for the best 

results. Use the recommended ranges as a guide. If 

further information is needed, consult your thermostat 

manufacturer's instructions.

Recommended Heat Anticipator Setting Ranges:

 

 

25 ft. (7.6m) 

50 ft. (15.2m)

Gas Ignition Type 

T'stat Wiring 

T'stat Wiring

For Natural Vent Units:

Standing Pilot 

0.68 to 0.75 A 

0.73 to 0.81 A

Intermittent (Spark) 

0.76 to 0.81 A 

0.81 to 0.91 A

FAN TIME  DELAY  CONTROL

Leads from time delay controls are factory wired to the 

junction box (when ordered as an optional component). 

The fan control is a time delay relay (approximately 45 

seconds ON, 65 seconds OFF). The fan control is rated 

at 17 amps.  

NOTICE: The start-up fan delay must not exceed 90 
seconds from a cold start.

IMPORTANT: For all wiring connections, refer to 
the wiring diagram that your unit is equipped with 
(either affi xed to the side jacket or enclosed in your 
unit's installation instruction envelope). Should any 
original wire supplied with the heater have to be 
replaced, it must be replaced with wiring material 
having a temperature rating of at least 105°C. 

Should any high limit or blocked vent (spill) switch 
wires have to be replaced, they must be replaced 
with wiring material having a temperature rating of 
200°C minimum.

 

HAZARDOUS VOLTAGE! 

DISCONNECT ALL ELECTRIC 
POWER INCLUDING REMOTE 
DISCONNECTS BEFORE 
SERVICING. Failure to 
disconnect power before 
servicing can cause severe 
personal injury or death.

Standard units are shipped for use on 115  volt, 60 hertz 

single phase electric power. The motor name-plate and 

electrical rating on the transformer should be checked 

before energizing the unit heater electrical system. All 

external wiring must conform to the latest edition of ANSI/

NFPA No. 70, National Electrical Code and applicable 

current local codes; in Canada, to the Canadian  Electrical 

Code, Part 1 CSA Standard C22.1.

 Do not use any tools (i.e. screwdriver, 

pliers, etc.) across the terminals to check for power.  
Use a voltmeter.

It is recommended that the electrical power supply 

to each unit heater be provided by a separate, fused 

and permanently live electrical circuit. A disconnect 

switch of suitable electrical rating for each unit heater 

should be located as close to the gas valve and controls 

as possible. Each unit heater must be electrically 

grounded in accordance with the latest edition of 

the National Electric Code, ANSI/NFPA No. 70 or CSA 

Standard C22.1. Sample wiring connections are depicted 

in Figure 7.

THERMOSTAT WIRING AND LOCATION

NOTICE: The thermostat must be mounted on a 
vertical vibration-free surface free from air currents 
and in accordance with the furnished instructions.

Mount the thermostat approximately 5 feet (1.5m) above 

the floor in an area where it will be exposed to a free 

circulation of average temperature air. Always refer to the 

thermostat instructions as well as our unit wiring diagram 

and wire accordingly. Avoid mounting the thermostat in 

the following locations:

1.  Cold areas - Outside walls or areas where drafts may 

affect the operation of the control.

2.  Hot areas - Areas where the sun's rays, radiation, or 

warm air currents may affect control operation.

3.  Dead areas - Areas where air cannot circulate freely, 

such as behind doors or in corners.

Содержание M)

Страница 1: ...nspect and correct any problems that may be found Install operate and maintain unit in accordance with manufacturer s instructions to avoid exposure to fuel substances or substances from incomplete co...

Страница 2: ...intenance which are important to equipment but not related to personal injury hazards International as providing a minimum of 80 thermal efficiency and approved for use in California when equipped wit...

Страница 3: ...a all external wiring must conform to the Canadian Electric Code Part 1 CSA Standard C22 1 All wiring should be done and checked by a qualified electrician using copper wire only All gas connections s...

Страница 4: ...1 4 38 1 4 702 702 702 702 826 826 914 914 914 972 972 959 972 972 E Hanging Distance Width 8 5 8 8 5 8 14 1 8 14 1 8 14 3 4 17 1 2 17 1 2 20 1 4 23 25 1 2 28 1 4 33 3 4 39 1 4 44 3 4 219 219 359 359...

Страница 5: ...edition of NFPA No 88B Repair Garages In parking structures unit heaters must be installed so that the burner flames are located a minimum of 18 inches 457mm above the floor or protected by a partiti...

Страница 6: ...t Heater shall be located with respect to building construction and other equipment so as to permit access to the Unit Heater Clearance between walls and the vertical sides of the Unit Heater shall be...

Страница 7: ...a shut off valve to isolate the unit while conducting gas pressure leak tests These valves may not be completely shut off exposing the unit gas valve to excessive pressure and damage Table 3 Gas Pipe...

Страница 8: ...The manual main shutoff valve must be located external to the jacket See gure 5 8 Make certain that all connections have been adequately doped and tightened Do not overtighten the inlet gas piping in...

Страница 9: ...223 1 or applicable provisions of local building codes See below for Canadian Installations CARBON MONOXIDE Your venting system must not be block by any snow snow drifts or any foreign matter Inspect...

Страница 10: ...NNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING Failure to disconnect power before servicing can cause severe personal injury or death Standard units are shipped for use on 115...

Страница 11: ...o the OFF position 2 Turn off the electricity 3 To relight follow the START UP instructions above EXPLANATION OF CONTROLS see Figure 8 1 The unit heater is equipped with a combination gas control valv...

Страница 12: ...ri ce 6 Transformer Junction Box 7 Pliot Tubing 9 High Limit Switch 9A E C O Not Shown White Rodgers Valve Only 10 Pilot Burner Assembly 11 Blocked Vent Spill Switch Honeywell Standing Pilot Gas Valve...

Страница 13: ...ONAL INTERMITTENT SPARK PILOT IGNITION 13 EXPLANATION OF CONTROLS see Figure 9 1 The unit heater is equipped with a dual automatic gas valve and electric ignition device separate from the gas valve on...

Страница 14: ...mit 14 Blocked Vent Spill Switch This safety device is located on the rear header plate of the heat exchanger air inlet side This safety device is located in the upper right corner of the right jacket...

Страница 15: ...Adjustment of the pressure regulator is not normally necessary since it is preset at the factory However eld adjustment may be made as follows a Attach manometer at pressure tap plug adjacent to the c...

Страница 16: ...o 4 drops of electric motor oil as follows a Light Duty After 3 years or 25 000 hours of operation b Average Duty Annually after 3 years or 8 000 hours of operation c Heavy Duty Annually after 1 year...

Страница 17: ...L SWITCH LOCATION Figure 12 Components Parts P 14 115 1 60 MOTOR P 15 FAN GUARD P 16 FAN BLADE P 17 HARDWARE 225 400 unit sizes only require a baf e Figure 13 Figure 14 Internal Furnace Components Bur...

Страница 18: ...er 2 Reduce pilot gas Refer to Operation 3 Replace ori ce 4 Reset manifold pressure Refer to Operation Replace regulator section of combination gas valve or complete valve or Check with local gas supp...

Страница 19: ...ruction label adjacent to gas valve 5 Remove pilot ori ce Clean with compressed air or solvent Do not ream 6 Refer to Operation 7 Determine and correct cause of overheat condition Replace E C O device...

Страница 20: ...e thermostat 4 There should be NO ducts attached to the front of this heater Check air movement through heat exchanger Check voltage to fan motor Clean fan blade and heat exchanger and oil fan motor 1...

Страница 21: ...rk is applic able Y Pilot lights Main valve does not energize Spark units only Z Hi Limit switch tripping 1 Refer to Operation 2 Check motor voltage with fan running Should be 115 volts AC 3 Refer to...

Страница 22: ...tructions or has been altered or modi ed in any way b to any expenses including labor or material incurred during removal or reinstallation of the defective Product or parts thereof c to any damage du...

Страница 23: ...nderstand the controls GAS EQUIPMENT START UP GENERAL With power and gas off Make certain all packing has been removed Tighten all electrical terminals and connections Check damper linkages for tightn...

Страница 24: ......

Отзывы: