Sterlco 30RAN010-055 AquaSnap Скачать руководство пользователя страница 13

13

AIR SEPARATION  — For proper system operation, it is
essential that water loops be installed with proper means to
manage air in the system. Free air in the system can cause
noise, reduce terminal output, stop flow, or even cause pump
failure due to pump cavitation. For closed systems, equipment
should be provided to eliminate all air from the system. 

The amount of air that water can hold in solution depends

on the pressure and temperature of the water/air mixture. Air is
less soluble at higher temperatures and at lower pressures.
Therefore, separation can best be done at the point of highest
water temperature and lowest pressure. Typically, this point
would be on the suction side of the pump as the water is return-
ing from the system or terminals. Generally speaking, this is
the best place to install an air separator, if possible.

1. Install automatic air vents at all high points in the system.

(If the 30RA unit is located at the high point of the
system, a vent can be installed on the piping entering the
heat exchanger on the ¼-in. NPT female port.)

2. Install an air separator in the water loop, at the place

where the water is at higher temperatures and lower
pressures — usually in the chilled water return piping.
On a primary-secondary system, the highest temperature
water is normally in the secondary loop, close to the
decoupler. Preference should be given to that point on the
system (see Fig. 12). In-line or centrifugal air separators
are readily available in the field.

It may not be possible to install air separators at the place of

lowest pressure and highest temperature. In such cases, prefer-
ence should be given to the points of highest temperature. It is
important that pipe be sized correctly so that free air can be
moved to the point of separation. Generally, a water velocity of
at least 2 feet per second will keep free air entrained and
prevent it from forming air pockets.

Automatic vents should be installed at all physically elevat-

ed points in the system so that air can be eliminated during
system operation. Provision should also be made for manual
venting during the water loop fill. It is important that the
automatic vents be located in accessible locations for mainte-
nance purposes, and that they be located where they can be
prevented from freezing.
WATER CONNECTIONS — The water connections are cop-
per or brass FPT. Any connecting pipe to the 30RA pump
package must be of a material that will not cause any galvanic
corrosion. For this reason, galvanized steel pipe or other dis-
similar metals must not be used unless joined by a dielectric
coupling. The connection sizes for the 30RA unit sizes 010-
030 are 2-in. FPT. Sizes 032-055 use 2

1

/

2

-in. FPT.

Follow the steps below when connecting pipe to the unit

water connections:

1. Remove side panel(s) of unit to access the piping area.
2. Remove access covers of pump box.
3. Use a backup wrench on internal water connections to

prevent twisting of internal piping, using a good sealant
that will also allow for disconnecting the pipes if needed.

4. After connection is made, replace access covers of pump

box and side panels of unit.

WATER SYSTEM CLEANING — Proper water system
cleaning is of vital importance. Excessive particulates in the
water system can cause excessive pump seal wear, reduce or
stop flow, and cause damage of other components. Water
quality should be maintained within the limits indicated in
Table 2.

1. Install a temporary bypass around the chiller to avoid cir-

culating dirty water and particulates into the pump pack-
age and chiller during the flush. Use a temporary circulat-
ing pump during the cleaning process. Also, be sure that
there is capability to fully drain the system after cleaning.
(See Fig 13.)

2. Be sure to use a cleaning agent that is compatible with all

system materials. Be especially careful if the system
contains any galvanized or aluminum components. Both
detergent-dispersant and alkaline-dispersant cleaning
agents are available.

3. It is a good idea to fill the system through a water meter.

This provides a reference point for the future for loop
volume readings, but it also establishes the correct
quantity of cleaner needed in order to get the required
concentration.

4. Use a feeder/transfer pump to mix the solution and fill the

system. Circulate the cleaning system for the length of
time recommended by the cleaning agent manufacturer.

a. After cleaning, drain the cleaning fluid and flush the

system with fresh water.

b. A slight amount of cleaning residue in the system can

help keep the desired, slightly alkaline, water pH of 8
to 9. Avoid a pH greater than 10, since this will
adversely affect pump seal components.

c. A side stream filter is recommended (see Fig. 14)

during the cleaning process. Filter side flow rate
should be enough to filter the entire water volume
every 3 to 4 hours. Change filters as often as neces-
sary during the cleaning process.

d. Remove temporary bypass when cleaning is

complete.

A strainer with a blow-down valve is standard on all 30RA

units, both with and without hydronic packages. The blow-
down valve allows removal of particulates caught in the strain-
er without complete removal of the screen. A female NPT
connection is provided on the valve, allowing hose connection
for drainage outside the unit.

 The Sterlco ComfortLink™ controls provided have a built-

in feature to remind building owners or operators to clean the
strainer by discharging the blow-down valve at a pre-set time
interval. Properly installed and cleaned systems will rarely
need the strainer cleaned after the initial fill. This time interval
is user-configurable.

Table 2 — Water Quality Characteristics

and Limitations

 *Sulfides in the water quickly oxidize when exposed to air, requiring that

no agitation occur as the sample is taken. Unless tested immediately
at the site, the sample will require stabilization with a few drops of one
Molar zinc acetate solution, allowing accurate sulfide determination up
to 24 hours after sampling. A low pH and high alkalinity cause system
problems, even when both values are within the ranges shown. The
term pH refers to the acidity, basicity, or neutrality of the water supply.
Below 7.0, the water is considered to be acidic. Above 7.0, water is
considered to be basic. Neutral water contains a pH of 7.0.

†Dissolved carbon dioxide can either be calculated from the pH and

total alkalinity values, shown below, or measured on the site using a
test kit. Dissolved Carbon Dioxide, PPM = TA x 2

[(6.3-pH)/0.3]

 where TA

= Total Alkalinity, PPM as CaCO

3

.

 WATER CHARACTERISTIC

QUALITY LIMITATION

Alkalinity (HCO

3

-

)

70 – 300 ppm

Sulfate (SO

4

2-

)

Less than 70 ppm

HCO

3

-

/SO

4

2-

Greater than 1.0

Electrical Conductivity

10 – 500

 µ

S/cm

pH

7.5 – 9.0

Ammonium (NH

3

)

Less than 2 ppm

Chorides (Cl

-

)

Less than 300 ppm

Free chlorine (Cl

2

)

Less than 1 ppm

Hydrogen Sulfide (H

2

S)*

Less than 0.05 ppm

Free (aggressive) Carbon
Dioxide (CO

2

)†

Less than 5 ppm

Total Hardness (dH)

4.0 – 8.5

Nitrate (NO

3

)

Less than 100 ppm

Iron (Fe)

Less than 0.2 ppm

Aluminum (Al)

Less than 0.2 ppm

Manganese (Mn)

Less than 0.1 ppm

Содержание 30RAN010-055 AquaSnap

Страница 1: ...ture and on tags stickers and labels attached to the equipment Follow all safety codes Wear safety glasses and work gloves Keep quenching cloth and fire extinguisher nearby when brazing Use care in handling rigging and setting bulky equipment See Tables 1A 1D for Physical Data Refer to Fig 2 for unit weights INSTALLATION Step 1 Rig and Place the Unit RIGGING Preferred method is with spreader bars ...

Страница 2: ...48 018 110 146 203 194 653 018 117 161 218 215 711 022 174 237 198 186 795 022 187 268 215 211 881 025 181 241 204 198 824 025 194 272 221 224 911 030 193 268 210 207 878 030 208 308 224 241 981 035 374 320 302 425 1421 035 422 356 341 474 1593 040 381 325 307 440 1453 040 429 361 346 490 1626 045 425 351 368 447 1591 045 473 387 408 496 1764 050 432 356 380 466 1634 050 479 394 421 514 1808 055 4...

Страница 3: ...ti freeze in cooler to prevent freezing of residual water 4 At the beginning of the next cooling season refill cooler and add recommended inhibitor Fig 3 Unit Rigging Label Detail C Copper Finned Condenser Coil UNIT MAX SHIP WT W O PACKAGING MAX SHIP WT W PACKAGING LIFTING HOLES CENTER OF GRAVITY Lb Kg Lb Kg in mm in mm in mm in mm 30RA032 2791 1266 2965 1345 105 44 2678 87 00 2210 43 87 1114 46 0...

Страница 4: ...a sq ft 23 23 23 32 32 40 55 55 64 64 80 HYDRONIC MODULE Optional Pump s Strainer W Blowdown Valve Expansion Tank Pressure Gages Drain and Vent Plugs Flow Switch and Balance Valve Pump Single or Dual Close Coupled Centrifugal Pump s 3500 Rpm Expansion Tank Volume gal 4 4 10 3 UNIT 30RA 010 015 018 022 025 032 035 042 045 REFRIGERANT TYPE R 22 TXV Controlled System Refrigerant Charge lb Ckt A Ckt B...

Страница 5: ... 2 97 2 97 3 72 5 11 5 11 5 95 5 95 7 43 HYDRONIC MODULE Optional Pump s Strainer W Blowdown Valve Expansion Tank Pressure Gages Drain and Vent Plugs Flow Switch and Balance Valve Pump Single or Dual Close Coupled Centrifugal Pump s 58 3 r s Expansion Tank Volume L 16 5 39 UNIT 30RA 010 015 018 022 025 032 035 042 045 REFRIGERANT TYPE R 22 TXV Controlled System Refrigerant Charge kg Ckt A Ckt B 8 ...

Страница 6: ...solid surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Страница 7: ...lid surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Страница 8: ...d surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to out side edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Страница 9: ...lid surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Страница 10: ...olid surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Страница 11: ...id surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Страница 12: ...should follow sound engineer ing practice as well as applicable local and industry standards Improperly designed or installed systems may cause unsatis factory operation and or system failure Consult a water treat ment specialist or appropriate literature for information regard ing filtration water treatment and control devices Figure 10 shows a typical installation with components that might be i...

Страница 13: ...tall a temporary bypass around the chiller to avoid cir culating dirty water and particulates into the pump pack age and chiller during the flush Use a temporary circulat ing pump during the cleaning process Also be sure that there is capability to fully drain the system after cleaning See Fig 13 2 Be sure to use a cleaning agent that is compatible with all system materials Be especially careful i...

Страница 14: ...a pressure drop between the tank and the pump must be accounted for NOTE If the system requires a pre charge greater than 40 psig increase pressure as described below Expansion Tank Pre Charge To pre charge the expansion tank do the following steps 1 Check the tank air pressure at the pre charge connection with an accurate pressure gage Adjust as needed 2 If additional pressure is required charge ...

Страница 15: ...on of the city water system should be consulted and followed to prevent contamination of the public water supply This is especially important when anti freeze is used in the system Set Water Flow Rate Once the system is cleaned pressur ized and filled the flow rate through the chiller needs to be established On units with the hydronic package this can best be done using the balancing valve In orde...

Страница 16: ...s available from the factory as an accessory These tanks are designed to physically fit beneath the corresponding 30RA unit taking up the same footprint Available volumes are as follows 30RA010 018 110 gallons 30RA022 030 152 gallons 30RA032 055 305 gallons Maximum Loop Volume Since the minimum size of the expansion tank is dependent upon loop volume units with the integrated hydronic kit must not...

Страница 17: ...tion where ambient tempera tures are expected to fall below 32 F Consult local water treat ment specialist on characteristics of the system water and add a recommended inhibitor to the chilled water 1 If the pump will be subjected to freezing temperatures steps must be taken to prevent freeze damage If the pump will not be used during this time it is recommend ed to drain the pump and hydronic pac...

Страница 18: ... Management Module Used for any of the following types of temperature reset demand limit and ice features 4 to 20 mA leaving fluid temperature reset requires field supplied 4 to 20 mA generator 4 to 20 mA cooling set point reset requires field supplied 4 to 20 mA generator Discrete inputs for 2 step demand limit requires field supplied dry contacts 4 to 20 mA demand limit requires field supplied 4...

Страница 19: ...92 2 125 311 3 110 96 2 125 110 97 4 125 110 97 4 125 110 99 6 125 110 208 230 60 187 253 1 102 4 125 316 4 125 106 8 125 125 108 2 125 125 108 2 125 125 110 6 150 125 460 60 414 506 1 50 3 70 160 0 60 52 3 70 80 52 9 70 80 52 9 70 80 54 0 70 80 575 60 518 633 1 41 2 50 140 4 50 42 8 50 50 43 3 50 50 43 3 50 50 44 2 60 50 380 60 342 418 1 65 2 90 202 2 80 67 6 90 80 68 4 90 80 68 5 90 80 69 7 90 8...

Страница 20: ...60 2 1 9 1 3 0 380 60 2 2 9 1 4 6 042 380 415 50 2 2 3 2 2 3 230 50 2 3 8 2 3 8 045 230 60 2 4 8 2 4 8 208 230 60 2 5 3 2 5 3 460 60 2 2 4 2 2 4 575 60 2 1 9 2 1 9 380 60 2 2 9 2 2 9 380 415 50 2 2 3 2 2 3 230 50 2 3 8 2 3 8 050 230 60 2 4 8 2 4 8 208 230 60 2 5 3 2 5 3 460 60 2 2 4 2 2 4 575 60 2 1 9 2 1 9 380 60 2 2 9 2 2 9 055 230 60 2 4 8 2 4 8 208 230 60 2 5 3 2 5 3 460 60 2 2 4 2 2 4 575 60 ...

Страница 21: ...2 205 34 1 225 41 6 310 035 230 60 29 4 265 36 7 265 43 8 380 208 230 60 32 7 265 40 8 265 48 7 380 460 60 14 6 120 20 2 135 23 8 175 575 60 12 2 80 16 6 120 18 9 140 380 60 18 9 155 26 4 170 30 1 235 380 415 50 24 2 175 24 2 175 24 2 175 230 50 41 6 310 41 6 310 41 6 310 040 230 60 36 7 265 36 7 265 43 8 380 208 230 60 40 8 265 40 8 265 48 7 380 460 60 20 2 135 20 2 135 23 8 175 575 60 16 6 120 1...

Страница 22: ...emove the orange harness wire from TB5 1 and wire contacts in series as shown The contacts must be rated for dry circuit application capable of handling a 24 vac load up to 50 mA 5 Terminals 11 and 13 of TB5 are for control of Chilled Water Pump 1 CWP1 starter Terminals 13 and 15 of TB5 are for control of Chilled Water Pump 2 CWP2 starter The maximum load allowed for the chilled water pump relay i...

Страница 23: ...ange harness wire from TB5 1 and wire contacts in series as shown The contacts must be rated for dry cir cuit application capable of handling a 24 vac load up to 50 mA 5 Terminals 11 and 13 of TB5 are for control of Chilled Water Pump 1 CWP1 starter Termi nals 13 and 15 of TB5 are for control of Chilled Water Pump 2 CWP2 starter The maximum load allowed for the chilled water pump relay is 75 va se...

Страница 24: ...ns 6 and 7 for details Do not use compressor to evacuate system REFRIGERANT CHARGE Refer to Tables 1A 1D Immediately ahead of filter drier in each circuit is a factory installed liquid line service valve Each valve has a 1 4 in Schrader connection for charging liquid refrigerant If unit is equipped with a Motormaster V control the pres sure transducer has to be removed from the liquid line Schrade...

Страница 25: ... PUMP UNITS 30RA032 055 PRESSURE DROP SINGLE PUMP UNITS 30RA010 030 PRESSURE DROP SINGLE PUMP UNITS 30RA010 030 LEGEND 1 30RA010 3 30RA018 5 30RA025 7 30RA032 30RA035 9 30RA042 30RA045 11 30RA055 2 30RA015 4 30RA022 6 30RA030 8 30RA040 10 30RA050 Use the following formula to convert Feet of water to psi Ft of water 4335 psi Use the following formula to convert psi to Feet of water Psi 2 306 Ft of ...

Страница 26: ... DUAL PUMP UNITS SIZES 30RA032 055 PRESSURE DROP SINGLE PUMP UNITS 30RA032 055 PRESSURE DROP SINGLE PUMP UNITS 30RA032 055 LEGEND 1 30RA010 3 30RA018 5 30RA025 7 30RA032 30RA035 9 30RA042 30RA045 11 30RA055 2 30RA015 4 30RA022 6 30RA030 8 30RA040 10 30RA050 Use the following formula to convert Feet of water to psi Ft of water 4335 psi Use the following formula to convert psi to Feet of water Psi 2...

Страница 27: ... Accessory Storage Tanks 1 ACCESSORY TANK FLOW RATE gpm PRESSURE DROP ft wg 30RA 900 010 30RA 900 001 009 100 0 10 0 1 0 0 1 10 100 1000 0 1 1 0 10 0 1 0 10 0 ACCESSORY TANK FLOW RATE L s PRESSURE DROP kPa 30RA 900 010 30RA 900 001 009 100 0 ...

Страница 28: ...continue or change at any time specifications or designs without notice and without incurring obligations PC 903 Catalog No 533 00045 Printed in U S A Form 30RA 12SI Pg 28 7 02 Replaces 30RA 1SI Book 2 Tab 5c Copyright 2002 Sterling Sterlco ...

Отзывы: