Sterilight Viqua S2Q-OZ Скачать руководство пользователя страница 7

Installation

7

Your spa may have come equipped with a 1/4” NPT threaded inlet on the air line, if not you may be required to drill and tap 

a 1/4” NPT hole to install the 1/4” NPT to barbed adaptor that comes with the OE-001 kit. The location for the ozone 

injection point will be decided by where you choose to place the adapter. Normally the placement of the adaptor will allow 

the ozone to flow through only one side of the tub. If possible, choose the air line with the most attached jets to take full 

advantage of the injection points. If drilling, place the adaptor downstream of the air vent controls. Your spa may have also 

come supplied with a garden hose threaded tap on the HIGH PRESSURE SIDE of the pump, which is commonly referred 

to as a power drain. If your spa has no power drain, then the optional saddle clamp must be installed on the HIGH 

PRESSURE side of the pump as close to the pump as possible. If you are not sure which is the high pressure side, be sure 

to contact your dealer to avoid any irreversible drilling. After you have located or installed the barbed adaptor on the air line 

and the adaptor on the water line, simply hook up the eduction system as the diagram illustrates. Make sure all the 

connections are sealed so no leaking will occur.
After all the water connections have been made you must choose a location for your ozonator. If you are locating the 

ozonator below the water level an approved check valve (model #CHK-01B) must be used on the ozone induction air line 

from the ozonator and the unit be hooked into an approved ground fault protected electrical supply. After the system is 

totally installed, re-fill the tub. When tub level is correct, thoroughly inspect the system for leaks. If your spa was equipped 

with a power drain, remember you must turn on the tap to allow water to pump through the system. If no leaks are found 

turn the power on to the tub and open the jet that has the ozonated water connected to it and re-check for leaks. When the 

unit is on high speed you should be able to detect suction at the inlet on the ozonator. If it can’t be detected, take the air line 

off at the venturi to check the air draw into the venturi at high speed. At low speed the air draw will be dramatically reduced, 

don’t be alarmed, there should only be a slight air draw at low speed. The retention loop has been incorporated to keep the 

ozone in contact with the water prior to induction into the spa. This will cause excellent ozone absorption and mixing. If you 

have a dominant ozone smell on high speed you simply need to increase the number of loops with an optional connector 

until the ozone smell is almost eliminated. You should smell a slight hint of ozone at the jet that is introducing the ozone. If 

you have no smell at all, simply cut the loop number back until you do smell a hint of ozone at high speed. ozone has a 

distinct fresh or pungent odour.

Figure 2 

Figure 2 Pressure Differential System

Содержание Viqua S2Q-OZ

Страница 1: ...o Canada N1L 1R1 t 1 519 763 1032 tf 1 800 265 7246 US and Canada only t 31 73 747 0144 Europe only f 1 519 763 5069 e mail info viqua com www viqua com Models S2Q OZ S2Q OZ 2 S8Q OZ S8Q OZ 2 Owner s Manual Powered by 520025_RevP ...

Страница 2: ...QUA replacement lamps Use of widely available non genuine replacement lamps has been shown to damage the control module of VIQUA UV equipment An increasing number of calls to VIQUA Technical Support are connected with non genuine lamps being used unknowingly as replacements Damage arising from the use of non genuine lamps poses a safety risk and is not covered by equipment warranty Unless the UV e...

Страница 3: ...c Shock To avoid possible electric shock special care should be taken since water is present near the electrical equipment Unless a situation is encountered that is explicitly addressed by the provided maintenance and troubleshooting sections do not attempt repairs yourself refer to an authorized service facility Risk of electric shock Connect this ozone generator in accordance with the installati...

Страница 4: ... 1 ft above the maximum water level to prevent water from contacting electrical equipment Install in accordance with the installation instructions The UV lamp inside the UV system is rated at an effective life of approximately 9000 hours To ensure continuous protection replace the UV lamp annually The UV system is not to be used or played with by children Persons with reduced physical sensory or m...

Страница 5: ...inside of a sealed stainless steel ozone generator cell which protects the electrical components and outer case from the oxidizing effects of ozone 185nm ultraviolet lamps can be replaced or cleaned by simply loosening the gland nuts from the ends of the stainless steel ozone generating cell removing the old lamp and re installing or installing a new UV lamp Figure 1 System Components Item Descrip...

Страница 6: ...o the generator in case the outlet line is blocked Select a location two feet above the water level and with access to a properly grounded electrical outlet The unit can be mounted vertically or horizontally with the connection ports facing down Mount the chamber to the wall using the cell clamp and mounting screws included with your system If mounting the unit to drywall use a plug or an expansio...

Страница 7: ...e locating the ozonator below the water level an approved check valve model CHK 01B must be used on the ozone induction air line from the ozonator and the unit be hooked into an approved ground fault protected electrical supply After the system is totally installed re fill the tub When tub level is correct thoroughly inspect the system for leaks If your spa was equipped with a power drain remember...

Страница 8: ...he ultraviolet output of the UV lamp gradually reduces with usage However there is a wide variation in the actual amount of ozone required because of differences in the volume of water and the number of people using the hot tub or spa The condition of the water is a reasonable indicator to tell when a new lamp or maintenance is needed A large increase in the amount of treatment chemical or a chang...

Страница 9: ... counter clockwise Carefully remove the o ring from the end of the lamp note that it may be stuck to the lamp and carefully remove the UV lamp from the stainless steel reactor chamber Note Lamp Cleaning Carefully clean the lamp with a clean lint free wiper dampened with vinegar New lamps should also be wiped clean to remove dust Do not handle the UV lamp with bare hands to avoid leaving oil and gr...

Страница 10: ...d reapply power to the controller until you see then release timer reset button A 5 second delay will occur until you hear an audible tone and LED display will read once again Note Even though the alarm on the system can be deferred for a period of time it is important to address each and every alarm condition as they are indicating that there is a potential problem with the system and should be r...

Страница 11: ...istry Cloudy water Total dissolved solids and particulates level is too high Clean or replace filter drain and replace water Incorrect pH levels Adjust pH to be between 7 4 7 6 Green water Excessive algae build up Shock water DISPLAY FAULT MODES LED display reads A3 UV lamp life expired countdown is at 0 days Press reset button for a deferred alarm replace UV lamp LED display is blank Controller i...

Страница 12: ...ardware components to be free from defects in material and workmanship for a period of three 3 years from the date of purchase During this time VIQUA will repair or replace at its option any defective parts covered by the warranty Please return the defective part to your dealer who will process your claim One Year Limited Warranty for Lamps Sleeves and UV Sensors VIQUA warrants lamps sleeves and U...

Страница 13: ...425 Clair Rd W Guelph Ontario Canada N1L 1R1 t 1 519 763 1032 tf 1 800 265 7246 US and Canada only t 31 73 747 0144 Europe only f 1 519 763 5069 e mail info viqua com www viqua com ...

Отзывы: